ELECTRICAL SYMBOLS LEGEND <br />(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS) GENERAL NOTES <br />SYMBOL DESCRIPTION <br />LIGHT FIXTURE 1. FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND LABOR, FOR A 14. SEISMIC ZONE REQUIREMENTS: PROVIDE EXPANSION COUPLINGS AND <br />KD/ O (WALL MOUNTED/CEILING MOUNTED) COMPLETE INSTALLATION IN ALL RESPECTS, READY FOR INTENDED USE BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY LOCAL <br />AND IN STRICT ACCORDANCE WITH NEC, NESC, STATE, AND LOCAL CODES. <br />O LIGHT FIXTURE CODES, AND MANUFACTURER'S RECOMMENDATIONS. PAY ALL <br />NECESSARY FEES AND PERMITS. 15. EXISTING ELECTRICAL AND ALARM: <br />LIGHT FIXTURE, <br />EMERGENCY LIGHT A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS THE A. WHERE DEMOLITION OR NEW CONSTRUCTION INTERRUPTS <br />LIGHT FIXTURE, ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR WALLS. EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING EQUIPMENT, <br />NIGHT LIGHT DEVICES, OR LIGHTING TO REMAIN, BUT NOT SHOWN ON DRAWINGS, <br />B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE. PROVIDE LABOR AND MATERIALS TO REWORK CIRCUITRY, AS <br />0 ENCLOSED COOLER/FREEZER LIGHT REQUIRED, TO MAINTAIN EXISTING OPERATION. <br />C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE <br />OPERATIONS. COORDINATE ALL DISRUPTIONS WITH WALMART B. IF DEMOLITION OR NEW CONSTRUCTION WILL DISRUPT EXISTING <br />TRACK LIGHTING CONSTRUCTION MANAGER AND STORE MANAGER. UNDERGROUND SERVICES (ELECTRICAL, TELEPHONE, PARKING LOT <br />LIGHTING CIRCUITRY, ETC.) PROVIDE ALL MATERIALS AND LABOR AS <br />I / ® EXIT FIXTURE D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESS REQUIRED TO REROUTE, SLEEVE, OR OTHERWISE REWORK THESE <br />(WALL MOUNTED/CEILING BEFORE INSTALLING BOXES. FURNISH AND INSTALL EXTENDED SERVICES TO MAINTAIN THEIR EXISTING OPERATION. <br />MOUNTED) BOXES OR BOX EXTENDERS WHERE REQUIRED. <br />EMERGENCY FIXTURE C. EXERCISE CAUTION AROUND ALARM AND SECURITY CABLES <br />E. CONTRACTOR SHALL VERIFY THAT ALL AFFECTED PANELBOARDS DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM AND <br />SWITCH, SINGLE POLE HAVE CIRCUIT BREAKER KNOCKOUTS PROPERLY COVERED AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO THAT SYSTEMS <br />THAT ALL TRIM IS IN GOOD CONDITION, ALLOWING NO ACCESS TO REMAIN OPERATIONAL AT ALL TIMES. <br />LIVE PARTS. <br />$3 SWITCH, 3-WAY D. DISPOSE OF ALL REMOVED MATERIALS, UNLESS OTHERWISE <br />2. PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS: NOTED. <br />�OS SWITCH, OCCUPANCY SENSOR A. FIRE RATED WALLS: SEAL PER SPECIFICATIONS FOR FIRE STOPPING. 