PROJECT SCOPE:
<br />I
<br />MECHANICAL SPECIFICATIONS
<br />SCOPE• THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE THE DRAWINGS AND SPECIFICATIONS BEFORE SUBMITTING A PROPOSAL
<br />LIMITED TO THE ADDITION OF TRANSFER AIR
<br />GRILLES AND THE RELOCATION OF TWO
<br />DIFFUSERS ONLY.
<br />TO ACCOMMODATE THE PROPOSED NEW
<br />ENTRY VESTIBULES AT BOTH ENDS OF THE
<br />BUILDING.
<br />ALL WORK SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODES SIXTH EDITION (2017), WITH ALL AMENDMENTS, AND LOCAL CODES AND ORDINANCES. INSTALLATION SHALL COMPLY WITH THE CODE REFERENCED STANDARDS SET BY NFPA,
<br />ASHRAE, ASPE, SMACNA, NEC AND UL. THE SYSTEMS, EQUIPMENT, DEVICES AND ACCESSORIES SHALL BE INSTALLED, FINISHED, TESTED AND ADJUSTED FOR CONTINUOUS AND PROPER OPERATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR HIS
<br />WORK FITTING IN PLACE AND SHALL COORDINATE WITH OTHER TRADES TO AVOID INTERFERENCE WITH THEIR WORK. THE INFORMATION GIVEN HEREIN AND ON THE DRAWINGS IS AS EXACTAS COULD BE SECURED, BUT ITS EXTREME ACCURACY IS NOT
<br />GUARANTEED. THE DRAWINGS ARE DIAGRAMMATIC, INTENDED TO SHOW GENERAL ARRANGEMENT, CAPACITY AND LOCATION OF VARIOUS COMPONENTS, EQUIPMENTS, AND DEVICES. IF WORK IS REQUIRED IN A MANNER TO MAKE IT IMPOSSIBLE TO PRODUCE
<br />FIRST CLASS WORK, OR SHOULD DISCREPANCIES APPEAR AMOUNG THE CONTRACT DOCUMENTS, OR BETWEEN THE CONTRACT DOCUMENTS AND THE MANUFACTURER'S RECOMMENDATIONS,THE CONTRACTOR SHALL REQUEST INTERPRETATION BEFORE
<br />PROCEDING WITH WORK. CONTRACTOR SHALL FURNISH AND INSTALL ALL MINOR ITEMS WHICH ARE OBVIOUSLY AND REASONABLY NECESSARY TO COMPLETE THE INSTALLATION WHETHER OR NOT SPECIFIED IN THE DOCUMENTS.
<br />REQUIRED COORDINATION: ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS AND PIPING (INCLUDING DIVIDED DUCTS) AND TRANSITIONS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE
<br />OWNER.
<br />CONSTRUCTION PLANS: IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED.
<br />REQUIRED ACCESS: CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT AND DEVICES THAT REQUIRE REPLACEMENT, SERVICING, ADJUSTING OR MAINTENANCE SHALL BE LOCATED TO ALLOW EASY ACCESS AND SPACE FOR REMOVAL OF INTERNAL ASSMBLIES,
<br />IF REQUIRED. CONTRACTOR SHALL PROVIDE ACCESS PANELS WHERE REQUIRED TO ALLOW ACCESS, EVEN IF NOT INDICATED ON THE DRAWINGS AT NO ADDITIONAL COST TO OWNER.
<br />DIMENSIONAL DATA: ALL DUCTWORK DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS.
<br />SUPPLEMENTARY SUPPORTS: CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND MECHANICAL EQUIPMENT AND MATERIALS, IN ORDER TO PROVIDE A "VIBRATION —FREE" RIGID INSTALLATION.
<br />DUCTWORK — GENERAL: FABRICATE AND INSTALL ALL DUCTWORK AND DUCT ACCESSORIES IN ACCORDANCE WITH THE LATEST EDITION OF APPLICABLE SMACNA STANDARDS, THE LATEST NFPA STANDARDS, AND THIS SPECIFICATION. THE MOST STRINGENT
<br />OF THESE SHALL BE THE MINIMUM STANDARD. MINIMUM OF 1" PRESSURE CLASS RATING FOR ALL DUCTWORK.
<br />TRANSFER DUCTWORK BOXES SHALL BE R-4.2 RIGID FIBERGLASS DUCTBOARD (UL-181 AND 181A) WITH CLEANABLE AIRSIDE SURFACE AND EPA —APPROVED BIOCIDE (ANTI —MICROBIAL AGENT) IMPREGNATED IN MATTED AIR —SIDE SURFACE.
