<br />HEIGHT REQUIREMENTS
<br />FOR WALL -MOUNTED DEVICES
<br />1. EACH MANUAL FIRE ALARM BOX SHALL BE SECURELY MOUNTED. THE OPERABLE PART FOR EACH MANUAL
<br />FIRE ALARM BOX SHALL NOT BE MORE THAN ±48" (1.37 M) ABOVE FLOOR LEVEL.
<br />2. WHERE CEILING HEIGHTS ALLOW, WALL -MOUNTED APPLIANCES SHALL HAVE THEIR BOTTOMS AT ±80" A.F.F.
<br />3. WALL -MOUNTED VISUAL APPLIANCES SHALL BE MOUNTED ±80 IN. (2 M) FROM THE
<br />BOTTOM OF THE DEVICE TO THE FINISHED FLOOR.
<br />4. WHERE COMBINATION AUDIBLE/VISIBLE APPLIANCES ARE INSTALLED, THE LOCATION OF THE INSTALLED
<br />APPLIANCE SHALL BE DETERMINED BY VISIBLE APPLIANCES.
<br />STROBE HORN/STROBE
<br />0 0
<br />CONTROL 1 VESDA
<br />PANEL PANEL
<br />MANUAL
<br />PULL
<br />F
<br />fso„
<br />t 70"
<br />f 48"
<br />HEIGHT OF DEVICES DETAIL
<br />N.T.S.
<br />CODE SUMMARY:
<br />FIRE SUPPRESSION SYSTEM DESIGNED IN ACCORDANCE WITH:
<br />1. FLORIDA FIRE PREVENTION CODE, 2010 EDITION.
<br />2. NFPA 72, 2007 EDITION
<br />3. RULES & REGULATIONS OF THE STATE FIRE MARSHALS
<br />OFFICE, AND ALL STATE AND LOCAL CODES.
<br />INSTALLATION NOTE:
<br />THE INTENT OF THE INFORMATION SHOWN ON THIS DRAWING IS
<br />TO PROVIDE THE SYSTEM INSTALLER WITH THE NECESSARY
<br />INFORMATION AS HOW TO WIRE FIELD DEVICES. ACTUAL CONDUIT
<br />ROUTING, CIRCUIT DIVISION, AND FIELD DEVICE LOCATIONS
<br />SHALL BE DETERMINED BY THE SYSTEM INSTALLER IN THE FIELD.
<br />FRONT -VIEW SECTION A -A
<br />F— A ,
<br />3
<br />VA L2 4
<br />A
<br />1. GYPSUM WALL ASSEMBLY (U.L CLASSIFIED U300 OR U400 SERIES)
<br />1-HR OR 2-HR FIRE -RATING) (2-HR SHOWN).
<br />2. PENETRATING ITEM TO 8E ONE OF THE FOLLOWING:
<br />A. MAXIMUM 30" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER).
<br />B. MAXIMUM 30" NOMINAL DIAMETER CAST IRON PIPE.
<br />C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE.
<br />D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT.
<br />E. MAXIMUM 4" NOMINAL DIAMETER EMT.
<br />3. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT:
<br />A. MINIMUM 5/8" DEPTH, FOR A 1-HR FIRE -RATING.
<br />B. MINIMUM 1-1/4" DEPTH, FOR A 2-HR FIRE -RATING.
<br />4. MINIMUM 1/2- BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT.
<br />NOTES:
<br />1. MAXIMUM DIAMETER OF OPENING:
<br />A. 32-1/4" FOR STEEL STUD WALLS.
<br />B. 14-1/2' FOR WOOD STUD WALLS.
<br />2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 2-1/4".
<br />F RATING = 1-HR OR 2-HR.
<br />T RATING = O-HR.
<br />L RATING AT AMBIENT = LESS THAN 1 CFM/SQ. Fr.
<br />L RATING AT 4007 = LESS THAN 4 CFM/SQ. FT.
<br />INSTALLATION INSTRUCTIONS FOR UL NO. WL1054
<br />STEP 1 - PREPARATION: ALL. SURFACES MUST BE CLEAN, SOUND, DRY AND FROST FREE PRIOR
<br />TO APPLICATION OF RRESTOPPING MATERIALS.
<br />STEP 2 - FIRESTOP SEALANT: APPLY THE REQUIRED DEPTH OF FIRESTOP SEALANT WITHIN THE
<br />ANNULUS ON BOTH SIDES OF WALL. TOOL WITH A PLiTY KNIFE UNTIL FLUSH WITH BOTH
<br />SURFACES. LEAVE COMPLETED SEAL UNDISTURBED FOR 48 HOURS.