16. EXISTING ELECTRICAL DEMOLITION: <br />#OS SWITCH, BI-LEVEL OCCUPANCY SENSOR B. NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL. A. GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL <br />EQUIPMENT CONDUIT, AND CONDUCTORS AS INDICATED ON THE <br />/ R❑ Ds) CEILING OCCUPANCY SENSOR AND ASSOCIATED RELAY <br />C. FREEZER/COOLER BOXES: SEAL WITH EXPANDING FOAM SEALANT. DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION. REMOVE ALL <br />PANELBOARDS, DISCONNECT SWITCHES, BOXES, RELAYS, TIME <br />D. EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR SEALING SWITCHES, LIGHTS, DEVICES, ETC., WHICH WILL NOT BE REUSED. <br />RECEPTACLE, DUPLEX REQUIREMENTS AT ALL EXTERIOR MOUNTED DEVICES, FIXTURES, <br />ENCLOSURES, AND RACEWAY PENETRATIONS. B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT, <br />RECEPTACLE, DUPLEX, 3. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR (SIZE CONDUCTORS AND RELATED DEVICES SERVING SALES AREA <br />MOUNTED HORIZONTALLY PER NEC) IN PVC TYPE CONDUIT, POWER CIRCUITS, ISOLATED GROUND GONDOLAS BEING RELOCATED OR REMOVED. EXISTING CONDUIT <br />CIRCUITS, OR AS SHOWN ON PLANS. CONDUIT SHALL BE SIZED PER AND CONDUCTORS MAY BE REUSED FOR NEW POWER DROPS <br />RECEPTACLE, DOUBLE DUPLEX NEC BASED ON THWN 600 VOLT COPPER SINGLE CONDUCTORS, PLUS WHERE SIZE, RATING, AND CONDITION MEET REQUIREMENTS <br />THE EQUIPMENT GROUNDING CONDUCTOR. INDICATED ON PLANS AND ALL U.L. RATINGS. REMOVE ALL UNUSED <br />1'f RECEPTACLE, DUPLEX ISOLATED GROUND CONDUIT AND CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER <br />4. WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM FINISHED FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS "SPARE". <br />RECEPTACLE, DOUBLE DUPLEX, FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED OTHERWISE ON PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT BREAKER IN <br />ISOLATED GROUND PLANS. COORDINATE THE STANDARD MOUNTING HEIGHTS WITH THE "OFF" POSITION. <br />RECEPTACLE, SIMPLEX TWIST MASONRY: <br />LOCK, L5-15R, UNO A. SWITCHES +42" C. CONDUIT AND WIRING TO BE ABANDONED IN CEILING SPACES AND <br />B. RECEPTACLES +20" OTHER NON-PUBLIC AREAS (I.E., THROUGH STOCKROOM AREA) - <br />RECEPTACLE, SIMPLEX TWIST C. VOICE/DATA +20" CUT WIRING LOOSE AND REMOVE FROM RACEWAY(S), LEAVING <br />LOCK, ISOLATED GROUND, L5-15R, UNO RACEWAY(S) IN PLACE. CONDUIT TO BE ABANDONED IN WALLS OR <br />RECEPTACLE, DUPLEX TWIST 5. WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT IN FLOORS SHALL BE REMOVED BACK TO FINISHED SURFACE AND <br />LOCK, L5-15R, UNO CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING DIAGRAMS. CAPPED INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT. <br />RECEPTACLE, DUPLEX TWIST 6. CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE D. ALL CIRCUIT BREAKERS SERVING BRANCH CIRCUITS TO BE <br />LOCK, ISOLATED GROUND, L5-15R, UNO PANELBOARD IDENTIFICATION SCHEDULES FOR PANELBOARDS ABANDONED OR REMOVED SHALL REMAIN IN RESPECTIVE <br />AFFECTED BY REMODEL. PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE ON <br />RECEPTACLE, SPECIAL DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT <br />7. NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN EXISTING BREAKER IN THE "OFF" POSITION. <br />RECEPTACLE, SIMPLEX PANELBOARDS OR DISTRIBUTION BOARDS SHALL MATCH THE TYPE <br />AND AIC RATING OF EXISTING OVERCURRENT PROTECTIVE DEVICES. E. DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO <br />SELECTIVE SITE DEMOLITION SPECIFICATION FOR DISPOSAL OF <br />RECEPTACLE, PLUG -MOLD 8. BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG UNLESS LIGHT FIXTURE. <br />NOTED OTHERWISE IN SCHEDULES. WHERE 20A BRANCH CIRCUITS <br />O JUNCTION BOX HAVE #8 AND LARGER WIRE SPECIFIED, #10 AWG WIRE SHALL BE USED F. BUILDING COMPONENTS ABANDONED BY THE SCOPE OF WORK <br />(WALL MOUNTED/CEILING FOR THE FINAL CONNECTION (15-FT MAXIMUM). SHALL BE SECURED TO PREVENT FALLING, LOOSENING, OR <br />ennl inlTr7n� CREATING DAMAGE OF ANY KIND IN THE FUTURE. <br />JUNCTION BOX, ALARM SYSTEM 9. WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND DERATE <br />® (WALL MOUNTED/CEILING CURRENT CARRYING CONDUCTORS PER NEC. 17.. ETHERNET CABLE: <br />MOUNTED), ALARM JUNCTION BOX <br />O FOR REMOTE TEST/RESET 10. PROVIDE UL LISTED HANDLE TIES ON ALL MULTIWIRE BRANCH A. FURNISH AND INSTALL JUNCTION BOXES AS SHOWN ON PLANS. <br />(WALL MOUNTED/CEILING MOUNTED) CIRCUITS PER NEC REQUIREMENTS. PROVIDE CONDUIT AS REQUIRED BY LOCAL CODES AND/OR <br />ORDINANCES. <br />EQUIPMENT CONNECTION POINT 11. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE SHALL <br />(PROVIDED WITH EQUIPMENT) BE MADE TO BRIDGING OR JOIST WEB MEMBERS. UTILIZE ONLY THE B: ETHERNET CABLE IS FURNISHED BY OTHERS. <br />TOP AND BOTTOM CHORDS FOR SUPPORTING THE ELECTRICAL <br />01 NON -FUSED SYSTEM INSTALLATIONS. C. ELECTRICAL CONTRACTOR SHALL INSTALL CABLE IN POWER POLES. <br />DISCONNECT <br />12. DEVICES SHOWN ON COOLER/FREEZER PANELS SHALL BE SURFACE D. ELECTRICAL CONTRACTOR SHALL INSTALL OTHER CABLE AS <br />01 FUSED DISCONNECT MOUNTED UNLESS NOTED OTHERWISE. REFER TO ARCHITECTURAL DIRECTED BY WALMART CONSTRUCTION MANAGER. <br />swlTcrEF)/ CIRCUIT, CONCEALED IN WALLS DOCUMENTS FOR CONDUIT INSTALLATION AND SEALING <br />rk�,vELER.s NEuJTRAL OR CEILING, E INDICATES REQUIREMENTS. <br />Ho ' <br />EXISTING WIRING <br />L,ROUN13. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM AND <br />CIRCUIT, CONCEALED IN FLOOR BRANCH CIRCUITS NOTED BY LEGEND SHALL BE INSTALLED UNDER <br />SLAB, E INDICATES EXISTING WIRING SLAB. ALL OTHER FEEDER AND BRANCH CIRCUITS SHALL BE <br />CIRCUIT, EXPOSED, E INSTALLED OVERHEAD. PROVIDE EXTERIOR COATED GRC BENDS ON <br />INDICATES EXISTING ALL CONDUIT RUNS THAT HAVE 45 DEGREE BENDS OR GREATER. REF <br />WIRING SPECIFICATIONS. <br />FLUSH MOUNTED PANELBOARD <br />— SURFACE MOUNTED PANELBOARD <br />VOICE/DATA, <br />-/ -d/-V d = DATA ONLY, v = VOICE ONLY <br />- LOW VOLTAGE CABLE BOX FOR OTHER <br />m VOICE/DATA, FLUSH FLOOR 4 <br />MOTOR <br />❑ TELEPOWER POLE ' I <br />E g'-4" T-3" T-3' <br />PUSH BUTTON 401) <br />(TYP - <br />BUZZER . B \ C° <br />J J o <br />SO SMOKE DETECTOR TYP 4 <br />E1 EDC3 <br />S-X ENERGY MANAGEMENT 16.477 #8 <br />TEMPERATURE SENSOR (20A-1P) <br />O THERMOSTAT PART 1/2 <br />©S TEMPERATURE SENSOR AP GATES—G R <br />TC TIME CLOCK 3 1/8" = 1'-0" <br />ABBREVIATIONS <br />a, b, c LOWER CASE LETTERS iG ISOLATED GROUND <br />INDICATE SWITCHING IRC INTER -REGISTER <br />AFC ABOVE FINISH COUNTER COMMUNICATION <br />AFF ABOVE FINISH FLOOR ISP IN-STORE PROCESSOR <br />AFG ABOVE FINISH GRADE LCU LIGHTING CONTROL UNIT <br />C CONDUIT K KEY OPERATED <br />CCT CIRCUIT N NEUTRAL <br />CF CEILING/CIRCULATION FAN NTS NOT TO SCALE <br />D DATA P WITH PILOT LIGHT <br />EC ELECTRICAL CONTRACTOR RH RADIANT HEATER <br />EF EXHAUST FAN RC REFRIGERATION <br />EP EXPLOSION CONTRACTOR <br />ETR EXISTING TO REMAIN SC SECURITY CAMERA <br />EWC ELECTRIC WATER SF SUPPLY FAN <br />FLIT FUTURE: TR TAMPER <br />GR GROUND TYP RESISTANT <br />GFEP GROUND FAULT EQUIPMENT WH WATER HEATER <br />PROTECTION WP WEATHERPROOF <br />GFI GROUND FAULT CIRCUIT WR WEATHER RESISTANT <br />i <br />INTERRUPTER UH UNIT HEATER 4 <br />GF GABLE FAN LINO UNLESS NOTED <br />HD HAND DRYER OTHERWISE E1 <br />I <br />T -1" 2'-2 " 5'-0 TYP <br />B — N <br />� J <br />o J J J <br />16.200 <br />(TYP) <br />EDC3 <br />16.47 #8 <br />(20A-1 P) <br />PART 2/2 <br />yl <br />P GATES-G M <br />28"= V-011 <br />J <br />W <br />tl) <br />S <br />T <br />t <br />GQ <br />d <br />N <br />st <br />N <br />to <br />O <br />co <br />a <br />to N N <br />M Z <br />� 3 <br />O 0 <br />0 <br />rn a <br />O N <br />N � <br />N Q, <br />N U <br />00 i <br />INSTALL FURNISHED POWER POLE. MOUNT JUNCTION BOX(ES) TO TOP SIDE OF <br />BOTTOM CHORD OF BAR JOIST. PROVIDE 3/8" FLEXIBLE METAL WHIPS FROM <br />JUNCTION BOX AND CONNECT AT TOP OF POWER POLE. CABLE WHIPS TO POWER <br />POLE SHALL BE INSTALLED IN A NEAT AND WORKMAN -LIKE MANNER. ROUTE <br />WHIPS TO