ELECTRICAL SYMBOLS <br />LEGEND <br />10-m.10 ESM <br />(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS) <br />SYMBOL <br />DESCRIPTION <br />/ O <br />FLUORESCENT / LED OR HID FDCTURE <br />(WALL MOUNTED/CEILING MOUNTED) <br />10 <br />FLUORESCENT/ LED FIXTURE <br />® <br />FLUORESCENT I LED FIXTURE, <br />NIGHT LIGHT <br />® <br />VOLUMETRIC LED FIXTURE <br />O <br />ENCLOSED FREEZER LIGHT <br />NZ <br />Aa <br />TRACK LIGHTING <br />/ ® <br />EXIT FIXTURE <br />(WALL MOUNTED) <br />EMERGENCY LIGHT <br />(KA-L MMOLNTED) <br />SINGLE POLE SWITCH <br />$3 <br />3-WAY SWITCH <br />$4 <br />4-WAY SWITCH <br />$K <br />KEYED SWITCH <br />4D <br />DIMMERSWITCH <br />*VS <br />VARIABLE SPED SWITCH <br />4m <br />MANUAL MOTOR SWITCH <br />SINGLE POLE OCCUPANCY <br />SENSOR SWITCH <br />DOUBLE POLE OCCUPANCY <br />SENSOR SWITCH <br />l <br />CEILING MOUNTED OCCUPANCY <br />RECEPTACLE, DUPLEX <br />RECEPTACLE, DUPLEX, <br />MOUNTED HORIZONTALLY <br />RECEPTACLE, GFI <br />® <br />RECEPTACLE, DUPLEX FLUSH FLOOR <br />® <br />RECEPTACLE, DUPLEX. ISOLATED <br />GROUND FLUSH FLOOR <br />RECEPTACLE, DOUBLE DUPLEX <br />x <br />V <br />RECEPTACLE, DUPLEX <br />ISOLATED GROUND <br />RECEPTACLE, DOUBLE DUPLEX, <br />ISOLATED GROUND <br />RECEPTACLE, SIMPLEX TWIST LOCI, <br />L5-15R, UNO <br />RECEPTACLE, SIMPLEX TWIST LOCK, <br />ISOLATED GROUND, 1-5-1511, UNO <br />RECEPTACLE, DUPLEX TWIST LOCK, <br />1-5-15R, UNO <br />RECEPTACLE, DUPLEX TWIST LOCK, <br />ISOLATED GROUND, L5-15R, LINO <br />RECEPTACLE, SPECIAL <br />d) <br />RECEPTACLE, SIMPLEX <br />�111 <br />RECEPTACLE, PLUG -MOLD <br />O <br />JUNCTION BOX <br />(WALL- MOUNTED) <br />O <br />I RMOSTAT <br />(WALL MOUNTED/CEILING MOUNTED) <br />�! <br />ALARM JUNCTION BOX, <br />(WALL MOUMEDICERM MOUNTED) <br />ALARM JUNCTION BOX, <br />® <br />FOR REMOTE TEST/RESET <br />(WALL MOUNTEDICEILING MOUNTED) <br />0 <br />EQUIPMENT CONNECTION POINT <br />(PROVIDED WITH EQUIPMENT) <br />NOWFUSED DISCONNECT <br />Ell <br />FUSED DISCONNECT <br />CIRCUIT, CONCEALED N WNL.LS OR <br />CEILING, E INDICATES EXISTING <br />WIRING <br />CIRCUIT, CONCEALED N SLAB FLOOR, <br />E INDICATES EXISTING WIRNG <br />CIRCUIT, EXPOSED, <br />-�T <br />E INDICATES EXISTING WIRING <br />1--t <br />CONDUIT SLEEVE <br />= <br />FLASH MOUNTED PANELBOARD <br />SURFACE MOUNTED PANELBOARD <br />+------ <br />MANUFACTURED WRING SYSTEM <br />- <br />TELEPHONE / DATA BOX FOR ISD <br />LOW VOLTAGE CABLE <br />BOX FOR OTHER <br />m <br />TELEPHONE, FLUSH FLOOR <br />O <br />MOTOR <br />0 <br />TELEPOWE2 POLE <br />4 <br />PUSH BUTTON <br />aBUZZER <br />SAIL SWITCH <br />JUNCTION BOX <br />SO <br />SMOKE DETECTOR <br />HORNISTROBE <br />® <br />DOOR HOLD OPEN <br />ABBREVIATIONS <br />CF (SING FAN <br />Co CHECK OUT <br />CW CASHWRAP <br />EF EXHAUST FAN <br />ETR EXISTING TO REMAIN <br />G GROUND <br />GFI GROUND FAULT CIRCUIT INTERRUPTER <br />IG ISOLATED GROUND <br />REC REFRIGERATION ELECTRICAL CONTRACTOR <br />RC REFRIGERATION CONTRACTOR <br />RH RADIANT HEATER <br />Sc SECURITY CAMERA <br />TR TAMPER RESISTANT <br />U H UNIT HEATER <br />WH WATER HEATER <br />WP WEATHER PROOF COVERPLATE <br />WR WEATHER RESISTANT