<br />OVEN EXHAUST DUCTWORK SHALL BE PRE —FABRICATED DOUBLE —WALL GREASE DUCT, EQUAL TO SELKIRK METALBESTOS #8—IPS—CI, RATED FOR 3" CLEARANCE TO COMBUSTIBLES. SUBSTITUTION MAY BE 16—GAUGE BLACK STEEL, WELDED LIQUIDTIGHT PER
<br />NFPA-96
<br />DUCTWORK INSTALLATION: ALL INTERIOR DUCTWORK SHALL BE SEALED TO SMACNA CLASS (B) REQUIREMENTS. CONTRACTOR SHALL FURNISH AND INSTALL ALL DUCT OFFSETS AS REQUIRED TO CLEAR INTERFERENCES WITH EXISTING BUILDING STRUCTURE,
<br />PIPES AND ELECTRICAL CONDUITS. FURNISH AND INSTALL ALL MISCELLANEOUS STEEL SUPPORTS REQUIRED FOR HANGING AND SUPPORTING DUCTWORK UNLESS OTHERWISE NOTED.
<br />FLEXIBLE DUCTWORK: FLEXIBLE DUCTWORK MAY BE USED FOR THE FINAL RUNOUTS TO AIR OUTLETS, AND SHALL BE SIZED TO MATCH AIR OUTLET NECK. FLEXIBLE DUCTS SHALL NOT EXCEED 8—FEET LENGTHS. NO FLEXIBLE DUCTS SHALL PENETRATE
<br />FIRE —RATED WALLS OR CEILINGS. FLEXIBLE DUCTS SHALL COMPLY WITH THE PROVISIONS OF UL-181 CLASS 1 AIR DUCT MATERIAL. DUCTS SHALL BE FACTORY MADE AND COMPOSED OF: AN INNER FIBERGLASS WOVEN LINER, ENCAPSULATED HELIX COIL,
<br />A FIBERGLASS INSULATING BLANKET AND OUTER VAPOR BARRIER OF FIBERGLAS REINFORCED METALIZED FILM LAMINATE. PROVIDE THERMAFLEX MK—C FLEXIBLE DUCT OR APPROVED EQUAL (MIN. OF R-6.0). CARE IS TO BE TAKEN THAT ALL RUNOUTS
<br />OF FLEXIBLE DUCTS ARE INSTALLED AS STRAIGHT AS PRACTICAL AND FASTENED SO AS TO ELIMINATE AIR LEAKAGE. THE INSTALLATION SHALL CONFORM TO THE TECHNIQUES SHOWN IN THE UL APPROVED AND FACTORY —SUPPLIED INSTRUCTIONS.
<br />GRILLES AND DIFFUSERS: ALL GRILLES AND DIFFUSERS SHALL BE INSTALLED WITH AN INSULATED BOOT OR BLANKET. PROVIDED A METHOD OF VOLUME CONTROL BY DEVICE ADJUSTABLE AT DIFFUSER FACE OR MANUAL VOLUME DAMPERS AT TAKEOFF
<br />BRANCHES. COORDINATE DIFFUSER AND GRILLE LOCATIONS WITH ELECTRICAL LIGHTING LAYOUT AND ARCHITECTURAL REFLECTED CEILING PLAN.
<br />SUBMITTALS REQUIRED:
<br />SUBMIT SHOP DRAWINGS FOR ALL MATERIALS, EQUIPMENT, AND SYSTEMS REQUIRED BY THESE DOCUMENTS (SEE ARCH. PLANS/SPECS FOR SPECIFIC FORMATTING), INCLUDING:
<br />DIFFUSERS AND GRILLES
<br />DUCTWORK, INSULATION AND ACCESSORIES (CONNECTIONS, MASTICS, ETC.)
<br />SUBSTITUTIONS: CONTRACTOR SHALL PAY FOR ANY AND ALL ADDED COSTS ASSOCIATED WITH ANY SUBSTITUTION, INCLUDING SUBSTITUTIONS THAT REQUIRE CHANGES TO THE OTHER BUILDING COMPONENTS, SUCH AS ELECTRICAL, STRUCTURAL REINFORCING,
<br />CEILINGS, WALLS, ROOFS, ETC. THIS WILL INCLUDE ANY ENGINEERING/ARCHITECTURAL RE —DESIGN COSTS AS A RESULT OF SAID SUBSTITUTION. THESE COSTS SHALL NOT BE BORNE BY THE OWNER, ARCHITECT, NOR ENGINEER, REGARDLESS OF
<br />ACCEPTABILITY OF SUBSTITUTION. ENGINEER RESERVES THE RIGHT TO ACCEPT OR DENY ANY SUBSTITUTION THAT HE DOES NOT DEEM TO BE EQUIVALENT, AND CONTRACTOR SHALL PROVIDE SPECIFIED OR EQUIVALENT MATERIALS/EQUIPMENT AT NO
<br />ADDITION COST TO OWNER, SHOULD A SUBSTITUTION BE DENIED.
