FIRE ALARM NOTES:
<br />SEQUENCE OF OPERATION:
<br />1. THE FIRE ALARM SYSTEM SHALL OPERATE AS FOLLOWS:
<br />A. MANUAL PULL STATION:
<br />1) IDENTIFY THE INDIVIDUAL STATION ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE ALARM AT THE FACP,
<br />3) ILLUMINATE THE ALARM RED LED,
<br />4) SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES)
<br />IN THE BUILDING ('WHERE THE ALARM ORIGINATED ONLY).
<br />B. AN AREA SMOKE DETECTOR OR HEAT DETECTOR ,OR SPRINKLER WATER -
<br />FLOW SWITCH SHALL CAUSE THE FOLLOWING:
<br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION.
<br />2) A SIGNAL DEDICATED TO THE SPRINKLER SYSTEM WATER -FLOW ALARM
<br />SHALL NO BE ABLE TO BE SILENCED.
<br />C. SMOKE & HEAT DETECTORS FOR ELEVATOR RECALL:
<br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION.
<br />2) ACTIVATION OF ELEVATOR LOBBY SMOKE DETECTOR ON THE PRIMARY
<br />FLOOR SHALL INITIATE ELEVATOR RECALL TO THE ALTERNATIVE FLOOR.
<br />3) ACTIVATION OF 2nd FLOOR AND ABOVE FLOORS ELEVATOR LOBBY OR
<br />ELEVATOR MACHINE ROOM SMOKE DETECTORS SHALL INITIATE ELEVATOR
<br />RECALL TO THE PRIMARY FLOOR,
<br />4) ACTIVATION OF ELEVATOR MACH RM HEAT DETECTOR SHALL INITIATE ELEV.
<br />RECALL TO PRIMARY FLOOR AND SHUT POWER TO THE ELEVATOR EQUIPMENT.
<br />D. SMOKE DUCT DETECTORS:
<br />1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP.
<br />3) ILLUMINATE THE SUPERVISORY LED.
<br />4) SHUT DOWN ITS RESPECTIVE AIR HANDLER UNIT.
<br />E. FLOW BELL:
<br />1) FLOW BELL SHALL SOUND UPON THE ACTIVATION OF FLOW SWITCH ONLY.
<br />2) FLOW BELL SHALL SOUND AS LONG AS THE WATER IS FLOWING.
<br />3) FLOW BELL SHALL NO BE CAPLABLE OF BEING SILENCED FROM THE FACP.
<br />F. ACTIVATION OF ANY SUPERVISORY CIRCUIT OR TAMPER SWITCH SHALL CAUSE THE
<br />FOLLOWING ACTIONS AND INDICATIONS:
<br />1) IDENTIFY THE INDIVIDUAL CIRCUIT OR DEVICE ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP.
<br />3) ILLUMINATE THE SUPERVISORY LED.
<br />G. RECEIPT OF A TROUBLE SIGNAL AT THE FACP SHALL CAUSE THE
<br />FOLLOWING ACTIONS AND INDICATIONS:
<br />1) IDENTIFY THE ORIGIN OF THE TROUBLE ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE TROUBLE SIGNAL AT THE FACP.
<br />3) ILLUMINATE THE TROUBLE LED.
<br />TYPICAL SPRINKLER CLOSET WITH FIRE ALARM PANEL
<br />INSTALLATION DIAGRAM.
<br />t 1 1 t
<br />• I
<br />--/7 2
<br />Ir
<br />FACP •
<br />FCPS
<br />EL I
<br />MAIN TAMPERS AND WATERFLOWS
<br />s
<br />Breaker Box
<br />CENTRAL STATION / TRANSMISSION OF SIGNALS / MONITORING
<br />- ALL SIGNALS (ALARM/ TROUBLE/SUPERVISORY) WILL BE TRANSMITTED TO THE
<br />CENTRAL STATION.
<br />- THE MEANS OF TRANSMISSION ARE PHONE LINES.