RECEPTACLE <br />O <br />RELOCATE LIGHT SWITCH TO <br />V1ALL AND RECONNECT TO <br />EXISTING LIGHTING CIRCUIT <br />1 <br />I <br />3C F�� <br />SEAFOOD INTERNAL HIGH POWER PLAN <br />10=1'4r <br />KEY PLAN <br />1 11W _ V4r <br />ELECTRICAL KEYNOTES <br />16.4V E.C. SHALL COORDINATE WffH GENERAL <br />CONTRACTOR AND ARCI-IITECTURAL <br />DEMOLITION PLANS THE EXTENT OF <br />EECTRICAL DEMOLITION_ REAAOVE <br />CONDIATS AND WIRES ALL THE WAY BACK TO <br />ORIGINATING JUNCTION BOXES OR <br />PN*jXV DS- DEMOLITION SHALL NOT <br />AFFECT ACTIVECVZCUR& LABEL - <br />DEMOLISHED CIRCUTP N PANE EX) ARDS <br />AS'SPAW- COORDINATE EXACT <br />REOLAtEMENTS WITH EXISTING CONDITIONS <br />PRIOR TO BID. <br />16_W04 120 VOLT GENERAL PO W R CIRCUIT(S): <br />FURNISH AND INSTALL NEW 20 AMP,12D VOLT <br />CRCxUIT(S), OR AS SPECIFIED ON DRAWINGS <br />Fib FROM NEAREST 120 VOLT PANEL, WITH <br />ADEQUATE SPACE AND AMPACTTY. A CIRCUIT <br />BAKER FOR CIRCUITS INDICTED WITH <br />(GFI) SHALL BE GFCI TYPE FOR PERSONNEL <br />PROTECTION_ <br />16.W07 208 VOLT GENERAL POWER CIRCUIT: <br />FURNISH AND INSTALL NEW 208 VOLT <br />CIRCUIT, AS SPECIFIED ON DRAWINGS. FEED <br />FROM NEAREST 208 VOLT PANEL, WITH <br />ADEQUATE SPACE AND AAMPACITY. <br />GENERAL POWER NOTES <br />1 TELEPO NM POLE(S): MOUNT JUNCTION BOX(ES) TO TOP <br />SIDE OF BOTTOM CHORD OF BAR JOIST_ INSTALL <br />FURNISH® PRE -WIRED POWER POLE AND TERMINATE <br />PROVIDED FLEXIBLE CONDUIT AND WIRING TO JUNCTION <br />BOX. PROVIDE UNISTRUT SUPPORTS AND HARDWARE TO <br />SECURE TE EPOWER POLE PL.LI B TO BUILDING <br />STRUCTURE <br />2- PROVIDE LIQUID:nGHT FLEXIBLE METAL CONDUIT AND <br />WIRING FROM DISCONNECT SWITCH OR JUNCTION BOX TO <br />EQUIPMENT KNOCKOUT OR ELECTRICAL CONNECTION <br />POINT. <br />3- WIBRE ErQI>pMENT NAMEPLATE PROTECTIVE DEVICE <br />RATING DEFERS FROM S12E PROVIDED, CHANGE OUT <br />BRANCH! CIRCUIT WIRING AND OVERCURRENT DEVICE TO <br />APPROPRIATE RATING PER NEC. <br />4- ELECTRONIC FIRE PRoTEcTnvsEGuRrry ALARM BOXES <br />AND CONDUITS SHOWM ON POWER PLANS SHALL BE <br />PROVIDED UNDER THIS CONTRACT. N ADDITION, UNLESS <br />NOTED OTHERWISE, THE FOLLOWING GENERAL NOTES <br />APPLY: <br />A- ALL ALARM JUNCTION BOXES SHALL BE <br />4'C4'X2-1/8' MINIMUM. <br />B- ALARM RACEWAYS SHALL BE 314' MINIMUM WITH <br />PILL VdRE AND NSt"TNG BUSHINGS AT END OF <br />VERTICAL RA(EV1AY RUN. <br />C- VERTICAL RACEWAYS FROM ALARM BOXES SHALL BE <br />EITHER CONCEALED INSIDE WAALL OR SURFACE <br />MOUNTED (TO MATCH JUNCTION BOX MOUNTING). ALL <br />VERTICAL RUNS SHALL BE TURNED 900EGREES AT <br />TOP SIDE OF BOTTOM CHORD OF BAR JOIST AND <br />EXTENDED HORIZONTALLY TO A LOCATION ACCESSIBLE <br />BY VERTICAL FLOOR TYPE LIFT. <br />5- UPON COMPLETION OF ELECTRICAL INSTALLATION AND <br />PRIOR TO ENERGIZING CRCUIT- <br />A- INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE. <br />B- PERFORM CONTNUITY TEST. <br />C- VERIFY PROPER PHASING CONNECTION TO ALL THREE <br />PHASE MOTOR LOADS. <br />20A WIRE SIZING SCHEDULE <br />ALL WIRE SIZES SHOWN ON PANEL SCHEDULES AND <br />PLANS ARE INTENDED TO BE MINMALIIM ACCEPTABLE <br />WIRE SIZE - <br />THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE <br />WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT). <br />LENGTHS; (N FEET) ARE INTENDED TO BE MAXIMUM. <br />FINAL CONNECTIONS: WHERE 20A BRANCH CIRCUITS <br />HAVE 08 AND LARGER WIRE CALLED OUT, #10AWG WIRE <br />MAY BE USED FOR THE FINAL CONNECTION (16 MAX.)