<br />GUARANTEE: THE ONE—YEAR GUARANTEE PERIOD SHALL NOT START UNTIL THE PROJECT IS FULLY COMPLETED AND THE CONTRACTOR HAS RECEIVED THE FINAL PAYMENT AND CERTIFICATION OF OCCUPANCY. ALL EQUIPMENT AND ALL WORK SHALL BE
<br />FULLY GUARANTEED, PARTS AND LABOR, FOR ONE YEAR FROM THE DATE OF THE CERTIFICATE OF COMPLETION. REPAIRS MADE DURING THIS PEROID MUST BE FULLY GUARANTEED FOR AN ADDITIONAL ONE YEAR PERIOD FROM THE DATE OF REPAIRS. IN
<br />ADDITION, THE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE TO THE BUILDING, AND ITS CONTENTS OR OTHER EQUIPMENT, CAUSED BY DEFECTS OR IMPROPER INSTALLATION OF EQUIPMENT OR MATERIAL INSTALLED.
<br />AIR DEVICE SCHEDULE
<br />GENERAL
<br />CONSTRUCTION
<br />MARK
<br />TYPE
<br />FUNCTION
<br />FRAME SIZE
<br />PATTERN
<br />MATERIAL
<br />FINISH
<br />MFG.
<br />MODEL
<br />RGC
<br />CEILING GRILLE
<br />RETURN
<br />SEE PLANS
<br />BLADES
<br />ALUMINUM
<br />WHITE
<br />PRICE
<br />630
<br />MAXIMUM SAG 1/2-
<br />PER FOOT OF
<br />SUPPORT SPACING
<br />1-1 /2"x22 GA. WIDE BAND CLAMP
<br />SADDLE
<br />7-1-1/2"x22 GA. WIDE
<br />1-1 /2" x 22 GA. SADDLE BAND CLAMP
<br />HANGER AND SUPPORT FOR FLEXIBLE DUCTS
<br />NO SCALE
<br />SPIN —IN COLLAR (INSULATED)
<br />WITHOUT VOLUME DAMPER
<br />(TYPICAL)
<br />INSULATED FLEXIBLE DUCT
<br />/— INSULATED SUPPLY BOX
<br />IIVl1�J1 LI\ VI\ILLLJ
<br />(SEE PLANS FOR TYPE)
<br />TRANSFER DUCT DETAIL
<br />SCALE: NONE
<br />INSULATING BLANKET
<br />VOLUME LEVER
<br />CEILING
<br />ELEV.
<br />EQUIP
<br />ROOM
<br />WORK
<br />ROOM
<br />BREAK
<br />ROOM
<br />FRONT
<br />(E) 6-0
<br />ENTRY
<br />SUPPLY =
<br />F-�I
<br />I
<br />I�_�I
<br />MOVE (2) DIFFUSERS;
<br />TO NEW LOCATION
<br />GRI
<br />1_xfki Lq
<br />� -E- AHU
<br />(5fT(
<br />it t
<br />OFFICE
<br />I
<br />TELLER AREA
<br />WORT(
<br />ROOM
<br />OFFICE
<br />CONFERENCE
<br />ROOM
<br />'1I r1� I i
<br />COUPON
<br />1 f F I , (E)CU-4
<br />(E)AHU-4 I I
<br />(.w.
<br />MEN �.
<br />(5—TON)<-�:W,:::.-:�.
<br />RECEPTION
<br />r' OFFICE j
<br />LOBBY
<br />,A
<br />(E) 6"0 T I ,COUPON
<br />SUPPLY
<br />-_ �TYI,
<br />— � I CUSTOMER/ � y
<br />SERVICE
<br />SUPPLY I---- _
<br />1 I _
<br />TGC-24x24
<br />" (TYP-2)
<br />8 I ' EXISTING DUCTWORK I
<br />LAND DIFFUSERS (TYP)
<br />_
<br />----------Fjw,
<br />Ab
<br />/ 1 I WORK AREA
<br />Fx
<br />17 I
<br />L- — — — — — —
<br />OFFICE II OFFICE
<br />MECHANICAL -1 ST FLOOR PLAN
<br />SCALE: 1/8" me V-0"
<br />OFFICE
<br />VAULT
<br />NEW RETURN GRILLES
<br />,
<br />FOR TRANSFER
<br />1 "
<br />(SEE DETAIL)
<br />1 "0
<br />TGC-24x24
<br />(TYP-2)
<br />jo
<br />(E) 6"0 l E
<br />SUPPLY
<br />�._.� 6"0
<br />WOMEN
<br />,DOOR UNDERCUT ( —{
<br />REAR
<br />ENTRY i 1!