<br />- ALL SIGNALS WILL BE TRANSMITTED AS FOLLOWS:
<br />A POINT ADDRESSABLE SIGNAL WILL BE TRANSMITTED TO THE CENTRAL STATION,
<br />SYSTEMS POINTS WILL BE IDENTIFY AT THE CENTRAL STATION AS FOLLOW:
<br />DEVICE TYPE ( PULL STATION, SMOKE, ETC) + DEVICE LOCATION
<br />(FLOOR + GENERAL DESCRIPTION) + INDIVIDUAL BUILDING PHYSICAL ADDRESS
<br />OR BUILDING NUMBER.
<br />- THE FIRE ALARM DIALER IS AN OPTIONAL BOARD THAT MOUNTS INSIDE
<br />THE FIRE ALARM CABINET ON TOP OF THE FIRE ALARM MAIN BOARD.
<br />CODES & PLAN NOTES
<br />- ALL DRAWINGS ARE SCALED TO 1/8 = 1Ft UNLESS OTHERWISE NOTED.
<br />- COORDINATE WITH SPRINKLER CONTRACTOR EXACT LOCATION OF ALL
<br />TAMPER AND FLOW SWITCHES.
<br />- INSTALL SPLICE/CHECK BOX IN ALL 1 ST FLOOR APARTMENT'S
<br />BATHROOMS.
<br />- CONFIRM LOCATION OF POWER SUPPLIES IN BLDGS PRIOR TO ROUGH IN.
<br />- REFER TO FLOOR PLANS FOR LOCATION OF DUCT DETECTORS (SUPPLY OR
<br />RETURN SIDE), COORDINATE WITH MECHANICAL CONTRACTOR THE ACTUAL
<br />LOCATIONS OF THE AHUs.
<br />- ALL STROBES WILL BE SET @ 75cd UNLESS NOTED.
<br />- CEILING HEIGHT IS 10ft UNLESS NOTED.
<br />- UNDERGROUND WIRE USED AS SLC FOR COMMUNICATION BETWEEN BUILDINGS
<br />IS SUITABLE FOR WET LOCATIONS / DIRECT BURIAL.
<br />- ANY PROPOSED INTERCONNECTION OF PANELS WILL BE A "NON -LATCHING"
<br />CONFIGURATION PANEL RESET FROM 1 LOCATION.
<br />- FIRE ALARM SYSTEM PROVIDED IS FULLY ADDRESSABLE.
<br />- SMOKE DETECTORS FOR SMOKE COMPARTMENTS WILL BE PROVIDED
<br />AS PER NFPA-72 17.7.5.6.5.1 (A)
<br />- COORDINATE WITH MECHANICAL CONTRACTOR LOCATION OF SMOKE DAMPERS
<br />- SINGLE STATION 120 AC SMOKE DETECTOR PROVIDED BY ELECTRICAL CONTRACTOR
<br />ON SEPARATE PERMIT.
<br />- ELECTRICAL LOAD, PANEL, BREAKER LOCKOUT IS ON SEPARATE PERMIT
<br />PERMIT . FBC 107.2
<br />- INSTALLATION SHALL BE IN ACCORDANCE WITH FFPC 5TH ED.AND NFPA 72 2010 ED
<br />- 24/5 STANDBY TEST IS REQUIRED BEFORE FINAL FIRE, IF BUILDING IS OCCUPIED
<br />DURING THIS TEST, FIREWATCH WILL BE REQUIRED.
<br />- ALL SYSTEM WIRING SHALL COMPLY WITH NFPA-70 ARTICLE 760.
<br />- ALL AUDIBLE DEVICES LOCATED INSIDE SLEEPING AREAS MEET NFPA-72 (2013)
<br />18.4.5.3 FOR LOW FREQUENCY REQUIREMENTS
<br />" 24/5 STANDBY TEST REQUIRED IF ANY PART OF THE BLDG IS OCCUPIED
<br />BY TENANTS DURING THIS TEST. A FIRE WATCH IS REQUIRED FROM
<br />7AM-7PM. THIS PERSON WILL BE A TAMPA INSPECTOR.
<br />EXTERIOR MAIN TAMPERS, BACKFLOWS, ETC.
<br />INSTALLATION NOTES:
<br />0 120vac Line in 112" or 3/4" EMT conduit, PVc or Flex supplied by electrical contractor.