TERMINATIONS ALONG UNISTRUT OR STRUCTURE AND SUPPORT <br />EVERY 12" TO 24" ALONG ENTIRE EXPOSED LENGTH. EXCESS CABLE SHALL BE <br />KEPT TO A MINIMUM AND TIGHTLY COILED AND ATTACHED TO UNISTRUT OR JOIST. <br />NO CONNECTION OF ANY KIND SHALL BE MADE TO JOIST <br />WEB MEMBERS, JOIST BRIDGING, OR ROOF DECK. MAINTAIN <br />MINIMUM 6" CLEARANCE FROM TOP OF POWER POLE TO <br />ROOF DECK. JUNCTION BOXES AND RACEWAYS SHALL NOT <br />BE MOUNTED WITHIN 1-1/2" OF DECK. <br />POLES ARE ABLE TO BE FIELD CUT FOR AREAS THAT HAVE <br />LOWER STRUCTURE OR CEILINGS. FOLLOW MANUFACTURER <br />INSTRUCTIONS FOR CUTTING. WHEN PENETRATING GYP <br />BOARD CEILINGS OR SOFFITS COORDINATE LOCATION AND <br />QUANTITY OF ACCESS PANELS TO MAINTAIN ACCESS PER NEC <br />REQUIREMENTS WITH ARCHITECT. SECURE TOP OF POLE PER <br />MANUFACTURER INSTRUCTIONS. <br />EXTEND POWER PROVIDE PVC SLEEVE LENGTH 12" <br />POLE 12" MIN. MIN. TO 36" MAX. TO ACCOMMODATE <br />WITHIN PVC SLEEVE VARIATIONS IN STRUCTURE HEIGHT. <br />PROVIDE 2-1/2" <br />UNISTRUT INSTALL CEILING FLANGE <br />STRAP TO FURNISHED WITH POLE WHEREVER <br />FIRMLY CLAMP POLE PASSES THROUGH CEILING <br />TO CONDUIT <br />INSTALL TWO-PIECE, SELF-ADHESIVE <br />FLANGE FURNISHED WITH POLE <br />WHEREVER POLE PASSES THROUGH <br />EXTENDER ARM / MILLWORK, EXCEPT AT CHECKOUTS <br />POWER POLE <br />UNISTRUT <br />2-1/2" PVC MILLWORK <br />CONDUIT <br />I I <br />III <br />SPACER <br />INCLUDED <br />POWER POLE WITH FOOT III <br />L�J <br />PROVIDE 1-1/4" FENDER <br />1/4" TAPCON+ FINISHED WASHER, LOCK WASHER <br />AT 2-3/4" FLOOR AND NUT, TYP <br />EMBEDMENT, POWER POLE FOOT <br />TYP (FOR FREESTANDING <br />POLES) <br />WHEN INSTALLING ENTERTAINMENT TABLE (ENT) POWER <br />POLE, A SEPARATE SPACER IS PROVIDED TO BE INSTALLED <br />IN SPACE BETWEEN SIDE OF MILLWORK AND POLE. <br />ENSURE PROPER POLE ORIENTATION TO ALLOW POLE AND <br />BRACKET TO BE MOUNTED FLUSH WITH THE TABLE. <br />POWER POLE CONNECTION <br />NTS <br />J <br />on <br />07/26/19 <br />PROVIDE UNISTRUT PER <br />SPECIFICATIONS. LENGTH AS <br />REQUIRED TO SPAN JOISTS. SECURE <br />TO BOTTOM CHORD OF BAR JOIST. <br />PROVIDE 1/4" BOLT AND <br />1-1/4" FENDER WASHER, TYP <br />PROVIDE UNISTRUT <br />P1026 ANGLE FITTING <br />OR EQUAL <br />BOTTOM <br />CHORD OF BAR <br />JOIST <br />WHERE POWER POLE FOOT IS TO BE INSTALLED ON TILE, RUBBER <br />FLOORING, OR CARPET, REMOVE PORTION OF THE FLOORING TO ALLOW <br />FOOT TO BE SECURED DIRECTLY TO THE FLOOR SLAB. REFER TO SPEC <br />SECTION 05090. DO NOT INSTALL DIRECTLY ON TOP OF TRANSITION STRIPS. <br />SECURING THE FOOT DIRECTLY ON TOP OF VCT FLOORING IS ACCEPTABLE. <br />1 2 3 4 56 7 8 9 <br />0 <br />10 11 12 13 14 15 <br />E <br />dill 1 1 <br />a <br />�J o <br />I I I I I I <br />— _ 1 — 1 — <br />1 <br />' ELECTRICAL ROOM #3 <br />o o c. <br />a HI!l0 e 0 <br />�o <br />aNTEY PLAN <br />S <br />GENERAL POWER NOTES <br />1. PROVIDE LIQUID -TIGHT FLEXIBLE METAL CONDUIT <br />AND WIRING FROM DISCONNECT SWITCH OR <br />JUNCTION BOX TO EQUIPMENT KNOCKOUT OR <br />ELECTRICAL CONNECTION POINT. <br />2. WHERE EQUIPMENT NAMEPLATE PROTECTIVE DEVICE <br />RATING DIFFERS FROM SIZE PROVIDED, CHANGE OUT <br />BRANCH CIRCUIT WIRING AND OVERCURRENT DEVICE <br />TO APPROPRIATE RATING PER NEC. <br />3. UPON COMPLETION OF ELECTRICAL INSTALLATION <br />AND PRIOR TO ENERGIZING CIRCUIT: <br />A. INSPECT WIRE AND CABLE FOR PHYSICAL <br />DAMAGE. <br />B. PERFORM CONTINUITY TEST. <br />C. VERIFY PROPER PHASING CONNECTION TO ALL <br />THREE PHASE MOTOR LOADS. <br />POWER INTERRUPTION NOTE <br />11.30.18 <br />COORDINATE ALL WORK THAT REQUIRES POWER <br />INTERRUPTIONS TO THE STORE WITH THE STORE <br />MANAGER AND THE WALMART CONSTRUCTION MANAGER <br />A MINIMUM OF 48 HOURS IN ADVANCE OF ALL STORE <br />POWER INTERRUPTIONS. IN ADDITION, IF THE MAIN <br />ELECTRICAL SWITCHGEAR REQUIRES WORK AND DOES <br />NOT HAVE A MAIN SERVICE DISCONNECTING MEANS, <br />COORDINATE WITH THE UTILITY COMPANY A MINIMUM OF <br />TWO WEEKS IN ADVANCE OF THE STORE POWER <br />INTERRUPTION. IF STORE IS NOT OPEN 24 HOURS PER <br />DAY, ALL STORE POWER INTERRUPTIONS ARE TO BE <br />ACCOMPLISHED AFTER NORMAL STORE BUSINESS <br />HOURS. PROVIDE TEMPORARY POWER AS REQUIRED <br />PER SPECIFICATIONS. INSTALLATION OF NEW EQUIPMENT <br />SHALL BE COMPLETED AND THE POWER SYSTEM TESTED <br />AND RE -ENERGIZED PRIOR TO THE TIME ESTABLISHED BY <br />THE STORE MANAGER AND THE WALMART <br />CONSTRUCTION MANAGER. <br />20A WIRE SIZING SCHEDULE <br />ALL WIRE SIZES SHOWN ON PANEL SCHEDULES <br />ARE INTENDED TO BE MINIMUM ACCEPTABLE WIRE <br />SIZE. <br />THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE <br />WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT). <br />LENGHTS (IN FEET) ARE INTENDED TO BE MAXIMUM <br />120 VOLT <br />#12 <br />#10 <br />#8 <br />1-5 AMPS <br />200 FT. <br />325 FT. <br />490 FT. <br />7 <br />6-10 AMPS <br />100 FT. <br />160 FT. <br />245 FT. <br />3 <br />qFT. <br />11-15 AM PS <br />70 FT. <br />110 FT. <br />165 FT. <br />2 <br />277 VOLT <br />#12 <br />#10 <br />#8 <br />#6 <br />1-5 AMPS <br />480 FT. <br />760 FT. <br />1170 FT. <br />1865 FT. <br />6-10 AMPS <br />240 FT. <br />380 FT. <br />585 FT. <br />930 FT. <br />11-15 AMPS <br />160 FT. <br />250 FT. <br />390 FT. <br />620 FT. <br />KEYNOTES <br />16.200 INSTALL