LOWER HANGER ATTACHMENTS
<br />25044' ANGLES TRAPEZE HANGFRR
<br />16 GA. x 1' WIDE STRAP OR ANGLE
<br />STRAP HANGERS 3/8'0 ROD
<br />HANGER
<br />STRAPS
<br />[>< MAX III X1 .11
<br />N SPACING
<br />a
<br />SIZE BOLT(S) FOR LOAD
<br />1_6
<br />- #10 SM. SCREWS
<br />LOAD RATED
<br />FASTENERS
<br />HANGER STRA7�
<br />BAND OF SAME SIZE y
<br />AS HANGER STRAP
<br />TdHANGER RODS
<br />OR STRAPS
<br />BAND
<br />5/8' DIA. MIN.
<br />250440 ANGLES
<br />ZWk1/4' ANGLES
<br />SPAN 2 JOISTS
<br />AVOID DISRUPTION
<br />OF INSULATION
<br />ROD
<br />01
<br />PREFERRED --�
<br />TRAP
<br />ATTACHMENT
<br />ANGLES 25c2'k1/4' �� NUT (TYP)
<br />ALTERNATE LOCATIO
<br />HANGERS FOR STACKED DUCTS
<br />GENERAL NOTES:
<br />REINFORCEMENT MAY BE USED FOR ATTACHMENT
<br />IF IT QUALIFIES FOR BOTH DUTIES.
<br />DO NOT EXCEED LOAD RATING FOR METHOD USED.
<br />ING ENGINEERING ASSOCIATES, INC. REV. 01-11-16 MD-0512
<br />OAU CONDENSATE DRAIN PIPING 1
<br />CONDENSATE DRAIN CONNECTION
<br />TO UNIT
<br />PVC CLEANOUT
<br />PLUG
<br />SCHEDULE 40 PVC
<br />TOTAL A
<br />HEIGHT
<br />MUST EQUAL OR
<br />OF
<br />TRAP
<br />B
<br />EXCEED TOTAL COIL
<br />STATIC PRESS. (4' MIN)
<br />REFER TO MECHANICAL
<br />DRAWINGS.
<br />DEEP SEAL TRAP
<br />PROVIDE A SECONDARY
<br />POSITIVE STATIC PRESSURE (BLOW-THRU)
<br />DRAIN PAN (MINIMUM 3'
<br />A= AT LEAST ONEW INCH PLUS CASING STATIC PRESSURE
<br />DEEP AND 6' PAST UNIT IN
<br />6= AT LEAST ONEW INCH
<br />ALL DIRECTIONS. PAN SHALL
<br />TOTAL HEIGHT OF TRAP-- A+B+(1b x PIPE DIA)
<br />HAVE FLOAT SWITCH WIRED
<br />TO SHUT DOWN UNIT IN
<br />NEGATIVE STATIC PRESSURE (DRAW-THRU)
<br />THE EVENT OF WATER IN
<br />PAN.
<br />A= ONE HALF (1/2) B
<br />B= AT LEAST ONE (1) INCH PLUS CASING STATIC PRESSURE
<br />TOTAL HEIGHT OF TRAP-- A+B+(1b x PIPE DIA)
<br />CONSULTING ENGINEERING ASSOCIATES, INC. REV. 03-29-16 MD-0211
<br />REFRIGERANT PIPING PENETRATION THROUGH
<br />EXTERIOR WALL
<br />SEAL VOID AROUND PIPING WITH
<br />3M FIRE SAFING OR FIRE PUTTY.
<br />TOP FIRE SAFING/PUTTY WITH
<br />SILICONE CAULK ON BOTH
<br />INTERIOR AND EXTERIOR
<br />SURFACES TO ENSURE A
<br />WATER -TIGHT SEAL
<br />REFRIGERANT PIPING SUCTION UNE
<br />REFRIGERANT PIPING UQUID UNE
<br />EXTERIOR WALL
<br />SLEEVE ANCHOR, (2) 3/8'0 RODS.
<br />PROVIDE SCHEDULE 40 STEEL
<br />SLEEVE AS SMALL AS POSSIBLE
<br />TO ACCOMMODATE PIPING.
<br />SLEEVE FLUSH WITH INTERIOR
<br />AND EXTERIOR OF WALL
<br />REFRIGERANT PIPING SUCTION
<br />LINE COPPER PIPE WITH
<br />ARMAFLEX INSULATION. SIZE PER
<br />MANUFACTURERS
<br />SPECIFICATIONS. PAINT ALL
<br />EXPOSED INSULATION WITH TWO
<br />COATS OF WHITE ARMAFLEX
<br />PAINT.
