GENERAL NOTES <br />PIPING <br />A. WHERE TRAPEZE PIPE HANGERS ARE PROVIDED, UTILIZE <br />DOUBLE NUT U-BOLTS. U-BOLTS SHALL BE LOOSELY FASTENED. <br />INTENT IS NOT TO BIND OR HOLD PIPE, BUT ONLY TO PROVIDE <br />LATERAL SEPARATION. <br />B. PROVIDE WATER HAMMER ARRESTORS FOR FLUSH VALVE <br />FIXTURES AND WHERE QUICK CLOSING VALVES ARE INSTALLED <br />IN ACCORDANCE WITH PDI STANDARDS OR RECOMMENDATIONS. <br />D <br />THIS INCLUDES ALL SENSOR OPERATED FAUCETS. <br />C. PRIME AND PAINT ALL OUTSIDE PIPE AND PIPE SUPPORTS IF <br />THEY ARE NOT GALVANIZED OR STAINLESS STEEL. <br />D. PRIME AND PAINT ALL GAS PIPING LOCATED INSIDE OR OUTSIDE <br />THE BUILDING PER PROJECT SPECIFICATIONS. <br />E. NO PIPE SUPPORT SYSTEMS SHALL CRUSH THE INSULATION <br />WHEN RESTING UPON THE SUPPORT. THE USE OF PIPE <br />SADDLES IS NECESSARY WHEN THE WEIGHT OF PIPE EXCEEDS <br />THE WEIGHT SUPPORT LIMIT OF THE INSULATION. <br />F. PIPE SIZES MAY BE SHOWN FOR SAME PIPE ON MORE THAN <br />ONE PLAN. IN CASE OF PIPE SIZE DISCREPANCY THE LARGER <br />PIPE SIZE SHALL BE CONSIDERED CORRECT DURING THE <br />BIDDING AND DURING CONSTRUCTION UNLESS SPECIFICALLY <br />APPROVED BY THE ARCHITECT/ENGINEER OTHERWISE. <br />G. PROVIDE PIPE SUPPORTS FOR ROOFTOP PIPING, I.E. <br />CONDENSATE DRAINS, GAS PIPING, STORM DRAINAGE, ETC. <br />H. PROVIDE SHUT-OFF VALVES FOR BOTH HOT AND COLD <br />DOMESTIC WATER FOR EACH TOILET BATTERY. LOCATE VALVES <br />IN AN ACCESSIBLE LOCATION WITH ACCESS DOOR AS <br />REQUIRED. <br />I. PROVIDE SHUT-OFF VALVES FOR ALL PRESSURE PIPING <br />CONTAINING TWO (2) OR MORE FIXTURE CONNECTIONS OR <br />BRANCH RUNOUTS. LOCATE VALVES IN AN ACCESSIBLE <br />LOCATION WITH ACCESS DOOR AS REQUIRED. <br />J. PROVIDE WARNING TAGS ON MEDIUM PRESSURE GAS (1/2" TO 5 <br />PSIG) UPSTREAM OF GAS REGULATORS STATING PRESSURE <br />C <br />AND "DO NOT REMOVE". <br />K. PROVIDE PIPE LABELING AS SPECIFIED. <br />F, <br />7 I 6 <br />PLUMBING <br />A. ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN <br />COMPLIANCE WITH ALL APPLICABLE CODES AS ADOPTED AND <br />AMENDED BY THE INSPECTING AUTHORITY. NOTHING IN THESE <br />DRAWINGS IS TO BE CONSTRUED TO PERMIT WORK NOT CONFORMING <br />TO THESE CODES. <br />B. EXACT LOCATIONS AND MOUNTING HEIGHTS OF PLUMBING FIXTURES <br />SHALL BE OBTAINED FROM THE ARCHITECTURAL DRAWINGS. <br />C. ALL PLUMBING WORK SHALL BE INSTALLED TO AVOID INTERFERENCE <br />WITH ELECTRICAL AND MECHANICAL EQUIPMENT AND STRUCTURAL <br />FRAMING. <br />D. BEFORE COMMENCEMENT OF WORK, CONTRACTOR SHALL VERIFY <br />THE EXACT LOCATIONS, ELEVATIONS AND CHARACTERISTICS OF ALL <br />UTILITIES AND PIPING. CONTRACTOR SHALL ALSO NOTIFY THE <br />ARCHITECT/ENGINEER OF ANY DISCREPANCIES. <br />E. ALL WASTE AND VENT PIPING 3" TO 6" IS TO SLOPE AT A MINIMUM OF <br />1/8" PER FOOT UNLESS INDICATED OTHERWISE. <br />F. ALL VENT PIPING SHALL BE