FIRE ALARM NOTES: <br />SEQUENCE OF OPERATION: <br />1. THE FIRE ALARM SYSTEM SHALL OPERATE AS FOLLOWS: <br />A. MANUAL PULL STATION: <br />1) IDENTIFY THE INDIVIDUAL STATION ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE ALARM AT THE FACP, <br />3) ILLUMINATE THE ALARM RED LED, <br />4) SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES) <br />IN THE BUILDING ('WHERE THE ALARM ORIGINATED ONLY). <br />B. AN AREA SMOKE DETECTOR OR HEAT DETECTOR ,OR SPRINKLER WATER - <br />FLOW SWITCH SHALL CAUSE THE FOLLOWING: <br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION. <br />2) A SIGNAL DEDICATED TO THE SPRINKLER SYSTEM WATER -FLOW ALARM <br />SHALL NO BE ABLE TO BE SILENCED. <br />C. SMOKE & HEAT DETECTORS FOR ELEVATOR RECALL: <br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION. <br />2) ACTIVATION OF ELEVATOR LOBBY SMOKE DETECTOR ON THE PRIMARY <br />FLOOR SHALL INITIATE ELEVATOR RECALL TO THE ALTERNATIVE FLOOR. <br />3) ACTIVATION OF 2nd FLOOR AND ABOVE FLOORS ELEVATOR LOBBY OR <br />ELEVATOR MACHINE ROOM SMOKE DETECTORS SHALL INITIATE ELEVATOR <br />RECALL TO THE PRIMARY FLOOR, <br />4) ACTIVATION OF ELEVATOR MACH RM HEAT DETECTOR SHALL INITIATE ELEV. <br />RECALL TO PRIMARY FLOOR AND SHUT POWER TO THE ELEVATOR EQUIPMENT. <br />D. SMOKE DUCT DETECTORS: <br />1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP. <br />3) ILLUMINATE THE SUPERVISORY LED. <br />4) SHUT DOWN ITS RESPECTIVE AIR HANDLER UNIT. <br />E. FLOW BELL: <br />1) FLOW BELL SHALL SOUND UPON THE ACTIVATION OF FLOW SWITCH ONLY. <br />2) FLOW BELL SHALL SOUND AS LONG AS THE WATER IS FLOWING. <br />3) FLOW BELL SHALL NO BE CAPLABLE OF BEING SILENCED FROM THE FACP. <br />F. ACTIVATION OF ANY SUPERVISORY CIRCUIT OR TAMPER SWITCH SHALL CAUSE THE <br />FOLLOWING ACTIONS AND INDICATIONS: <br />1) IDENTIFY THE INDIVIDUAL CIRCUIT OR DEVICE ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP. <br />3) ILLUMINATE THE SUPERVISORY LED. <br />G. RECEIPT OF A TROUBLE SIGNAL AT THE FACP SHALL CAUSE THE <br />FOLLOWING ACTIONS AND INDICATIONS: <br />1) IDENTIFY THE ORIGIN OF THE TROUBLE ON THE SYSTEM CONTROL PANEL. <br />2) SOUND THE LOCAL AUDIBLE TROUBLE SIGNAL AT THE FACP. <br />3) ILLUMINATE THE TROUBLE LED. <br />TYPICAL SPRINKLER CLOSET WITH FIRE ALARM PANEL <br />INSTALLATION DIAGRAM. <br />t 1 1 t <br />• I <br />--/7 2 <br />Ir <br />FACP • <br />FCPS <br />EL I <br />MAIN TAMPERS AND WATERFLOWS <br />s <br />Breaker Box <br />CENTRAL STATION / TRANSMISSION OF SIGNALS / MONITORING <br />- ALL SIGNALS (ALARM/ TROUBLE/SUPERVISORY) WILL BE TRANSMITTED TO THE <br />CENTRAL STATION. <br />- THE MEANS OF TRANSMISSION ARE PHONE LINES. <br />- ALL SIGNALS WILL BE TRANSMITTED AS FOLLOWS: <br />A POINT ADDRESSABLE SIGNAL WILL BE TRANSMITTED TO THE CENTRAL STATION, <br />SYSTEMS POINTS WILL BE IDENTIFY AT THE CENTRAL STATION AS FOLLOW: <br />DEVICE TYPE ( PULL STATION, SMOKE, ETC) + DEVICE LOCATION <br />(FLOOR + GENERAL DESCRIPTION) + INDIVIDUAL BUILDING PHYSICAL ADDRESS <br />OR BUILDING NUMBER. <br />- THE FIRE ALARM DIALER IS AN OPTIONAL BOARD THAT MOUNTS INSIDE <br />THE FIRE ALARM CABINET ON TOP OF THE FIRE ALARM MAIN BOARD. <br />CODES & PLAN NOTES <br />- ALL DRAWINGS ARE SCALED TO 1/8 = 1Ft UNLESS OTHERWISE NOTED. <br />- COORDINATE WITH SPRINKLER CONTRACTOR EXACT LOCATION OF ALL <br />TAMPER AND FLOW SWITCHES. <br />- INSTALL SPLICE/CHECK BOX IN ALL 1 ST FLOOR APARTMENT'S <br />BATHROOMS. <br />- CONFIRM LOCATION OF POWER SUPPLIES IN BLDGS PRIOR TO ROUGH IN. <br />- REFER TO FLOOR PLANS FOR LOCATION OF DUCT DETECTORS (SUPPLY OR <br />RETURN SIDE), COORDINATE WITH MECHANICAL CONTRACTOR THE ACTUAL <br />LOCATIONS OF THE AHUs. <br />- ALL STROBES WILL BE SET @ 75cd UNLESS NOTED. <br />- CEILING HEIGHT IS 10ft UNLESS NOTED. <br />- UNDERGROUND WIRE USED AS SLC FOR COMMUNICATION BETWEEN BUILDINGS <br />IS SUITABLE FOR WET LOCATIONS / DIRECT BURIAL. <br />- ANY PROPOSED INTERCONNECTION OF PANELS WILL BE A "NON -LATCHING" <br />CONFIGURATION PANEL RESET FROM 1 LOCATION. <br />- FIRE ALARM SYSTEM PROVIDED IS FULLY ADDRESSABLE. <br />- SMOKE DETECTORS FOR SMOKE COMPARTMENTS WILL BE PROVIDED <br />AS PER NFPA-72 17.7.5.6.5.1 (A) <br />- COORDINATE WITH MECHANICAL CONTRACTOR LOCATION OF SMOKE DAMPERS <br />- SINGLE STATION 120 AC SMOKE DETECTOR PROVIDED BY ELECTRICAL CONTRACTOR <br />ON SEPARATE PERMIT. <br />- ELECTRICAL LOAD, PANEL, BREAKER LOCKOUT IS ON SEPARATE PERMIT <br />PERMIT . FBC 107.2 <br />- INSTALLATION SHALL BE IN ACCORDANCE WITH FFPC 5TH ED.AND NFPA 72 2010 ED <br />- 24/5 STANDBY TEST IS REQUIRED BEFORE FINAL FIRE, IF BUILDING IS OCCUPIED <br />DURING THIS TEST, FIREWATCH WILL BE REQUIRED. <br />- ALL SYSTEM WIRING SHALL COMPLY WITH NFPA-70 ARTICLE 760. <br />- ALL AUDIBLE DEVICES LOCATED INSIDE SLEEPING AREAS MEET NFPA-72 (2013) <br />18.4.5.3 FOR LOW FREQUENCY REQUIREMENTS <br />" 24/5 STANDBY TEST REQUIRED IF ANY PART OF THE BLDG IS OCCUPIED <br />BY TENANTS DURING THIS TEST. A FIRE WATCH IS REQUIRED FROM <br />7AM-7PM. THIS PERSON WILL BE A TAMPA INSPECTOR. <br />EXTERIOR MAIN TAMPERS, BACKFLOWS, ETC. <br />INSTALLATION NOTES: <br />0 120vac Line in 112" or 3/4" EMT conduit, PVc or Flex supplied by electrical contractor. <br />Q 120vac surge protector, supplied by Fire Alarm contractor, Installed by Electrical Contractor on <br />Electrical breaker Panel <br />Splice Box, Installed and Supplied By Electrical Contractor. <br />@FACP. Supplied