<br />REFRIGERANT PIPING LIQUID
<br />LINE BARE COPPER PIPE
<br />SIZE PER MANUFACTURERS
<br />SPECIFICATIONS.
<br />CONSULTING ENGINEERING ASSOCIATES, INC. REV: 01-14-16 MD-0825
<br />REPLACEMENT EVAPORATOR COILS
<br />MARK --- AHU-1 AHU-2
<br />COOLING
<br />TOTAL CAPACITY
<br />BTUH
<br />191,500
<br />165,300
<br />SENSIBLE CAPACITY
<br />BTUH
<br />153,900
<br />129 500
<br />TOTAL AIR FLOW
<br />CFM
<br />7150
<br />6000
<br />OUTSIDE AIR FLOW
<br />CFM
<br />1200
<br />1520
<br />EXTERNAL STATIC PRESSURE
<br />IN WG
<br />1.5
<br />1.5
<br />ENT. AIR TEMP DB WB
<br />DEG F DEG F
<br />74.5 62.5
<br />74.3 62.4
<br />LVG. AIR TEMP DB WB
<br />DEG F DEG F
<br />54.8 53.3
<br />54.6 52.9
<br />COOLING COIL MIN MAX
<br />ROWS FINS PER INCH
<br />6 10
<br />6 10
<br />COOLING COIL MAX FACE VEL.
<br />FPM
<br />424
<br />501
<br />COOLING COIL MAX PRESS. DROP
<br />IN WG
<br />0.63
<br />0.86
<br />REFRIGERANT TYPE
<br />-
<br />R-410a
<br />R-410a
<br />SUCTION TEMP
<br />DEG F
<br />48.5
<br />45.5
<br />NOTES:
<br />1. PROVIDE STAINLESS STEEL COIL CASINGS AND COIL SUPPORTS.
<br />100% OAU SUPPORT - FLOOR MOUNTED
<br />OUTSIDE a PROVIDE DUCT MOUNTED
<br />DUCT F
<br />AIR SMOKE DETECTOR AS
<br />.
<br />PROVIDE 4' FLEXIBLE
<br />CONNECTOR AT
<br />SUPPLY AND OUTSIDE
<br />AIR DUCT
<br />CONNECTIONS.
<br />FILTER SECTION
<br />SUPPLY
<br />DUCT
<br />PAN TO EXTEND A
<br />MINIMUM OF 6' PAST
<br />UNIT IN ALL DIRECTIONS.
<br />3' DEEP SECONDARY
<br />DRAIN PAN
<br />PROVIDE FIVE SIDED, EXTERNALLY INSULATED PLENUM BOX ON SICE OF OAU
<br />FOR OUTSIDE AIR DUCT CONNECTION. BOX TO BE A MINIMUM OF 6' AFF.
<br />SIZE BOX PER UNIT DIMENSIONS AND RETURN DUCT/OUTSIDE AIR DUCT SIZE
<br />REQUIREMENTS.
<br />CONSULTING ENGINEERING ASSOCIAT
<br />TYPICAL BRANCH DUCTS
<br />3
<br />09
<br />LL
<br />Q
<br />OPPOSED BLADE
<br />DAMPER
<br />CONSULTING ENGINEERING
<br />REQUIRED.
<br />DUCT CONNECTIONS
<br />TO BE A MINIMUM OF
<br />TWO FAN DIAMETERS
<br />IN DISTANCE FROM
<br />TOP OF UNIT.
<br />FAN SECTION. ENSURE
<br />FAN IS ROTATED AS
<br />REQUIRED FOR DUCT
<br />CONNECTION.
<br />COIL SECTION
<br />- CONTRACTOR TO
<br />CONSTRUCT GALVANIZED
<br />STEEL FRAME UNDER
<br />UNIT FOR SUPPORT. USE
<br />SIMPLE' FRAMING
<br />PROCEDURES. SIZE
<br />APPROPRIATELY FOR UNIT
<br />WEIGHT.
<br />CONDENSATE
<br />PIPING, REFER
<br />TO AHU
<br />�- CONDENSATE
<br />DRAIN PIPING
<br />DETAIL
<br />- FLOAT SWITCH
<br />- 1' THICK NEOPRENE PAD
<br />REV:08-08-16 MD-0443
<br />OPPOSED BLADE
<br />DAMPER
<br />- PROVIDE 2'
<br />STAND-OFF FOR
<br />INSULATED DUCTS
<br />INC. REV.10-27-16 1 MD-0504B
<br />EXISTING AIR HANDLER UNIT DATA
<br />MARK
<br />AHU-1
<br />AHU-2
<br />TOTAL AIR FLOW
<br />CFM
<br />7150
<br />6000
<br />OUTSIDE AIR FLOW
<br />CFM
<br />1200
<br />1520
<br />STATIC PRESSURE
<br />EXT. TOT.