ATTACHED TO WALL NO FURTHER THAN 3- <br />0" AWAY. <br />G. PROVIDE ADDITIONAL ATTACHMENT TO WALL FOR ALL FLOOR <br />STANDING SINKS. <br />H. ELECTRICAL OUTLETS SHALL BE INSTALLED BEHIND ELECTRIC WATER <br />COOLERS (NOT EXPOSED). <br />I. FCO'S SHALL BE INSTALLED FLUSH TO FINISHED FLOOR. NO DISHING <br />PERMITTED. <br />J. ALL FLOOR DRAINS LOCATED IN TOILET ROOMS, MECHANICAL ROOMS <br />AND OTHER LOCATIONS NOT SUBJECT TO PERIODIC WASHDOWN <br />SHALL BE PROVIDED WITH TRAP PRIMERS. <br />K. ALL VENT PIPING LOCATED IN A RETURN AIR PLENUM SHALL BE CAST <br />IRON. <br />L. ALL VENT PIPING SHALL BE FULL LINE SIZE IF A WCO IS SHOWN, OR AS <br />DIRECTED BY LOCAL, STATE CODES. <br />M. FLOOR DRAIN LINE SIZE AND VENTING SHALL BE IN ACCORDANCE WITH <br />PLUMBING CODE HAVING JURISDICTION, COMBINATION WASTE AND <br />VENT SYSTEM. <br />N. ALL FLOOR DRAINS SHALL BE INSTALLED FLUSH WITH FINISHED <br />FLOOR. PLUMBING CONTRACTOR SHALL EXAMINE ARCHITECTURAL <br />AND STRUCTURAL DRAWINGS TO DETERMINE THE EXACT TYPE OF <br />FLOOR FINISH AND MAKE ALLOWANCE DURING THE INSTALLATION. IF <br />ANY DRAIN IS NOT FOUND TO BE FLUSH WITH THE FINISHED FLOOR OR <br />PARALLEL TO THE WALLS THE PLUMBING CONTRACTOR WILL BE <br />REQUIRED TO REMOVE SUCH DRAIN AND RE -INSTALL AT NO COST. <br />0. ALL PIPING SHALL BE LOCATED WITHIN STUD WALLS AND OTHER WALL <br />CONSTRUCTION THAT MAY BE USED TO ENCLOSE THE PIPING. NO <br />PIPING IS TO BE LOCATED IN MASONRY WALLS. PIPING SHOWN ON <br />THE DRAWINGS MAY NOT REFLECT THIS INSTALLATION METHOD <br />BECAUSE OF THE DEGREE OF DETAIL INCONSISTENT WITH SCALED <br />DRAWINGS. IF PIPING CANNOT BE INSTALLED WITHIN THESE <br />STRUCTURES THE APPROVAL OF THE ENGINEER OF ANOTHER <br />INSTALLATION METHOD IS REQUIRED. <br />P. ALL PLUMBING FIXTURE VENTS SHALL TERMINATE A MINIMUM OF 12 <br />INCHES FROM ANY VERTICAL SURFACE AND 10'-0" FROM ANY OUTSIDE <br />AIR INTAKES. <br />Q. PLUMBING FIXTURE DESCRIPTION SHALL TAKE PRECEDENCE WHEN <br />THEIR EXISTS A CONFLICT WITH A DESCRIPTION AND MODEL NUMBER. <br />R. PROVIDE FACTORY FORMED "TRUEBRO" PVC JACKET COVERS FOR <br />DRAIN AND SUPPLY PIPING OF ALL LAVATORIES. <br />S. PROVIDE OFFSET DRAIN STRAINER FITTING FOR ALL LAVATORIES. <br />5 <br />4 <br />3 <br />ABBREVIATIONS: <br />AFF = <br />ABOVE FINISHED FLOOR <br />ANSI = <br />AMERICAN NATIONAL STANDARDS INSTITUTE <br />APPROX. = <br />APPROXIMATE <br />ASJ = <br />ALL SERVICE JACKET <br />AVG = <br />AVERAGE <br />BHP = <br />BRAKE HORSEPOWER <br />BOP = <br />BOTTOM OF PIPE <br />BOS = <br />BOTTOM OF STEEL <br />BOT. = <br />BOTTOM <br />BTU = <br />BRITISH THERMAL UNIT <br />CL = <br />CENTER LINE <br />CFM = <br />CUBIC FEET PER MINUTE <br />CU. FT. = <br />CUBIC FEET <br />CU. IN. = <br />CUBIC INCH <br />DIA.0 = <br />DIAMETER <br />DN = <br />DOWN <br />DWG. = <br />DRAWING <br />E.C. = <br />ELECTRICAL