<br />Q 120vac surge protector, supplied by Fire Alarm contractor, Installed by Electrical Contractor on
<br />Electrical breaker Panel
<br />Splice Box, Installed and Supplied By Electrical Contractor.
<br />@FACP. Supplied and Installed by Fire Alarm Contractor.
<br />Q FCPS, Supplied and Installed by Fire Alarm Contractor.
<br />Q 14- EMT Conduit or Flex Supplied By Electrical Contractor.
<br />@PVC Box 6x6x4, Supplied and Installed by Electrical Contractor.
<br />0 3/4" PVC Conduit for Underground Connection Front/To other Fire Alarm Closets.
<br />Q WaterFlow Sensor.
<br />@ Water Tamper.
<br />Surge Protector, Supplied and Installed BY Fire Alarm Contractor.
<br />3/4" EMT Conduit or Flex Supplied By Electrical Contractor.
<br />@ 4 Square PVC Splice Box, Supplied and Installed by Fire Alarm Contractor.
<br />@ 1/2" or 3/4" PVC Conduit or Seal tight Flex Supplied By Electrical Contractor.
<br />® 3/4" PVC Conduit for Underground Connection To Outside Tampers.
<br />0 Single gang Box attached to Water Tamper, Supplied and Installed By El3ctrical Contractor. .
<br />Q 4 Square Box with Rised P-Ring For Smoke Detector, Supplied By Electrical
<br />Contractor.
<br />@Breaker Lock, Supplied By Electrical Contractor.
<br />ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING ALL THE
<br />NECESSARY HARDWARE (BOXES, CONNECTORS, CONDUITS, Etc.) AS WELL
<br />AS PARTIAL INSTALLATION AS PER INSTALLATION NOTES.
<br />ELEVATOR SEQUENCE OF OPERATION:
<br />1. ACTIVATION OF ANY OF THE FOLLOWING DEVICES SHALL INITIATE THE ELEVATOR RECALL
<br />FUNCTION FOR THE AFFECTED ELEVATOR(S),
<br />1.1 ELEVATOR LOBBY SMOKE DETECTOR.
<br />1.2 ELEVATOR MACHINE ROOM SMOKE DETECTOR.
<br />1.3 ELEVATOR HOISTWAY SMOKE DETECTOR.
<br />2. ACTIVATION OF ANY OF THE FOLLOWING DEVICES SHALL ACTIVATE (OPEN) THE SHUNT
<br />TRIP CIRCUIT BREAKER FOR THE AFFECTED ELEVATOR(S).
<br />2.1 ELEVATOR MACHINE ROOM HEAT DETECTOR.
<br />2.2 ELEVATOR HOISTWAY HEAT DETECTOR.
<br />3. ACTIVATION OF ANY OF THE FOLLOWING DEVICES SHALL INITIATE, FOR THE AFFECTED
<br />ELEVATOR(S), A SEPARATE AND DISTINCT SIGNAL THAT INDICATES THE ELEVATOR IS NO
<br />LONGER SAFE TO USE:
<br />3.1 ELEVATOR MACHINE ROOM SMOKE DETECTOR.
<br />3.2 ELEVATOR HOISTWAY SMOKE DETECTOR.
<br />4. THE FOLLOWING CONDITION SHALL INITIATE THE FIRE ALARM SUPERVISORY SIGNAL:
<br />4.1 ELEVATOR SHUNT TRIP CIRCUIT LOSS OF POWER.
<br />5. ELEVATOR RECALL FUNCTIONS SHALL BE PROVIDED AS REQUIRED BY NFPA-72 AND
<br />ANSI A17.1:
<br />5.1 ACTIVATION OF
<br />AN INITIATING DEVICE AT ANY FLOOR OTHER THAN THE
<br />DESIGNATED
<br />LEVEL SHALL CAUSE THE AFFECTED ELEVATOR(S) THAT SERVE THAT FLOOR
<br />TO BE
<br />RECALLED NON-STOP TO THE DESIGNATED LEVEL.