<br />1.5 2.73
<br />1.5 2.01
<br />MOTOR
<br />HP BHP
<br />10 7.9
<br />7.5 5.11
<br />FAN TYPE
<br />MIN. DIA.
<br />AF 15
<br />AF 15
<br />FAN RPM
<br />MAX.
<br />2331
<br />2016
<br />FAN OUTLET
<br />VEL. MAX
<br />3505
<br />3039
<br />ELECTRICAL
<br />V PH HZ
<br />208 3
<br />208 3
<br />TOTAL CAPACITY
<br />BTUH
<br />185600
<br />162900
<br />SENS. CAPACITY
<br />BTUH
<br />154000
<br />130900
<br />COIL ENT. AIR TEMP. DB WB
<br />74.5 62.5
<br />74.3 62.4
<br />COIL LVG. AIR TEMP. DB WB
<br />54.8 53.5
<br />55 53.3
<br />COIL
<br />ROWS FINS
<br />8 '9
<br />5 '8
<br />COIL FACE VELOCITY
<br />MAX
<br />500
<br />450
<br />SATURATED SUCTION TEMP
<br />42
<br />42.5
<br />AIR PRESS. DROP
<br />MAX.
<br />0.99
<br />0.32
<br />EXTERNAL FACE & BYPASS
<br />-----
<br />N/A
<br />N/A
<br />FILTER TYPE
<br />-----
<br />2"
<br />2"
<br />EFFICIENCY ASHRAE 52-89
<br />-----
<br />30%
<br />30%
<br />MEDIAN P.D.
<br />EACH
<br />0.61
<br />0.63
<br />MANUFACTURER
<br />-----
<br />YORK
<br />YORK
<br />MODEL NO.
<br />-----
<br />AP-150
<br />AP-150
<br />UNIT WEIGHT
<br />LBS.
<br />2197
<br />2277
<br />NOTES
<br />ALL
<br />ALL
<br />NOTES:
<br />1. THIS SCHEDULE HAS BEEN REPRODUCED FROM EXISTING RECORD DOCUMENTS BY CONSULTING
<br />ENGINEERING ASSOCIATES, INC. ISSUED OCTOBER 3, 2002, FOR REFERENCE ONLY.
<br />DIRECT EXPANSION AIR COOLED CONDENSING UNIT SCHEDULE
<br />MARK
<br />---
<br />CU-1 A
<br />CU-1 B
<br />CU-2A
<br />CU-2B
<br />CAPACITY
<br />BTUH
<br />90,600
<br />90 600
<br />85,400
<br />85,400
<br />AMBIENT TEMP.
<br />DEG F
<br />95
<br />95
<br />95
<br />95
<br />SUCTION TEMP.
<br />DEG F
<br />48.5
<br />48.5
<br />45.5
<br />45.5
<br />WEIGHT
<br />LBS
<br />390
<br />390
<br />390
<br />390
<br />REFRIGERANT TYPE
<br />---
<br />R-410A
<br />R-410A
<br />R-410A
<br />R-41OA
<br />NO. OF CIRCUITS
<br />---
<br />1
<br />1
<br />1
<br />1
<br />UNLOADING
<br />STEP MIN
<br />100-0
<br />100-0
<br />100-0
<br />100-0
<br />COMPRESSOR
<br />NO
<br />1
<br />1
<br />1
<br />1
<br />COMPRESSOR RLA EACH
<br />AMPS
<br />25
<br />25
<br />25
<br />25
<br />COMPRESSOR (LRA EACH
<br />AMPS
<br />164
<br />164
<br />164
<br />164
<br />CONDENSER FAN
<br />NO. HP
<br />2 TO.33
<br />2 0.33
<br />2 0.33
<br />2 0.33
<br />CONDENSER FAN FLA EACH
<br />AMPS
<br />2.1
<br />2.1
<br />2.1
<br />2.1
<br />EER
<br />---
<br />12.4
<br />12.4
<br />12.4
<br />12.4
<br />TOTAL UNIT MCA
<br />AMPS
<br />35.5
<br />35.5
<br />35.5
<br />35.5
<br />TOTAL UNIT MOCP
<br />AMPS
<br />45
<br />45
<br />45
<br />45
<br />ELECTRICAL
<br />V PH HZ
<br />208 3 60
<br />208 3 60
<br />208 3 60
<br />208 3 60
<br />MANUFACTURER
<br />---
<br />JCI
<br />JCI
<br />JCI
<br />JCI
<br />MODEL
<br />---
<br />J07YCCOOA2AA65
<br />J07YCCOOA2AAB5
<br />J07YCCOOA2AAB5
<br />J07YCCOOA2AAB5
<br />NOTES
<br />1 12345
<br />2345
<br />1 12345
<br />1 2345
<br />NOTES:
<br />1. PROVIDE RAWALL DEVICE FACTORY INSTALLED
<br />2. PROVIDE ONE INCH THICK NEOPRENE PAD(S) BETWEEN CONDENSING UNIT AND CONCRETE PAD.