<br />METAL PIPE THROUGH 1-HR. OR
<br />2-HR. GYPSUM WALL ASSEMBLY
<br />N.T.S.
<br />TOP VIEW
<br />I A
<br />75cd
<br />56
<br />L1-08O C
<br />P
<br />STOR. ROOM
<br />e DIA. (OR SMALLER) STEEL
<br />PIPE, COPPER PIPE, EMIT OR
<br />CONDUIT
<br />MIN. 1/2" DEPTH HILTI —
<br />FS 601 FlR(3TOP
<br />SEALANT
<br />>d�
<br />�A
<br />MIN. 4-1/2" THICK CONCRETE —
<br />FLOOR/WALL OR ANY U.L CLASSIFIED
<br />CONCRETE BLOCK WALL
<br />SECTION A -A
<br />1/2" BEAD
<br />HILTI FS 601
<br />!— MIN. 3" THICK MINERAL WOOL
<br />NOTES: (MR 4 PCF) TIGHTLY PACKED
<br />1. MAXIMUM DIAMETER OF OPENING = 6".
<br />2. ANNULAR SPACE = MIN. 0" (POINT CONTACT), MAX. 2".
<br />3. WALLS REQUIRED 1/2" OF SEALANT FLUSH WITH BOTH SIDES.
<br />F RATING = 2-HR.
<br />T RATING = 0-HR.
<br />INSTALLATION INSTRUCTIONS FOR UL NO. CAJJ1149
<br />STEP 1 - PREPARATION: ALL SURFACES MUST BE CLEAN, DAD. DRY AND FROST -FREE PRIOR TO
<br />APPLICATION OF MATERIALS.
<br />STEP 2 - BACKING MATERIAL: PACK MINERAL WOOL TGny AROUND THE PENETRATION ITEM TO THE
<br />DEPTH SHOWN IN THE DRAWINGS, AND RECESS IT BELOW A TOP SURFACE OF THE FLOOR (OR BOTH
<br />SURFACES OF A WALL) TO ALLOW PROPER SPACE FOR THE FIRESTOP MATERIAL -
<br />STEP 3 - FIRESTOP SEALANT: APPLY THE FIRESTOP SEAM OVER THE BACKNG MATERIAL TO THE
<br />DEPTH SHOWN. IF THE PIPE IS OFFSET TO ONE SIDE, APPLY A 1/2" BEAD OF FIRESTOP SEALANT
<br />AROUND ITS CIRCUMFERENCE WHERE IT CONTACTS THE WAIL OR FLOOR. WALL PENETRATIONS REQUIRE
<br />FIRESTOP SEALANT ON BOTH SIDES. LEAVE COMPLETED SEA. UNDISTURBED FOR 48 HOURS.
<br />METAL PIPE THROUGH CONCRETE FLOOR/WALL
<br />N.T.S.
<br />=L ML_L. I /O — 1 -LI
<br />FROM CONTRC
<br />PREVIOUS AGENT
<br />ICE
<br />MANUAL PULL STATION
<br />WIRING DIAGRAM
<br />N.T.S.
<br />55-045 MINI
<br />MONITORING MODULE
<br />NOT TO SCALE
<br />SLC+1
<br />FROM PANEL OR
<br />PREVIOUS DEVICE
<br />From Control Panel
<br />or Previous Device
<br />0 0
<br />+1 SLC
<br />TO NEXT
<br />DEVICE
<br />4" OCTAGONAL BOX
<br />TRUE CEILING
<br />MOUNTING
<br />SCREWS
<br />ate',
<br />JUNCTION BOX
<br />OR PULL BOX
<br />FLEXIBLE CONDUIT
<br />/ HEAD
<br />FALSE CEILING
<br />- CADDIE BAR g�E
<br />PART NO. 512
<br />T-BAR
<br />FALSE CEILING DETECTOR MOUNTING DETAIL
<br />To next Device
<br />or EOL Resistor
<br />O 0
<br />6 3-1 O 54
<br />DETECTOR BASE
<br />N.T.S.
<br />14. CUR T IS #3791
<br />'211 5AX 352-588-19
<br />29775 BAYHIEAD RD.