<br />5.2 ACTIVATION OF
<br />AN INITIATING DEVICE AT THE DESIGNATED LEVEL SHALL
<br />CAUSE
<br />THE AFFECTED ELEVATOR(S) THAT SERVE THAT FLOOR TO BE RECALLED TO
<br />AN
<br />ALTERNATE LEVEL.
<br />5.3 ACTIVATION OF
<br />AN INITIATING DEVICE IN THE MACHINE ROOM SHALL CAUSE
<br />THE VISUAL SIGNAL
<br />TO ILLUMINATE INTERMITTENTLY ONLY IN THE ELEVATOR
<br />CARD(S)
<br />WITH EQUIPMENT IN
<br />THAT MACHINE ROOM.
<br />5.4 ACTIVATION OF
<br />AN INITIATING DEVICE IN THE HOISTWAY SHALL CAUSE
<br />THE VISUAL SIGNAL
<br />TO ILLUMINATE INTERMITTENTLY ONLY IN THE ELEVATOR
<br />CARD(S)
<br />WITH EQUIPMENT IN
<br />THAT HOISTWAY.
<br />6. ELEVATOR SHUTDOWN FUNCTIONS SHALL BE PROVIDED AS REQUIRED BY NFPA-72 AND
<br />ANSI A17.1:
<br />6.1 ACTIVATION OF A HEAT DETECTOR IN THE MACHINE ROOM SHALL DISCONNECT
<br />THE MAIN LINE POWER TO THE AFFECTED ELEVATOR(S).
<br />6.2 ACTIVATION OF A HEAT DETECTOR IN A HOISTWAY SHALL DISCONNECT
<br />THE MAIN LINE POWER TO THE AFFECTED ELEVATOR(S).
<br />is
<br />R
<br />E
<br />5
<br />T
<br />O
<br />P
<br />S
<br />Y
<br />5
<br />T
<br />E
<br />M
<br />THROU614-PENETRATION DETAIL
<br />5Y5TEM No. F-A-1015
<br />F"Ini _1 up
<br />I. FLOOR ASSEMBLY - THE FIRE -RATED UNPROTECTED CONCRETE AND STEEL FLOOR
<br />ASSEMBLY SHALL 13E CONSTRUCTED OF THE MATERIALS AND IN THE MANNER
<br />SPECIFIED IN THE INDIVIDUAL D400 SERIES DE5ISNS IN THE U.L. FIRE RESISTANCE
<br />DIRECTORY AND AS SUMMARIZED BELOK
<br />A. CONCRETE - MIN 2 IN THICK REINFORCED Ll&rr C7HT OR NORMAL WEIGHT
<br />000-150 PCF) CONCRETE.
<br />B. STEEL FLOOR AND FORM UMTS• - COMPOSITE OR NON -COMPOSITE MAX
<br />3 IN. DEEP SALV FLUTED UNITS A5 SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING
<br />DESION. MAX DIAM OF OPENNe 15 6 IN.
<br />2. THROUGH PENETRANTS - ONE METALLIC, PIPE, CONDWT OR TUBING INSTALLED
<br />EITHER CONCENTRICALLY OR E=31TRICALLY WITHIN THE FIRESTOP SYSTEM.
<br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THHROUeH
<br />OPENING SHALL BE MIN O IN. (POINT CONTACTS) TO MAX 1-1/6 IN. PIPE, CONDUIT OR
<br />TUBING TO BE RIODLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY.
<br />THE FOLLOMW TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY
<br />BE USED+
<br />A. STEEL PIPE
<br />S. IRON PIPE
<br />G. C.ONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELEGTRIGAL METALLIC,
<br />TUBING OR STEEL CONDUIT.
<br />D. COPPER TIEING
<br />E. COPPER PIPE
<br />3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING+
<br />PAGKINe MATERIAL - MIN I-V2' IN. THIGKlE55 OF MIN 4 PCF DENSITY MINERAL
<br />WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM.
<br />PACKING MATERIAL TO 13E RCC.ESSED FROM TOP SURFACE OF FLOOR AS
<br />REWRED TO ACC.OMODATE THE REQWRED THICKNESS OF FILL MATERIAL t1TEM 3B).