<br />3. DISCONNECT PROVIDED BY DIVISION 26.
<br />4. SECURE CONDENSING UNIT TO CONCRETE PAD USING 1" WIDE, 10 GAGE SHEET METAL
<br />STRAPS NEATLY SECURED TO THE UNIT AND BASE SUPPORT USING 1" STAINLESS STEEL SCREWS.
<br />COORDINATE LOCATIONS OF SCREWS WITH STRUCTURAL COMPONENTS OF THE UNIT.
<br />DO NOT BLOCK SERVICE ACCESS.
<br />5. MANUFACTURER SHALL SIZE REFRIGERANT PIPING AND PROVIDE ALL REFRIGERANT SPECIALTIES.
<br />CONDENSING UNIT ON GRADE
<br />PROVIDE CONDENSER
<br />FAN GUARD
<br />ALL SCREWS SHALL
<br />BE J14 GASKETED
<br />WASHER SCREWS,
<br />STAINLESS STEEL
<br />CONSULTING ENGI
<br />CONDENSING UNIT
<br />PROVIDE
<br />CONDENSER
<br />COIL GUARDS
<br />PROVIDE
<br />CONTINUOUS 22
<br />GAUGE STAINLESS
<br />STEEL STRAPS
<br />(THREE PER SIDE)
<br />1' THICK NEOPRENE PAD(S)
<br />EXISTING CONCRETE PAD TO
<br />EXTEND A MINIMUM OF 6'
<br />AROUND ALL SIDES OF UNIT.
<br />INC. REV: 07-25-16 MD-0444
<br />VOLUME DAMPERS FOR DUCTWORK 6
<br />J
<br />' '
<br />�
<br />I�jl
<br />ill■
<br />-.
<br />L
<br />FIG. C
<br />ROUND DAMPER
<br />o
<br />o
<br />DUCT
<br />FIG D
<br />ELEVATION
<br />TWO BLADE ARRANGEMENT
<br />30 QUADRANT DUCT
<br />BEARING OPTION
<br />1/2' QUADRANT DUCT
<br />30 PIN
<br />FOR SINGLE
<br />1/2' ROD -PIN
<br />BLADE DAMPERS
<br />mi
<br />22 GA. BLADE
<br />16 GA. BLADE
<br />10 CLEARANCE ALL
<br />AROUND
<br />1)W CLEARANCE ALL
<br />C+FNFRgI NnTF•
<br />AROUND
<br />UP TO 18
<br />-- - - -•
<br />OVER 4' HIGH USE
<br />19' TO 48'
<br />FIG.
<br />MULTIPLE BLADES
<br />FIG. B
<br />STIFFEN AS
<br />orniuDan
<br />0 0 6 6
<br />OUTSIDE INSIDE
<br />END BEARING END BEARING
<br />FIG. A OR REQUIRED ON 2' Wra
<br />SIDE ELEVATION CLASS DUCT. OPTIONAL
<br />ON OTHERS.
<br />CONSULTING ENGINEERING ASSOCIATES, INC. I REV: 01-11-16 MD-0508
<br />EXISTING DEHUMIDIFICATION UNIT SCHEDULE
<br />MARK
<br />-
<br />OA-1
<br />COOLING CAPACITY
<br />MBH
<br />257565
<br />SENSIBLE CAPACITY
<br />MBH
<br />117846
<br />ENTERING AIR TEMP.
<br />'FDB °FWB
<br />91 79
<br />LEAVING AIR TEMP / COIL/ UNIT
<br />-FDB 'FWB
<br />52 51.5 72 61.8
<br />LEAVING AIR DEWPOINT, MAXIMUM
<br />-F
<br />50.8
<br />AIRFLOW
<br />CFM
<br />2720
<br />EXT./TOT. STATIC PRESSURE
<br />IN. WTR.
