GENERAL NOTES ELECTRICAL SYMBOLS LEGEND
<br />10.28.16 (SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS) ES06
<br />GENERAL POWER NOTES
<br />20A WIRE SIZING SCHEDULE
<br />10.28.16 EN08
<br />SYMBOL
<br />DESCRIPTION
<br />1. FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND
<br />LABOR, FOR A COMPLETE INSTALLATION IN ALL RESPECTS,
<br />READY FOR INTENDED USE AND IN STRICT ACCORDANCE WITH
<br />/
<br />LIGHT FIXTURE
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />LIGHT FIXTURE
<br />NEC, NESC, STATE, AND LOCAL CODES, AND MANUFACTURER'S
<br />RECOMMENDATIONS. PAY ALL NECESSARY FEES AND PERMITS.
<br />LIGHT FIXTURE
<br />A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS
<br />THE ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR
<br />EMERGENCY LIGHT
<br />LIGHT FIXTURE
<br />WALLS.
<br />B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE.
<br />NIGHT LIGHT
<br />0
<br />ENCLOSED COOLER/FREEZER LIGHT
<br />C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE
<br />OPERATIONS. COORDINATE ALL DISRUPTIONS WITH
<br />WALMART CONSTRUCTION MANAGER AND STORE MANAGER.
<br />TRACK LIGHTING
<br />D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESSES
<br />BEFORE INSTALLING BOXES. FURNISH AND INSTALL
<br />EXTENDED BOXES OR BOX EXTENDERS WHERE REQUIRED.
<br />®
<br />EXIT FIXTURE
<br />(WALL MOUNTED CEILING MOUNTED)
<br />E. CONTRACTOR SHALL VERIFY THAT ALL AFFECTED
<br />EMERGENCY FIXTURE
<br />PANELBOARDS HAVE CIRCUIT BREAKER KNOCKOUTS
<br />PROPERLY COVERED AND THAT ALL TRIM IS IN GOOD
<br />$
<br />SWITCH, SINGLE POLE
<br />CONDITION, ALLOWING NO ACCESS TO LIVE PARTS.
<br />$3
<br />SWITCH, 3-WAY
<br />2. PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS:
<br />A. FIRE RATED WALLS: SEAL PER SPECIFICATIONS FOR FIRE
<br />STOPPING.
<br />$4
<br />SWITCH, 4-WAY
<br />B. NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL.
<br />$K
<br />SWITCH, KEYED
<br />C. FREEZER/COOLER BOXES: SEAL WITH EXPANDING FOAM
<br />SEALANT.
<br />$D
<br />SWITCH, DIMMER
<br />D. EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR
<br />SEALING REQUIREMENTS AT ALL EXTERIOR MOUNTED
<br />$VS
<br />SWITCH, VARIBLE SPEED
<br />DEVICES, FIXTURES, ENCLOSURES, AND RACEWAY
<br />PENETRATIONS.
<br />3. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR
<br />(SIZE PER NEC) IN PVC TYPE CONDUIT, POWER CIRCUITS,
<br />$M
<br />SWITCH, MANUAL MOTOR
<br />ISOLATED GROUND CIRCUITS, OR AS SHOWN ON PLANS.
<br />CONDUIT SHALL BE SIZED PER NEC BASED ON THWN 600
<br />$OS
<br />SWITCH, OCCUPANCY SENSOR
<br />VOLT COPPER SINGLE CONDUCTORS, PLUS THE EQUIPMENT
<br />$$Og
<br />SWITCH, BI-LEVEL OCCUPANCY SENSOR
<br />GROUNDING CONDUCTOR.
<br />4. WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM
<br />OS R
<br />❑/
<br />CEILING OCCUPANCY SENSOR AND ASSOCIATED RELAY
<br />FINISHED FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED
<br />OTHERWISE ON PLANS. COORDINATE THE STANDARD
<br />MOUNTING HEIGHTS WITH MASONRY:
<br />A. SWITCHES +44"
<br />RECEPTACLE, DUPLEX
<br />B. RECEPTACLES +20"
<br />C. VOICE/DATA +20"
<br />�
<br />RECEPTACLE, DUPLEX,
<br />MOUNTED HORIZONTALLY
<br />5. WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT
<br />IN CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING
<br />RECEPTACLE, DOUBLE DUPLEX
<br />DIAGRAMS.