CONTRACTOR <br />EWT = <br />ENTERING WATER TEMPERATURE <br />F = <br />FAHRENHEIT <br />FPS = <br />FEET PER SECOND <br />GA. = <br />GAGE OR GAUGE <br />GAL. = <br />GALLON <br />GALV. = <br />GALVANIZED <br />GPD = <br />GALLONS PER DAY <br />GPH = <br />GALLONS PER HOUR <br />GPM = <br />GALLONS PER MINUTE <br />HOA = <br />HAND - OFF - AUTOMATIC SWITCH <br />HP = <br />HORSEPOWER <br />ID = <br />DIAMETER, INSIDE <br />I.E. = <br />INVERT ELEVATION <br />KW = <br />KILOWATT <br />LF = <br />LINEAR FEET <br />LWT = <br />LEAVING WATER TEMPERATURE <br />MAX. = <br />MAXIMUM <br />MBH = <br />BTU PER HOUR (THOUSAND) <br />MEZZ. = <br />MEZZANINE <br />MIN. = <br />MINIMUM <br />N.C. = <br />NORMALLY CLOSED <br />NG = <br />NATURAL GAS <br />N.O. = <br />NORMALLY OPEN <br />NTS = <br />NOT TO SCALE <br />O.C. = <br />ON CENTER <br />OD = <br />DIAMETER, OUTSIDE <br />OZ = <br />OUNCE <br />P.O.C. = <br />POINT OF CONNECTION <br />PRESS. = <br />PRESSURE <br />PSI = <br />POUNDS PER SQUARE INCH <br />PSIG = <br />PSI GAGE <br />PW = <br />PROCESS WASTE <br />RPM = <br />REVOLUTIONS PER MINUTE <br />SOV = <br />SHUT-OFF VALVE <br />SFU = <br />SUPPLY FIXTURE UNITS <br />SUCT = <br />SUCTION <br />TEMP = <br />TEMPERATURE <br />TYP. = <br />TYPICAL <br />UG = <br />UNDERGROUND <br />VEL = <br />VELOCITY <br />VERT = <br />VERTICAL <br />VOL = <br />VOLUME <br />VTR = <br />VENT THROUGH ROOF <br />W/ = <br />WITH <br />W/ TP = <br />WITH TRAP PRIMER <br />APPLICABLE CODES <br />FLORIDA BUILDING CODE, 2014 EDITION <br />FLORIDA MECHANICAL CODE, 2014 EDITION <br />FLORIDA PLUMBING CODE, 2014 EDITION <br />FLORIDA FIRE PREVENTION CODE, 2014 EDITION <br />FLORIDA FUEL GAS CODE, 2014 EDITION <br />FLORIDA ENERGY CONSERVATION CODE, 201 EDITION <br />ASHRAE 90.12010 <br />,,���A7-srnq`I�I/rho <br />ff�ANI <br />AEI ,� C PI ADDENDUM #1 04/16/18 HASKELL IIIRMa Wl Avenue <br />• � TM HaNceu comw"rr <br />* STATE ` * <br />Jar*sonvie, Fluids 32 <br />B PI 02/21 /18 202 f�harrolF ceal,�,-,� <br />A j0R#1 02/14/18 <br />Oj(� �•••�QR�Q:.••• C.OPPOR.ATE Eld( i�JEEFRJG c EFIi,E <br />�� i�o••• �G� DRAWN: DESIGN FIRM _ +_,RE TSIDE DFIVE. `,LIITE 100 <br />�7 EV. REVISION DESCRIPTION DRN. REV. DATE REV. REVISION DESCRIPTION DRN. REV. DATE CONTROL <br />NO.: <br />O�00% C,L�PE�. TEXAS <br />8 7 6 7 5 4 3 <br />2 <br />SCOPE & ASSUMPTIONS: <br />1 <br />-SCOPE INCLUDES THE ADDITION OF NEW TRENCH DRAINS AND NEW HUB/FLOOR DRAINS ROUTED <br />NEW BELOW GRADE SUMP. PUMPS AND DOWNSTREAM PIPING TO EXISTING PH NEUTRALIZATION <br />STATION BY OTHERS. <br />-BOTH NEW HAND SINKS WILL INDIRECTLY DISCHARGE INTO HUB DRAINS. <br />•TD-2 (160 GPM) AND TD-1 (140 GPM) FLOW CONCURRENTLY. <br />•FD-5 FLOWS AT 20 GPM (ESEWS SUPPLY RATE). <br />-HD-3: AFTER COOLER IS USED FOR BOILER BLOWDOWN 1407 MAX <br />-ALL DRAINS WILL BE INSTALLED WITH P-TRAPS. <br />-SUMP (1000 