<br />.75 1.75
<br />EVAPORATOR FAN
<br />HP BHP
<br />3
<br />EVAPORATOR FAN
<br />RPM
<br />1750
<br />DEHUMIDIFICATION COIL
<br />ROWS MIN.
<br />6
<br />MIN. SATURATED SUCTION TEMP
<br />'F FULL LOAD
<br />47.3
<br />ELECTRIC HEAT
<br />KW TYPE
<br />25 SCR CONTROL
<br />FILTER TYPE EFF
<br />- %
<br />30
<br />NUMBER OF COMPRESSORS MIN.
<br />-
<br />1
<br />ELECTRICAL
<br />V PH Hz
<br />208 3 60
<br />COMPRESSOR
<br />FLA
<br />37.4,37.4
<br />EVAPORATOR FAN
<br />FLA
<br />7
<br />MINIMUM CIRCUIT AMPS
<br />-
<br />95
<br />REC. FUSE SIZE
<br />-
<br />110
<br />UNIT EER
<br />MIN.
<br />12
<br />WEIGHT
<br />LBS
<br />1700
<br />MANUFACTURER
<br />-
<br />DESERT AIRE
<br />MODEL
<br />-
<br />Total Aire 20
<br />REMOTE CONDENSER
<br />THR
<br />316805
<br />NUMBER OF FANS
<br />-
<br />2
<br />MINIMUM CIRCUIT AMPS
<br />-
<br />14
<br />REC. FUSE SIZE
<br />-
<br />20
<br />MANUFACTURER
<br />-
<br />DESERT AIRE
<br />MODEL
<br />-
<br />ROC 0021
<br />NOTES:
<br />ALL
<br />NOTES:
<br />1. THIS SCHEDULE HAS BEEN REPRODUCED FROM EXISTING RECORD DOCUMENTS BY CONSULTING
<br />ENGINEERING ASSOCIATES, INC. ISSUED OCTOBER 3, 2002, FOR REFERENCE ONLY.
<br />DIRECT EXPANSION OUTSIDE
<br />AIR UNIT REMOTE CONDENSER SCHEDULE
<br />MARK
<br />---
<br />OACU-1
<br />CAPACITY
<br />BTUH
<br />262,500
<br />AMBIENT TEMP.
<br />DEG F
<br />95
<br />WEIGHT
<br />LBS
<br />369
<br />REFRIGERANT TYPE
<br />---
<br />R-410A
<br />NO. OF CIRCUITS
<br />---
<br />1
<br />CONDENSER FAN
<br />NO.
<br />2
<br />CONDENSER FAN FLA EACH
<br />AMPS
<br />3.3
<br />TOTAL UNIT MCA
<br />AMPS
<br />9
<br />TOTAL UNIT MOCP
<br />AMPS
<br />12
<br />ELECTRICAL
<br />V PH HZ
<br />230 3 60
<br />MANUFACTURER
<br />---
<br />DESERT AIRE
<br />MODEL
<br />---
<br />RC5SO67
<br />NOTES
<br />---
<br />ALL
<br />NOTES:
<br />1. REFRIGERANT LINES TO BE SIZED PER MANUFACTURER'S SPECIFICATIONS.
<br />2. PROVIDE ONE INCH THICK NEOPRENE PAD(S) BETWEEN CONDENSER AND
<br />CONCRETE PAD.
<br />3. SECURE CONDENSER TO CONCRETE PAD USING 1" WIDE, 10 GAGE SHEET
<br />METAL STRAPS NEATLY SECURED TO THE UNIT AND BASE SUPPORT USING
<br />1" STAINLESS STEEL SCREWS. COORDINATE LOCATIONS OF SCREWS WITH
<br />STRUCTURAL COMPONENTS OF THE UNIT. DO NOT BLOCK SERVICE
<br />ACCESS.
<br />4. DISCONNECT PROVIDED BY DIVISION 26.
<br />FPIPE HANGERS 11
<br />ALL THREADED HANGER ROD
<br />LOCKING NUT
<br />HEAVY DUTY CLEVIS HANGER
<br />INSULATION WITH---,,
<br />VAPOR BARRIER
<br />PIPING ��
<br />18 GA GALVID STEEL
<br />SADDLE 3 TIMES
<br />PIPE DIAMETER OR
<br />9' MIN. LENGTH.