<br />DADE CITY., FL 33523
<br />01-23
<br />GENERATOR
<br />75cd oc_
<br />G
<br />75cd
<br />S16r
<br />2Y ZEPH
<br />Date
<br />amiewer:
<br />H
<br />06) f4AVh :R:F,,.: !IItfiV!EWWb
<br />FIRE MARSHA1_.'S OFFICE
<br />Please be advised tIII, II , vY
<br />-lifted is a
<br />cursory review to assist flit contractor in : ,
<br />dliance with
<br />applicable fire safety codes. This re ie f ;:
<br />�.) intended
<br />to be a final approval of the submitied :
<br />,,s. It is file
<br />contractor's sole responsibility to ensure t"
<br />}; plans re in
<br />Lk/4(
<br />complete compliance with all applica`1:•: N
<br />codes . �d
<br />S�
<br />local ordinances. In the event th�r, e-
<br />: ninatio )r
<br />site inspection revez's areas of non -cc,:;:,
<br />,�, it sh ae
<br />the contractor's sole responsibility, at the;--
<br />A, exper . to
<br />bring those areas in compliance. The C,,.,
<br />sumes no
<br />responsibility for the contractor's failure to b`-
<br />I, � compliance
<br />�l
<br />with all applicable NFPA Codes and local
<br />, rdinances.
<br />EQUIPMENT SCHEDULE AND LEGEND
<br />SYMBOL
<br />CITY
<br />PART NUMBER
<br />MODEL NUMBER
<br />DESCRIPTION
<br />MANUFACTURER
<br />FRCP
<br />1
<br />10-2542
<br />10-2542
<br />CHEETAH Xi CONTROL PANEL
<br />FIKE
<br />VLP
<br />2
<br />VLP-002
<br />-
<br />VESDA LASER PLUS
<br />XTRALIS
<br />FV_PSj
<br />1
<br />VPS-3000S-120
<br />-
<br />VESDA POWER SUPPLY -MULTI ZONE
<br />XTRALIS
<br />2
<br />BSL1116
<br />PC1218
<br />18AH BATTERIES
<br />INTERSTATE
<br />4
<br />BSL1105
<br />PC12100
<br />12AH BATTERIES
<br />INTERSTATE
<br />18
<br />63-1052
<br />SLR-24V
<br />PHOTOELECTRIC DETECTOR
<br />FIKE
<br /><8>
<br />6
<br />60-1039
<br />-
<br />HEAT DETECTOR
<br />FIKE
<br />24
<br />63-1054
<br />-
<br />DETECTOR BASE
<br />FIKE
<br />❑F
<br />5
<br />20-1063
<br />-
<br />MANUAL PULL STATION
<br />FIKE
<br />19
<br />904-1317-002
<br />GEC3-24WR
<br />HORN/STROBE 75cd)
<br />GENTEX
<br />4
<br />904-1321-002
<br />GES3-24WR
<br />STROBE (75cd)
<br />GENTEX
<br />2
<br />904-1321-002
<br />GES3-24WR
<br />STROBE (75cd)
<br />GENTEX
<br />MM
<br />13
<br />55-045
<br />-
<br />MINI -MONITOR MODULE
<br />FIKE
<br />sCM
<br />1
<br />55-042
<br />-
<br />SUPERVISED CONTROL MODULE
<br />FIKE
<br />43
<br />1 VARIES
<br />VARIES
<br />VESDA SAMPLING POINTS & PIPE
<br />XTRALIS
<br />_
<br />PN1riL.PuNNnrn F7.. ILAU0r- rRD[ftlLre
<br />5201 BROOK HOLLOW PKWY. SUITE C 10260 N.W. 47TH STREET
<br />-
<br />-
<br />NORCROSs, GA 30071 SUNRISE, FL 33351
<br />(770) 889-6684 (954) 572-0119
<br />(770)888-6685-FAX (954)572-0528-FAX
<br />L UNITED FIRE A
<br />Ix
<br />DOTS
<br />D>escx¢�rmx
<br />VERIZON ZEPHYRHILLS CO
<br />38508 A Ave.
<br />Zephyrhills, FL 33542
<br />FLOOR PLAN
<br />PROVIDINE WORLD CLASS SERVICE
<br />1f4�U�iJIP'/A/wIIEG^aID}(o1lWG^�IRT1fIE�9� ORL.AKDO
<br />S SHOWN
<br />Ds""" BY D.PIERCE
<br />n> HyC. NORRIS
<br />12001 31ST COURT N. r_V(0R1nA 31"goII�(Piq/,� 224 W.CENTRAL PARKWAY, SUITE 1020
<br />ST. PETERSBURG, FL 33716 ALTAMONTE SPRINGS, FL 32714
<br />4 JOB xu D):TIDfO AUI�t
<br />[�
<br />02/10/14 13-1885TP FS - I OF 3
<br />(727) 471-0860 90068800012000 9023B (407) 830-7000
<br />(727) 471-0861-FAX EFOOOII85 LVA205328 (407) 830-7702-FAX
<br />L.L
<br />r
<br />N
<br />m
<br />C3
<br />r
<br />f7
<br />r
<br />v
<br />O
<br />J
<br />J
<br />CIL
<br />I
<br />LLj
<br />N
<br />13
<br />N_
<br />11
<br />Ld
<br />
|