GALLONS) SHALL BE FULLY 304 STAINLESS STEEL. <br />-PIPING MATERIAL: CPVC <br />COMPRESSED AIR: — — <br />-SCOPE INCLUDES CONNECTION TO EXISTING CA LINE, DROPS BETWEEN DOCK DOORS, AND <br />CONNECTION TO TWO HOSE REEL STATIONS PROVIDED AND INSTALLED BY HASKELL. <br />•3/4" DROPS WILL PROVIDE ADEQUATE SUPPLY TO HOSE REEL STATIONS. <br />-EXISTING COMPRESSED AIR SYSTEM HAS ENOUGH CAPACITY FOR ADDITIONAL CA HOSE REELS <br />-MATERIAL: COPPER (TO MATCH EXISTING) <br />COLD WATER SUPPLY: <br />-SCOPE INCLUDES TYING INTO EXISTING SYSTEM AND ROUTING TO SINKS AND ESEWS. <br />-EXISTING CW HAS ENOUGH CAPACITY FOR THE PROPOSED ADDITIONS. <br />-MATERIAL: COPPER WITH FIBERGLASS INSULATION AND WHITE PVC JACKET. <br />HOT WATER SUPPLY: <br />•SCOP5.4UCLUDES SINKS AND ESEWS INSTANTANEOUS HEATERS. <br />NATURAL GAS: <br />-BELOW GRADE PIPING AND REGULATOR/METER SET DESIGNED, FURNISHED AND INSTALLED BY <br />UTILITY CO. <br />-MECHANICAL CONTRACTOR'S SCOPE INCLUDES CONNECTION FROM REGULATOR/METER SET <br />OUTLET, PIPE PENETRATION THRU WALL AND A VALVE INSTALLED IN THE VERTICAL POSITION. <br />-MATERIAL: SOCKET WELDED SCH 40 CARBON STEEL PAINTED TO MATCH EXISTING <br />SEISMIC DESIGN REQUIREMENTS <br />CATEGORY-B: SEISMIC DESIGN CATEGORY FOR THIS PROJECT <br />IS CATEGORY B. PER ASCE STANDARD, ASCE/SEI 7-05, CHAPTER <br />13, MECHANICAL AND ELECTRICAL COMPONENTS ARE EXEMPT <br />AND REQUIRE NO SEISMIC SUPPORT OR SEISMIC BRACING. <br />SHT No <br />SHEET NAME <br />REV <br />DATE <br />P-001 <br />PLUMBING LEGEND, ABBREVIATIONS, & NOTES <br />C <br />04/16/18 <br />P-110 <br />OVERALL PLUMBING FLOOR PLAN <br />C <br />04/16/18 <br />P-111 <br />ENLARGED PLUMBING FLOOR PLAN - <br />DRAINAGE <br />C <br />04/16/18 <br />P-121 <br />ENLARGED PLUMBING FLOOR PLAN - UTILITIES <br />C <br />04/16/18 <br />P-501 <br />PLUMBING DETAILS <br />C <br />04/16/18 <br />P-601 <br />PLUMBING SCHEDULES <br />C <br />04/16/18 <br />P-701 <br />PLUMBING RISER DIAGRAMS <br />C <br />04/16/18 <br />Grand total: 7 <br />GLOSSARY <br />FURNISH: <br />PURCHASE AND DELIVER (EQUIPMENT) TO <br />THE JOB SITE ONLY. <br />INSTALL: <br />PROVIDE ALL MISCELLANEOUS MATERIALS <br />& SERVICES (LABOR & MATERIAL) REQUIRED <br />TO MAKE EQUIPMENT OPERATIONAL. <br />PROVIDE: <br />FURNISH AND INSTALL. <br />REMARKS: <br />INFORMATION PERTAINING TO ALL ITEMS <br />ON A SCHEDULE. <br />NOTES: <br />INFORMATION PERTAINING ONLY TO <br />INDICATED ITEMS ON A SCHEDULE <br />WAREHOUSE EXPANSION <br />ZEPHYRHILLS NATURAL SPRING WATER <br />ZEPHYRHILLS, FLORIDA <br />The Information contained on this document is the sole property of NWNA <br />and may not be copied or disclosed to others unless authorized by NWNA. <br />DATE: I D.M.: I SCALE: <br />2 <br />PLUMBING LEGEND, <br />ABBREVIATIONS, & NOTES <br />SIZE SHEET NO. <br />D P-001 <br />1 <br />REV. NO. <br />C <br />IV <br />