<br />ALL THREADED HANGER ROD
<br />LOCKING NUT
<br />SUPPORT NUT
<br />HEAVY DUTY CLEVIS HANGER
<br />INSULATION WITH
<br />VAPOR BARRIER
<br />PIPING
<br />18 GA. GALVID STEEL
<br />SADDLE 3 TIMES
<br />PIPE DIAMETER OR
<br />9' MIN. LENGTH.
<br />CONSULTING ENGINEERING ASSOCIATES, INC. REV: 01-14-16
<br />rRECTANGLAR DUCT HANGERS MINIMUM SIZES
<br />MAXIMUM
<br />PAIR AT
<br />PAIR AT
<br />PAIR AT
<br />PAIR AT
<br />HALF OF
<br />10 FT. SPACING
<br />8 FT. SPACING
<br />5 FT. SPACING
<br />4 FT. SPACING
<br />DUCT
<br />PERIMETER
<br />STRAP
<br />ROD
<br />STRAP
<br />ROD
<br />STRAP
<br />ROD
<br />STRAP
<br />ROD
<br />P
<br />2
<br />1' x 22 GA.
<br />1/4'
<br />1' x 22 GA
<br />1/4'
<br />1' x 22 GA
<br />1/4'
<br />1' x 22 GA.
<br />1/4'
<br />P
<br />2 = 96'
<br />1' x 18 GA.
<br />3/8'
<br />1' x 20 GA
<br />1/4'
<br />1' x 22 GA.
<br />1/4'
<br />1' x 22 GA.
<br />1/4'
<br />P
<br />2 = 120'
<br />1' x 16 GA.
<br />30
<br />1' x 18 GA.
<br />3/8'
<br />1' x 22 GA.
<br />1/4'
<br />1' x 22 GA.
<br />1/4'
<br />P
<br />2 = 168'
<br />1B' x 16 GA
<br />1/2'
<br />1' x 16 GA.
<br />3/8'
<br />1' x 18 GA.
<br />3/8'
<br />1' x 18 GA.
<br />3/8'
<br />P
<br />= 192'
<br />2
<br />1/2'
<br />15' x 16 GA.
<br />1/2'
<br />1' x 16 GA.
<br />30
<br />1' x 16 GA.
<br />3/8'
<br />P = 193, UP
<br />2
<br />SPECIAL ANALYSIS REQUIRED
<br />WHEN STRAPS ARE LAP JOINED
<br />SINGLE HANGER
<br />USE THESE MINIMUM FASTENERS.
<br />MAXIMUM ALLOW. LOAD
<br />V x 18, 20,22 GA. - TWO #10
<br />1' x 22 GA. - 260 LBS. 1/4 DIA. 270 LBS.
<br />?x 16 GA. - TWO 1/4' DIA
<br />T x 20 GA. - 320 LBS. 3/8 DIA 680 LBS.
<br />1.7 x 16 GA - TWO 3/8' DIA
<br />1' x 18 GA - 420 LBS. 1/2 DIA. 1250 LBS.
<br />PLACE FASTENERS IN SERIES,
<br />1' x 16 GA. - 700 LBS. 5/8 DIA 2000 LBS.
<br />NOT SIDE BY SIDE
<br />1.5' x 16 GA - 1100 LBS. 3/4 DIA. 3000 LBS.
<br />NOTES:
<br />1. DIMENSIONS OTHER THAN GAGE ARE IN INCHES.
<br />2 TABLES ALLOW FOR DUCT WEIGHT, OS LB/SF INSULATION WEIGHT & NORMAL REINFORCEMENT AND
<br />TRAPEZE WEIGHT, BUT NO EXTERNAL LOADSI
<br />3. CONSULT AISI LIGHT GAGE STEEL DESIGN MANUAL AND AISC STEEL CONSTRUCTION MANUAL FOR CRITERIA
<br />FOR DESIGN OF OTHER HANGERS.
<br />4. STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL
<br />5. ALLOWABLE LOADS LISTED ASSUME THAT DUCTS ARE 16 GA. MAXIMUM.