and Installed by Fire Alarm Contractor. <br />Q FCPS, Supplied and Installed by Fire Alarm Contractor. <br />Q 14- EMT Conduit or Flex Supplied By Electrical Contractor. <br />@PVC Box 6x6x4, Supplied and Installed by Electrical Contractor. <br />0 3/4" PVC Conduit for Underground Connection Front/To other Fire Alarm Closets. <br />Q WaterFlow Sensor. <br />@ Water Tamper. <br />Surge Protector, Supplied and Installed BY Fire Alarm Contractor. <br />3/4" EMT Conduit or Flex Supplied By Electrical Contractor. <br />@ 4 Square PVC Splice Box, Supplied and Installed by Fire Alarm Contractor. <br />@ 1/2" or 3/4" PVC Conduit or Seal tight Flex Supplied By Electrical Contractor. <br />® 3/4" PVC Conduit for Underground Connection To Outside Tampers. <br />0 Single gang Box attached to Water Tamper, Supplied and Installed By El3ctrical Contractor. . <br />Q 4 Square Box with Rised P-Ring For Smoke Detector, Supplied By Electrical <br />Contractor. <br />@Breaker Lock, Supplied By Electrical Contractor. <br />ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING ALL THE <br />NECESSARY HARDWARE (BOXES, CONNECTORS, CONDUITS, Etc.) AS WELL <br />AS PARTIAL INSTALLATION AS PER INSTALLATION NOTES. <br />ELEVATOR SEQUENCE OF OPERATION: <br />1. ACTIVATION OF ANY OF THE FOLLOWING DEVICES SHALL INITIATE THE ELEVATOR RECALL <br />FUNCTION FOR THE AFFECTED ELEVATOR(S), <br />1.1 ELEVATOR LOBBY SMOKE DETECTOR. <br />1.2 ELEVATOR MACHINE ROOM SMOKE DETECTOR. <br />1.3 ELEVATOR HOISTWAY SMOKE DETECTOR. <br />2. ACTIVATION OF ANY OF THE FOLLOWING DEVICES SHALL ACTIVATE (OPEN) THE SHUNT <br />TRIP CIRCUIT BREAKER FOR THE AFFECTED ELEVATOR(S). <br />2.1 ELEVATOR MACHINE ROOM HEAT DETECTOR. <br />2.2 ELEVATOR HOISTWAY HEAT DETECTOR. <br />3. ACTIVATION OF ANY OF THE FOLLOWING DEVICES SHALL INITIATE, FOR THE AFFECTED <br />ELEVATOR(S), A SEPARATE AND DISTINCT SIGNAL THAT INDICATES THE ELEVATOR IS NO <br />LONGER SAFE TO USE: <br />3.1 ELEVATOR MACHINE ROOM SMOKE DETECTOR. <br />3.2 ELEVATOR HOISTWAY SMOKE DETECTOR. <br />4. THE FOLLOWING CONDITION SHALL INITIATE THE FIRE ALARM SUPERVISORY SIGNAL: <br />4.1 ELEVATOR SHUNT TRIP CIRCUIT LOSS OF POWER. <br />5. ELEVATOR RECALL FUNCTIONS SHALL BE PROVIDED AS REQUIRED BY NFPA-72 AND <br />ANSI A17.1: <br />5.1 ACTIVATION OF <br />AN INITIATING DEVICE AT ANY FLOOR OTHER THAN THE <br />DESIGNATED <br />LEVEL SHALL CAUSE THE AFFECTED ELEVATOR(S) THAT SERVE THAT FLOOR <br />TO BE <br />RECALLED NON-STOP TO THE DESIGNATED LEVEL. <br />5.2 ACTIVATION OF <br />AN INITIATING DEVICE AT THE DESIGNATED LEVEL SHALL <br />CAUSE <br />THE AFFECTED ELEVATOR(S) THAT SERVE THAT FLOOR TO BE RECALLED TO <br />AN <br />ALTERNATE LEVEL. <br />5.3 ACTIVATION OF <br />AN INITIATING DEVICE IN THE MACHINE ROOM SHALL CAUSE <br />THE VISUAL SIGNAL <br />TO ILLUMINATE INTERMITTENTLY ONLY IN THE ELEVATOR <br />CARD(S) <br />WITH EQUIPMENT IN <br />THAT MACHINE ROOM. <br />5.4 ACTIVATION OF <br />AN INITIATING DEVICE IN THE HOISTWAY SHALL CAUSE <br />THE VISUAL SIGNAL <br />TO ILLUMINATE INTERMITTENTLY ONLY IN THE ELEVATOR <br />CARD(S) <br />WITH EQUIPMENT IN <br />THAT HOISTWAY. <br />6. ELEVATOR SHUTDOWN FUNCTIONS SHALL BE PROVIDED AS REQUIRED BY NFPA-72 AND <br />ANSI A17.1: <br />6.1 ACTIVATION OF A HEAT DETECTOR IN THE MACHINE ROOM SHALL DISCONNECT <br />THE MAIN LINE POWER TO THE AFFECTED ELEVATOR(S). <br />6.2 ACTIVATION OF A HEAT DETECTOR IN A HOISTWAY SHALL DISCONNECT <br />THE MAIN LINE POWER TO THE AFFECTED ELEVATOR(S). <br />is <br />R <br />E <br />5 <br />T <br />O <br />P <br />S <br />Y <br />5 <br />T <br />E <br />M <br />THROU614-PENETRATION DETAIL <br />5Y5TEM No. F-A-1015 <br />F"Ini _1 up <br />I. FLOOR ASSEMBLY - THE FIRE -RATED UNPROTECTED CONCRETE AND STEEL FLOOR <br />ASSEMBLY SHALL 13E CONSTRUCTED OF THE MATERIALS AND IN THE MANNER <br />SPECIFIED IN THE INDIVIDUAL D400 SERIES DE5ISNS IN THE U.L. FIRE RESISTANCE <br />DIRECTORY AND AS SUMMARIZED BELOK <br />A. CONCRETE - MIN 2 IN THICK REINFORCED Ll&rr C7HT OR NORMAL WEIGHT <br />000-150 PCF) CONCRETE. <br />B. STEEL FLOOR AND FORM UMTS• - COMPOSITE OR NON -COMPOSITE MAX <br />3 IN. DEEP SALV FLUTED UNITS A5 SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING <br />DESION. MAX DIAM OF OPENNe 15 6 IN. <br />2. THROUGH PENETRANTS - ONE METALLIC, PIPE, CONDWT OR TUBING INSTALLED <br />EITHER CONCENTRICALLY OR E=31TRICALLY WITHIN THE FIRESTOP SYSTEM. <br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THHROUeH <br />OPENING SHALL BE MIN O IN. (POINT CONTACTS) TO MAX 1-1/6 IN. PIPE, CONDUIT OR <br />TUBING TO BE RIODLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. <br />THE FOLLOMW TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY <br />BE USED+ <br />A. STEEL PIPE <br />S. IRON PIPE <br />G. C.ONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELEGTRIGAL METALLIC, <br />TUBING OR STEEL CONDUIT. <br />D. COPPER TIEING <br />E. COPPER PIPE <br />3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING+ <br />PAGKINe MATERIAL - MIN I-V2' IN. THIGKlE55 OF MIN 4 PCF DENSITY MINERAL <br />WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. <br />PACKING MATERIAL TO 13E RCC.ESSED FROM TOP SURFACE OF FLOOR AS <br />REWRED TO ACC.OMODATE THE REQWRED THICKNESS OF FILL MATERIAL t1TEM 3B). <br />FILL, VOID OR CAVITY MATERIAL0 - SEALANT - MIN 1/2 IN. THICKNESS OF FILL <br />MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR. AT <br />POINT