<br />E
<br />r41
<br />ma (
<br />OFFICE j�� E-T�=
<br />STOW
<br />_ _....................... _...
<br />.
<br />OFFICE
<br />STAR
<br />I HVAC LEGEND
<br />17-ill SUPPLY AIR DIFFUSER
<br />��� RETURN/TRANSFER AIR GRILLE
<br />NEW DUCTWORK, WITH SIZE LISTED
<br />FLEXIBLE DUCT
<br />SD —
<br />DUCT SMOKE DETECTOR
<br />—�
<br />FIRE DAMPER
<br />QT
<br />THERMOSTAT BASE
<br />Q
<br />REMOTE TEMPERATURE SENSOR
<br />0
<br />ROUND, DIAMETER
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />CFM
<br />CUBIC FEET PER MINUTE
<br />TYP
<br />TYPICAL — ITEM OR METHOD
<br />VD / L_
<br />MANUAL VOLUME DAMPER (W/HANDLE)
<br />SUPPLY DUCT TAKE —OFF WITH VD
<br />(N)
<br />NEW
<br />(E)
<br />EXISTING
<br />.-=*
<br />CONNECT NEW TO EXISTING
<br />DIFFUSER TAG
<br />AIRFLOW
<br />EQUIPMENT TAG
<br />r—TEQUIPMENT
<br />400
<br />CFM
<br />RTU-1
<br />CD-12"0
<br />MARK
<br />�
<br />EQUIPMENT
<br />SIZE
<br />NUMBER
<br />NOTE TO CONTRACTOR
<br />ON EXISTING CONDITIONS:
<br />1. CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID
<br />AND SURVEY ALL EXISTING CONDITIONS AND
<br />EQUIPMENT PRIOR TO SUBMITTING BID FOR WORK
<br />REQUIRED BY THESE DOCUMENTS. THIS
<br />INCLUDES ABOVE THE CEILING AND ON TOP OF
<br />THE ROOF.
<br />2. CONTRACTOR SHALL REFER TO AND READ
<br />THROUGH ALL OF THE "CONTRACTOR'S SCOPE OF
<br />WORK" AS DEFINED IN THE BID SPECIFICATIONS
<br />AND DOCUMENTS AS PART OF THE BID PROCESS.
<br />3. IF AT ANY TIME. THERE IS DISCREPANCY BETWEEN
<br />THE PLANS & SPECS. OR CONFUSION/CONCERN
<br />OVER REQUIRED WORK. CONTRACTOR SHALL
<br />IMMEDIATELY NOTIFY ARCHITECT. ENGINEER. &/OR
<br />OWNER AND GET DIRECTION BEFORE PROCEEDING
<br />WITH WORK IN QUESTION,
<br />I
<br />No 56189
<br />p ' STATE OF
<br />��i F • ; O R
<br />SO N A ittlest I
<br />STEPANEK—LEWIS
<br />�2ELVE
<br />ASSOCIATES
<br />OAKS WAY, SUITE 103
<br />WESLEY CHAPEL, FL 335"
<br />PH (813) 991-1248
<br />MATTHEW D. LEWIS, P.E. FL LIC#56189
<br />THE
<br />LUNZ
<br />GROUP
<br />585 Main Street, Suite 201
<br />Dunedin, FI 34698
<br />p 727.733.9400
<br />f 727.733.9555
<br />IiC. AA0001580
<br />lunz.com
<br />3
<br />CM
<br />m
<br />N O3
<br />� Q
<br />M7 LL_
<br />W
<br />_ N
<br />m f
<br />T
<br />to A
<br />REVISION&• • . .... . . •
<br />REVISION& • • . . .
<br />REVISION& ... . ... . . .
<br />ISSUED FOR CONSTRUCTION: --
<br />ISSUED FOR PERMIT: OZOZ18
<br />ISSUED FOR BID: --
<br />ISSUED FOR APPROVAL• --
<br />DRAWN BY: KB, TJ
<br />REVIEW BY: ML