<br />CONSULTING ENGINEERING ASSOCIATES, INC. REV: 01-11-16 MD-0511
<br />DIRECT EXPANSION 100% OUTSIDE AIR UNIT SCHEDULE
<br />MARK --- OAU-1
<br />COOLING
<br />TOTAL CAPACITY
<br />BTUH
<br />212,960
<br />SENSIBLE CAPACITY
<br />BTUH
<br />101,532
<br />TOTAL AIR FLOW
<br />CFM
<br />2720
<br />EXTERNAL STATIC PRESSURE
<br />IN WG
<br />0.8
<br />EVAP COIL ENT. AIR TEMP. DB WB
<br />DEG F DEG F
<br />91.0 79.0
<br />EVAP COIL LVG. AIR TEMP. DB WB
<br />DEG F DEG F
<br />56.9 56.9
<br />REHEAT COIL LVG. AIR TEMP. DB RH
<br />DEG F RH
<br />72460
<br />DEHUMIDIFICATION COIL MIN MAX
<br />ROWS FINS PER INCH
<br />6 12
<br />DEHUMIDIFICATION COIL MAX FACE VEL.
<br />FPM
<br />400
<br />DEHUMIDIFICATION COIL MAX PRESS. DROP
<br />IIN WG
<br />1 0.3
<br />HEATING
<br />LOCATION
<br />---
<br />IN UNIT
<br />TOTAL CAPACITY
<br />KW STEPS
<br />I 25 SCR
<br />UNIT
<br />DRIVE
<br />---
<br />Belt
<br />FAN TYPE
<br />---
<br />FC
<br />FAN MOTOR
<br />HP
<br />2.0
<br />REFRIGERANT TYPE
<br />---
<br />R-410A
<br />COMPRESSOR
<br />NO./HP
<br />2 7.5
<br />COMPRESSOR (RLA EACH
<br />AMPS
<br />29.5
<br />EVAPORATOR FAN
<br />N0. HP
<br />2.0
<br />MRE PER AHRI 920
<br />---
<br />7.9
<br />TOTAL UNIT MCA
<br />AMPS
<br />96
<br />TOTAL UNIT MOCP
<br />AMPS
<br />100
<br />ELECTRICAL
<br />V PH HZ
<br />230 3 60
<br />FILTER
<br />MERV
<br />8
<br />WEIGHT
<br />LBS
<br />1444
<br />MANUFACTURER
<br />---
<br />DESERT AIRE
<br />MODEL
<br />---
<br />QV15
<br />NOTES
<br />---
<br />ALL
<br />NOTES:
<br />1. UNIT PERFORMANCE TO MEET MINIMUM LEAVING AIR TEMPERATURE AND DEWPOINT VALUES.
<br />2. PROVIDE MINIMUM 6 ROW DEHUMIDIFICATION COIL - NO EXCEPTIONS.
<br />3. PROVIDE VARIABLE HOT GAS REHEAT CONTROL TO MAINTAIN DESIRED AIR TEMPERATURE
<br />WITHIN PLUS OR MINUS 2 DEG F UNDER ALL AMBIENT CONDITIONS.
<br />4. PROVIDE HOT GAS BYPASS.
<br />5. PROVIDE FULL COOLING PERFORMANCE OPTION (REFRIGERANT REHEAT OFF).
<br />6. PROVIDE SLOPED IAQ STAINLESS STEEL DRAIN PAN.
<br />7. PROVIDE DOUBLE WALL CONSTRUCTION - NO EXECPTIONS.
<br />8. PROVIDE STAINLESS STEEL CABINET HARDWARE - ZINC PLATED NOT ACCEPTABLE.
<br />9. ALL STARTERS/CONTROLS TO BE FACTORY INSTALLED.
<br />10. PROVIDE SINGLE POINT POWER CONNECTION.
<br />11. PROVIDE CONTACT CLOSURE SIGNAL FOR MOTORIZED OCCUPANCY DAMPERS IN FIELD
<br />PROVIDED DUCTWORK.
<br />12. UNIT TO BE ETL LISTED AND LABELED AND FULLY FACTORY RUN TESTED.
<br />13. DISCONNECT FURNISHED AND INSTALLED BY DIVISION 26.
<br />PERFORMANCE STANDARD:
<br />THIS IS A 100% DEDICATED OUTDOOR AIR SYSTEM (DOAS); PERFORMANCE IS OF THE UTMOST
<br />IMPORTANCE TO THE QUALITY OF THE INDOOR AIR ENVIRONMENT. THIS UNIT IS SPECIFIED TO
<br />PRODUCE A LEAVING AIR TEMPERATURE, AND RESULTING RELATIVE HUMIDITY, TO WITHIN PLUS
<br />OR MINUS 2.0 DEGREES FAHRENHEIT OF SET -POINT. THERE WILL BE NO EXCEPTIONS.