_ <br />12D VOLT <br />#12 <br />#10 <br />#8 <br />#6 <br />1S AMPS <br />200 FT. <br />325 FT. <br />4W FT. <br />7T0 HT. <br />6-10 AMPS <br />100 FT. <br />160 FT. <br />245 FT. <br />385 FT. <br />1145 AMPS <br />70 FT. <br />110 FT. <br />165 FT. <br />255 FT. <br />277 VOLT <br />#12 <br />#10 <br />#8 <br />#6 <br />1S AMPS <br />4W FT. <br />760 FT. <br />1170 FT. <br />1865 FT. <br />6-10 AMPS <br />240 FT. <br />380 FT. <br />585 FT. <br />930 FT. <br />11-15 AMPS <br />160 FT. <br />250 FT. <br />390 FT. <br />620 FT. <br />GENERAL NOTES <br />06.31.12 EN08 <br />1- FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND <br />LABOR, FOR A COMPLETE INSTALLATION IN ALL RESPECTS, <br />READY FOR INTENDED USE AND IN STRICT ACCORDANCE WITH <br />NEC, NESC, STATE, AND LOCAL CODES, AND MANUFACTURERS <br />RECOMMENDATIONS. PAY ALL NECESSARY FEES AND PERMITS. <br />A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS <br />THE ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR <br />WVALL.S. <br />B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE <br />C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE <br />OPERATIONS. COORDINATE ALL DISRUPTIONS WITH <br />WWLMART CONSTRUCTION MANAGER AND STORE MANAGER. <br />D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESSES <br />BEFORE INSTALLING BOXES. FURNISH AND INSTALL <br />EXTENDED BOXES OR BOX EXTENDERS WHERE REQUIRED. <br />E- CONTRACTOR SHALL VERIFY THAT ALL AFFECTED <br />PANEBOARDS HAVE CIRCUIT BREAKER KNOCKOUTS <br />PROPERLY COVERED AND THAT ALL TRIM IS IN GOOD <br />CONDITION, ALLOWING NO ACCESS TO LIVE PARTS. <br />2- PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS: <br />A- FIRE RATED WALLS- SEAL PER SPECIFICATIONS FOR FIRE <br />STOPPING. <br />B NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL <br />C FREEZERCOOLER BOXES: SEAL WITH EXPANDING FOAM <br />SEALANT. <br />D- EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR <br />SEALING REQUIREMENTS AT ALL EXTERIOR MOUNTED <br />DEVICES, FIXTURES, ENCLOSURES, AND RACEWAY <br />PENETRATIONS. <br />3- PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR <br />(SIZE PER NEC) N PVC TYPE CONDUIT, POWER CIRCUITS, <br />ISOLATED GROUND CIRCUITS, OR AS SHOWN ON PLANS. <br />CONDUIT SHALL BE SIZED PER NEC BASED ON THWN 600 <br />VOLT COPPER SINGLE CONDUCTORS, PLUS THE EQUIPMENT <br />GROUNDING CONDUCTOR <br />4- WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM <br />FINISHED FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED <br />OTHERWISE ON PLANS. COORDINATE THE STANDARD <br />MOUNTING HEIGHTS WITH MASONRY: <br />A. SWITCHES +46' <br />B. RECEPTACLES +20' <br />C. VOK;F"TA +20' <br />5- WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT <br />IN CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING <br />DIAGRAMS. <br />6- CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE <br />PANELBOARD IDENTIFICATION SCHEDULES FOR PANE BOARDS <br />AFFECTED BY REMODEL- <br />7- NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN <br />EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL <br />MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT <br />PROTECTIVE DEVICES <br />8- BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG THHN <br />UNLESS NOTED OTHERWISE N SCHEDULES. WHERE 20A <br />BRANCH CIRCUITS HAVE #8 AND LARGER WIRE SPECIFIED, #10 <br />AWG WIRE SHALL BE USED FOR THE FINAL CONNECTION <br />(15-FT MAXIMUM)_ <br />9. WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND <br />DERATE CURRENT CARRYING CONDUCTORS PER NEC. <br />10. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE <br />SHALL BE MADE TO BRIDGING OR JOIST WEB MEMBERS. <br />UTILIZE ONLY THE TOP AND BOTTOM CHORDS FOR <br />SUPPORTING THE ELECTRICAL SYSTEM INSTALLATIONS. <br />1i. DEVICES SHOWN ON COOLEWFREEZER PANELS SHALL BE <br />SURFACE MOUNTED UNLESS NOTED OTHERWISE REFER TO <br />ARCHITECTURAL DOCUMENTS FOR CONDUIT INSTALLATION AND <br />SEALING REQUIREMENTS. <br />12. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM <br />AND BRANCH CIRCUITS NOTED BY LEGEND SHALL BE <br />INSTALLED UNDER SLAB. ALL OTHER FEEDER AND BRANCH <br />CIRCUITS SHALL BE INSTALLED OVERHEAD. PROVIDE EXTERIOR <br />COATED GRC BENDS ON ALL CONDUIT RUINS THAT HAVE 45 <br />DEGREE BENDS OR GREATER REF SPECIFICATIONS. <br />13. SEISMIC ZONE REQUIREMENTS-. PROVIDE EXPANSION COUPLINGS <br />AND BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY <br />LOCAL CODES. <br />14. EXISTING ELECTRICAL AND ALARM: <br />A- WHERE DEMOLITION OR NEW INTERRUPTS <br />EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING <br />EQUIPMENT, DEVICES, OR LIGHTING TO REMAIN, BUT NOT <br />SHOWN ON DRAWINGS, PROVIDE LABOR AND MATERIALS TO <br />REWORK CIRCUITRY, AS REQUIRED, TO MAINTAIN EXISTING <br />OPERATION. <br />B• IF DEMOLTION OR NEW CONSTRUCTION WILL DISRUPT <br />EXISTING UNDERGROUND SERVICES (ELECTRICAL, <br />TELEPHONE, PARKING LOT LIGHTING CIRCUITRY, ETC-) <br />PROVIDE ALL MATERIALS AND LABOR AS REQUIRED TO <br />REROUTE, SLEEVE, OR OTHERWISE REWORK THESE SERVICES <br />TO MAINTAIN THEIR EXISTING OPERATION. <br />C LSE CAUTION AROUND At AND SECURITY CABLES <br />- EXERC <br />DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM <br />AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO <br />THAT SYSTEMS REMAIN OPERATIONAL AT ALL TINES. <br />D- DISPOSE OF ALL REMOVED MATERIALS, UNLESS OT'HERWWSE <br />NOTED. <br />15. EXISTING ELECTRICAL DEbbLf170N: <br />A- GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL <br />EQUIPMENT CONDUIT, AND CONDUCTORS AS INDICATED ON <br />THE DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION. <br />SCO NE T SWITCHES BOXES <br />0 <br />w m m%O Cw0Dy <br />W p moMaz <br />wTwww w 1a <br />ix <br />~Q���mam°am <br />lL cFLI 0) aLLF?Wit Wi <br />z 22 �am�00 rOZp <br />O g 0 ogj`�fsa- <br />$� 05 m�� I'i p <br />D a luo aumn—wom <br />IL <br />pmo"'°�g` Sma°cmw S <br />w x i nook-0 ww-wx <br />Ego <br />gZ■ <br />0 <br />� S <br />Z <br />z <br />�_ <br />U <br />�$ <br />z <br />w <br />O O <br />w <br />O C= <br />OO <br />J <br />w <br />O <br />J <br />M <br />$ <br />Z <br />1.i.. <br />0 <br />Z <br />O <br />N <br />N <br />w <br />m <br />D <br />z <br />O <br />ISSUE BLOCK I <br />CHECKED BY: <br />SAG <br />DRAWN BY: <br />JOP <br />FEE N <br />E1 <br />PROTO CYCLE <br />07/03/18 <br />DOCUMENT DATE: <br />07/25/18 <br />REMOVE ALL PANELBOARDS, DI N C , <br />RELAYS, TIME SWITCHES, LIGHTS, DEVICES, ETC., WHICH <br />WILL NOT BE REUSED. <br />B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT, <br />CONDUCTORS AND RELATED DEVICES SERVING SALES AREA <br />GONDOLAS BEING RELOCATED OR REMOVED. EXISTING <br />CONDUIT AND CONDUCTORS MAY BE REUSED FOR NEW <br />POWER DROPS WHERE SIZE, RATING, AND CONDITION MEET <br />REQUIREMENTS INDICATED ON PLANS AND ALL U.L RATINGS. REL40VE ALL <br />D CONDUIT AND <br />CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER ����````0' <br />FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS'SP, <br />PROVIDE HANDLE DEVICE TO LOCK'SPARE' CIRCUIT * 19 <br />BREAKER IN THE `OFF` POSITION. = * = <br />C- CONDUIT AND WIRING TO BE ABANDONED IN CEILING " 78 L ST <br />SPACES AND OTHER NON-PUBLIC AREAS (I.E., THROU6g,0wk ; uG 0 3 2�t8 <br />STOCKROOM AREA): CUT WIRING LOOSE AND REMOVE�i �iQ "' O pP �� ��� <br />FROM RACEWAY(S), LEAVING RACEWAY(S) IN PLACE - <br />CONDUIT <br />CONDUIT TO 13E ABANDONED IN WALLS OR FLOORS SHALL /lllll <br />BE REMOVED BACK TO FINISHED SURFACE AND CAPPED <br />INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT. RIIINI�1 ' ��' P.E. <br />D- ALL C9RCUT BREAKERS SERVING BRANCH CIRCUITS TO BE FL I179819 <br />ABANDONED OR REMOVED SHALL REMAIN IN RESPECTIVE <br />PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE <br />ON DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK'SPARE` <br />CIRCUIT BREAKER IN THE'OFF' POSITION. <br />E- DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO <br />SELECTIVE SITE SON SPECIFICATION FOR <br />DISPOSAL OF LIGHT FIXTURE. <br />F. BUILDING COMPONENTS ABANDONED BY THE SCOPE OF <br />WORK SHALL BE SECURED TO PREVENT FALLING, <br />LOOSENING, OR CREATING DAMAGE OF ANY KIND IN THE <br />FUTURE. <br />EXISTING CONDITIONS WERE TAKEN FROM <br />ORIGINAL DRAWINGS AND MAY NOT REFLECT <br />EXACT AS-BUILr CONDITIONS. CONTRACTOR <br />SHALL FIELD VERIFY ALL EXISTING CONDIITONS <br />PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR <br />SHALL CAREFULLY COORDINATE NEW WORK AND <br />DEMOLITION ION WITH ALL OTHER DIMMES AMID <br />EXISTING CONDITIONS. <br />NOTE: <br />RECEPTACLES, SWITCHES, DATA BOXES <br />AND THEIR CORRESPONDING COVER <br />PLATES SHALL BE WHITE NYLON. <br />EACH SLBCONTRATOR IS RESPONSIBLE FOR HAVING A <br />THOROUGH KNOWLEDGE OF ALL DRAWINGS AND <br />SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE <br />TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES <br />NOT RELIEVE THE RESPONSIBILITY OF PERFORMING <br />THE WORK PROPERLY. NO ADDITIONAL <br />COMPENSATION SHALL BE ALLOWED BECAUSE OF <br />CONDITIONS THAT OCCUR DUE TO FAILURE TO <br />FAMILIARIZE WORKERS WITH THIS KNOWLEDGE <br />ELECTRICAL <br />PLANS <br />SHEET - <br />El <br />