CONTACT LOCATION BETWEEN PENETRANT AND CONCRETE, A MIN 1/2 IN. <br />DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE 0ONCRETEIPENETRANT <br />INTERFACE ON TOP SURFACE OF FLOOR. <br />FIRESTOP SYSTEM INC. - 000 DW I <br />« BEARING THE UL CLA551FICATION MARKING <br />THROUC H-PENETRATION DETAIL <br />5Y5TEM No. W-J-1048 <br />I <br />F RATINGS - 2 HR <br />E <br />A <br />C.J <br />� . yr <br />�••�,'JtM <br />T <br />O <br />P <br />2 �.. <br />A <br />S <br />r <br />Y <br />SECTION A -A <br />S <br />T <br />1. WALL ASSEMBLY - MIN 6-1/6 IN. THICK NORMAL WEIGHT OR LleHTMiSHT <br />E <br />000-15OPC -) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY Ul.. <br />CLASSIFIED CONCRETE BLOCKS". MAX DIAM OF OPENING 15 14-1/8 IN. <br />M <br />SEE CONCRETE BLOCKS (CAZT) GAT5SORY IN THE FIRE RESISTANCE DIRECTORY <br />FOR NAME OF MANUFACTURERS. <br />2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED <br />EITHER GONCOMOALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. <br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF <br />OPENING SHALL BE MIN 3/6 IN. TO MAX I IN. PIPE, CONDUIT OR TUBING TO BE <br />R161DLY SUPPORTED ON BOTH 510E5 OF WALL ASSEMBLY. THE FOLLOWING <br />TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY 13E USED. <br />A. STEEL PIPE <br />S. IRON PIPE <br />G. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLEW STEEL ELECTRICAL METALLIC, <br />TUBING (EMT) OR STEEL CONDUIT. WHEN EMT OR STEEL CONDUIT 15 USED <br />T RATING 15 1/4 HP. <br />D. COPPER TUBING <br />E. COPPER PIPE <br />3. FILL, VOID OR CAVITY MATERIALS - SEALANT - MIN 1-1/4 IN. THICKNESS <br />OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES <br />OF WALL. <br />FIRESTOP SYSTEMS, INC. - PLOWBUARD eOLD FIRESTOP SEALANT <br />• BEARING THE UL CLAS5IFIGATION MARKING. <br />"CADDY" T-GRID BOX HANGER <br />SUPPORT, OR EQUAL. "CADDY'-' <br />REFERENCE NO. CEC 30-302(3). <br />sec <br />a <br />ELECTRICAL MOUNTING BOX <br />FOR THE CEILING MOUNTED <br />NOTIFICATION DEVICES. <br />ACOUSTICAL TILE CEILING <br />GRID SUPPORT FRAMING. <br />CEILING GRID ELECTRICAL BACK -BOX ATTACHMENT <br />NTS <br />AU At`tIICABL1 !1111111.1t00Q1 <br />&UWFIUCA "Pi,I 400 AM <br />t42Ck& CAL CUM, <br />REVIEW DA17 <br />C►TYOFZEPHY <br />®UII,DING OFFICIAL <br />II• <br />Kiperal�Rri rd vu iYTfr <br />Fire Alarm & Communications <br />■ <br />SUPERIOR FIRE ALARM & <br />COMMUNICATIONS <br />6201 JOHNS RD <br />SUITE 9 <br />TAMPA, FL 33634 <br />813- 818- 4444 <br />CERTIFIED ALARM SYSTEM <br />CONTRACTOR 1 <br />LICENSE EF 20001162 <br />■ <br />CAD DATE: 05/18/2016 <br />E <br />Ruo4y,,Puga <br />EF A 20'001162 <br />SHEET: <br />NOTES <br />i, <br />�:. <br />PM <br />