OWNER FURNISHED BLANK POWER <br />POLE SUCH THAT GATE OPERATION IS NOT <br />OBSTRUCTED. ORIENT POLE SUCH THAT MOUSE <br />HOLE IS FACING GATE POST. ROUTE FLEXIBLE <br />METALLIC CONDUIT THROUGH POWER POLE AND <br />PROVIDE DIRECT CONNECTION TO GATE <br />POST(S). DO NOT ROUTE METALLIC CONDUIT ON <br />FLOOR. INSTALL 2 PIN AND 6 PIN CROSSLINK <br />CABLES FOR EACH GATE PAIR TO ENSURE <br />SIMULTANEOUS OPERATION. UTILIZE CABLE <br />DUCT AND POWER POLES TO ROUTE CROSSLINK <br />CABLES. <br />16.477 FURNISH AND INSTALL NEW CIRCUIT BREAKER <br />(##A-#P) IN EXISTING PANELBOARD INDICATED. <br />PROVIDE CIRCUIT BREAKER LOCKING DEVICE <br />(LOCK -OFF FOR MAINTENANCE). E.C. SHALL <br />MATCH MANUFACTURER, TYPE AND AIC RATINGS <br />OF EXISTING CIRCUIT BREAKERS. <br />EXISTING CONDITIONS WERE TAKEN FROM <br />EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING <br />ORIGINAL DRAWINGS AND MAY NOT REFLECT <br />A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND <br />EXACT "AS -BUILT" CONDITIONS. CONTRACTOR <br />SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE <br />SHALL FIELD VERIFY ALL EXISTING CONDITIONS <br />TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES <br />PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR <br />NOT RELIEVE THE RESPONSIBILITY OF PERFORMING <br />SHALL CAREFULLY COORDINATE NEW WORK AND <br />THE WORK PROPERLY. NO ADDITIONAL <br />DEMOLITION WITH ALL OTHER DISCIPLINES AND <br />COMPENSATION SHALL BE ALLOWED BECAUSE OF <br />EXISTING CONDITIONS. <br />CONDITIONS THAT OCCUR DUE TO FAILURE TO <br />FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. <br />Qw <br />U) <br />OLL�s¢ OW�Fw0Z <br />w <br />1-�ZO~LL= <br />�'�~00< >w0~Q <br />2LFLL�U'ZW~ZZW <br />vooa <br />WQ�N zO�FwjVaO�ZWo <br />O <br />a F�a W~Q <br />0�0 <br />ms <br />�z O <br />0 w WW OQnzwIs <br />F- <br />Z-mop LL Z ,< <br />1 <br />�UO pZw{wjw}W0w <br />waZWOwc~>awzv~ <br />001 <br />n <br />w=wwwwz-w0 <br />D¢ZLLW a0005200 <br />(n <br />NO0oo�aaawoam <br />H <br />z <br />F_ <br />U) <br />z <br />O <br />U <br />w <br />Q <br />%0 <br />C� <br />a <br />Q <br />% <br />LL <br />(0 <br />O <br />^ <br />N <br />O <br />o <br />c- <br />i <br />S� <br />0 <br />z <br />CD <br />LLJ� <br />rn_ <br />N <br />0 <br />0 <br />co <br />N <br />a! <br />w <br />m <br />z <br />m <br />O <br />ISSUE BLOCK <br />CHECKED BY: <br />JPM <br />DRAWN BY: <br />KM <br />PROTO CYCLE: <br />AP ATE <br />DOCUMENT DATE: <br />09/02/19 <br />♦♦��� QFtADEp� 41, <br />No 76917 <br />i <br />S F 01 <br />:�U <br />i�T•. QP '�♦♦ <br />ONA <br />r,111I111 1% <br />09/02/19 <br />POWER <br />PLANS <br />SHEET: <br />El <br />