<br />DESERT AIRE AND DECTRON ARE ACCEPTABLE MANUFACTURERS OF THIS PRODUCT. ALL
<br />MANUFACTURER'S, INCLUDING THE TWO LISTED MANUFACTURERS, WISHING TO BID THEIR
<br />PRODUCT MUST CERTIFY IN WRITING VIA U.S. MAIL TO THE ENGINEER 10 DAYS PRIOR TO BID
<br />DATE (AND AGAIN INCLUDED IN THE SUBMITTAL DOCUMENTS) THAT THE EQUIPMENT PROVIDED
<br />WILL MEET THE LEAVING AIR TEMPERATURE REQUIREMENTS OF PLUS OR MINUS 2.0 DEGREES
<br />FAHRENHEIT IN ALL OPERATIONAL CONDITIONS. THE LETTER OF CERTIFICATION MUST BE SIGNED
<br />BY ONE OF THE MANUFACTURERS CORPORATE OFFICERS IN THE FORM OF A LETTER TO THE
<br />ENGINEER OF RECORD. THE CERTIFICATION LETTER MUST CONFIRM THAT THE SUBMITTED
<br />EQUIPMENT WILL OPERATE THE COMPRESSORS AT AN ENTERING AIR TEMPERATURE TO A
<br />MINIMUM OF THE SPECIFIED EQUIPMENTS DESIGNED LEAVING AIR DEW -POINT, NO
<br />EXCEPTIONS, AND THAT THE UNIT WILL MEET THE LEAVING AIR TEMPERATURE REQUIREMENTS
<br />OF PLUS OR MINUS 2.0 DEGREES FAHRENHEIT IN ALL OPERATIONAL CONDITIONS, NO
<br />EXCEPTIONS. FURTHERMORE, AT NO ADDITIONAL COST TO THE OWNER, THE MANUFACTURER
<br />MUST PROVIDE SUPCO LTH DATA LOGGERS, ACCURATE TO 1.0 DEGREE FAHRENHEIT, MOUNTED
<br />IN THE DISCHARGE AIR AND ENTERING AIR DUCTS, TO TEST THE UNIT FOR LEAVING AIR
<br />TEMPERATURE AND HUMIDITY COMPLIANCE UNDER THE TESTED ENTERING AIR
<br />TEMPERATURE. DATA SHALL BE LOGGED EVERY THREE MINUTES, RECORDED IN AN EXCEL
<br />SPREADSHEET FORMAT WITH CORRESPONDING CHARTS DOCUMENTING THE UNITS
<br />PERFORMANCE, PROVIDED MONTHLY TO THE ENGINEER. DATA SHALL BE CERTIFIED BY THE
<br />MANUFACTURER. TESTING SHALL COMMENCE AT TIME OF BUILDING TURNOVER TO THE OWNER
<br />AND CONTINUE FOR A PERIOD OF 3 MONTHS. FAILURE TO COMPLY WITH THE SPECIFIED
<br />TEMPERATURE AND HUMIDITY CONTROL REQUIREMENTS WILL REQUIRE REMOVAL OF THE
<br />SUBSTANDARD EQUIPMENT AND REPLACEMENT WITH EQUIPMENT COMPLYING WITH THE PROJECT
<br />REQUIREMENTS AT NO ADDITIONAL COST TO THE OWNER. ALL ADDITIONAL TIME REQUIRED IN
<br />RETESTING, MEETING ATTENDANCE BY THE ENGINEER, AND DATA REVIEW SHALL BE PAID FOR
<br />BY THE MANUFACTURER OF THE SUBSTANDARD EQUIPMENT.
<br />CONSULTING
<br />ENGINEERING
<br />ASSOCIATES
<br />SEAL
<br />8365 GUNN HIGHWAY
<br />TAMPA, FL 33626
<br />(81W) 448-0225
<br />FAX (813) 448-0226
<br />EB - 0003962
<br />Mechanical Plumbing
<br />Fire Protection
<br />BIDDING DOCUMENTS
<br />SIGNATURE DATE
<br />JOHN W. WELLS, III, PE
<br />PE 0049347
<br />zN
<br />O�
<br />LO
<br />p
<br />M
<br />�a
<br />u�
<br />wo
<br />U.
<br />J
<br />OCo
<br />� J
<br />J = ~
<br />2W W
<br />�- N W
<br />aW U
<br />W � J
<br />N
<br />Lim W
<br />0
<br />..moo �U
<br />WLU
<br />mr
<br />�� �a
<br />REVISIONS
<br />delta date revision
<br />SHEET TITLE
<br />HVAC
<br />DETAILS AND
<br />SCHEDULES
<br />SHEET NO.:
<br />M-
<br />TMH/ JWW
<br />02/12/19
<br />18010
<br />501