<br />FILL, VOID OR CAVITY MATERIAL0 - SEALANT - MIN 1/2 IN. THICKNESS OF FILL
<br />MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR. AT
<br />POINT CONTACT LOCATION BETWEEN PENETRANT AND CONCRETE, A MIN 1/2 IN.
<br />DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE 0ONCRETEIPENETRANT
<br />INTERFACE ON TOP SURFACE OF FLOOR.
<br />FIRESTOP SYSTEM INC. - 000 DW I
<br />« BEARING THE UL CLA551FICATION MARKING
<br />THROUC H-PENETRATION DETAIL
<br />5Y5TEM No. W-J-1048
<br />I
<br />F RATINGS - 2 HR
<br />E
<br />A
<br />C.J
<br />� . yr
<br />�••�,'JtM
<br />T
<br />O
<br />P
<br />2 �..
<br />A
<br />S
<br />r
<br />Y
<br />SECTION A -A
<br />S
<br />T
<br />1. WALL ASSEMBLY - MIN 6-1/6 IN. THICK NORMAL WEIGHT OR LleHTMiSHT
<br />E
<br />000-15OPC -) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY Ul..
<br />CLASSIFIED CONCRETE BLOCKS". MAX DIAM OF OPENING 15 14-1/8 IN.
<br />M
<br />SEE CONCRETE BLOCKS (CAZT) GAT5SORY IN THE FIRE RESISTANCE DIRECTORY
<br />FOR NAME OF MANUFACTURERS.
<br />2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED
<br />EITHER GONCOMOALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM.
<br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF
<br />OPENING SHALL BE MIN 3/6 IN. TO MAX I IN. PIPE, CONDUIT OR TUBING TO BE
<br />R161DLY SUPPORTED ON BOTH 510E5 OF WALL ASSEMBLY. THE FOLLOWING
<br />TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY 13E USED.
<br />A. STEEL PIPE
<br />S. IRON PIPE
<br />G. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLEW STEEL ELECTRICAL METALLIC,
<br />TUBING (EMT) OR STEEL CONDUIT. WHEN EMT OR STEEL CONDUIT 15 USED
<br />T RATING 15 1/4 HP.
<br />D. COPPER TUBING
<br />E. COPPER PIPE
<br />3. FILL, VOID OR CAVITY MATERIALS - SEALANT - MIN 1-1/4 IN. THICKNESS
<br />OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES
<br />OF WALL.
<br />FIRESTOP SYSTEMS, INC. - PLOWBUARD eOLD FIRESTOP SEALANT
<br />• BEARING THE UL CLAS5IFIGATION MARKING.
<br />"CADDY" T-GRID BOX HANGER
<br />SUPPORT, OR EQUAL. "CADDY'-'
<br />REFERENCE NO. CEC 30-302(3).
<br />sec
<br />a
<br />ELECTRICAL MOUNTING BOX
<br />FOR THE CEILING MOUNTED
<br />NOTIFICATION DEVICES.
<br />ACOUSTICAL TILE CEILING
<br />GRID SUPPORT FRAMING.
<br />CEILING GRID ELECTRICAL BACK -BOX ATTACHMENT
<br />NTS
<br />AU At`tIICABL1 !1111111.1t00Q1
<br />&UWFIUCA "Pi,I 400 AM
<br />t42Ck& CAL CUM,
<br />REVIEW DA17
<br />C►TYOFZEPHY
<br />®UII,DING OFFICIAL
<br />II•
<br />Kiperal�Rri rd vu iYTfr
<br />Fire Alarm & Communications
<br />■
<br />SUPERIOR FIRE ALARM &
<br />COMMUNICATIONS
<br />6201 JOHNS RD
<br />SUITE 9
<br />TAMPA, FL 33634
<br />813- 818- 4444
<br />CERTIFIED ALARM SYSTEM
<br />CONTRACTOR 1
<br />LICENSE EF 20001162
<br />■
<br />CAD DATE: 05/18/2016
<br />E
<br />Ruo4y,,Puga
<br />EF A 20'001162
<br />SHEET:
<br />NOTES
<br />i,
<br />�:.
<br />PM
<br />
|