<br />RECEPTACLE, DUPLEX ISOLATED GROUND
<br />6. CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE
<br />PANELBOARD IDENTIFICATION SCHEDULES FOR PANELBOARDS
<br />RECEPTACLE, DOUBLE DUPLEX,
<br />AFFECTED BY REMODEL.
<br />7. NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN
<br />EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL
<br />ISOLATED GROUND
<br />n
<br />RECEPTACLE, SIMPLEX TWIST LOCK,
<br />MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT
<br />`Y
<br />L5-15R, UNO
<br />RECEPTACLE, SIMPLEX TWIST LOCK,
<br />PROTECTIVE DEVICES.
<br />8. BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG
<br />ISOLATED GROUND, L5-15R, UNO
<br />RECEPTACLE, DUPLEX TWIST LOCK,
<br />UNLESS NOTED OTHERWISE IN SCHEDULES. WHERE 20A
<br />BRANCH CIRCUITS HAVE #8 AND LARGER WIRE SPECIFIED, #10
<br />L5-15R, LINO
<br />AWG WIRE SHALL BE USED FOR THE FINAL CONNECTION
<br />(15-FT MAXIMUM).
<br />RECEPTACLE, DUPLEX TWIST LOCK,
<br />ISOLATED GROUND, L5-15R, UNO
<br />RECEPTACLE, SPECIAL
<br />9. WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND
<br />DERATE CURRENT CARRYING CONDUCTORS PER NEC.
<br />RECEPTACLE, SIMPLEX
<br />10. PROVIDE UL LISTED HANDLE TIES ON ALL MULTIWIRE BRANCH
<br />CIRCUITS PER NEC REQUIREMENTS.
<br />11. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE
<br />RECEPTACLE, PLUG -MOLD
<br />SHALL BE MADE TO BRIDGING OR JOIST WEB MEMBERS.
<br />UTILIZE ONLY THE TOP AND BOTTOM CHORDS FOR
<br />SUPPORTING THE ELECTRICAL SYSTEM INSTALLATIONS.
<br />O
<br />JUNCTION BOX
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />Q
<br />JUNCTION BOX, ALARM SYSTEM
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />12. DEVICES SHOWN ON COOLER/FREEZER PANELS SHALL BE
<br />SURFACE MOUNTED UNLESS NOTED OTHERWISE. REFER TO
<br />ARCHITECTURAL DOCUMENTS FOR CONDUIT INSTALLATION AND
<br />SEALING REQUIREMENTS.
<br />®
<br />ALARM JUNCTION BOX,
<br />FOR REMOTE TEST/RESET
<br />13. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />EQUIPMENT CONNECTION POINT
<br />(PROVIDED WITH EQUIPMENT)
<br />AND BRANCH CIRCUITS NOTED BY LEGEND SHALL BE
<br />INSTALLED UNDER SLAB. ALL OTHER FEEDER AND BRANCH
<br />CIRCUITS SHALL BE INSTALLED OVERHEAD. PROVIDE EXTERIOR
<br />COATED GRC BENDS ON ALL CONDUIT RUNS THAT HAVE 45
<br />O,
<br />NON -FUSED DISCONNECT
<br />DEGREE BENDS OR GREATER. REF SPECIFICATIONS.
<br />14. SEISMIC ZONE REQUIREMENTS: PROVIDE EXPANSION COUPLINGS
<br />01
<br />FUSED DISCONNECT
<br />AND BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY
<br />LOCAL CODES.
<br />SVATCHmIS
<br />TRAVELERN�TRAL
<br />CIRCUIT, CONCEALED IN WALLS OR
<br />CEILING, E INDICATES EXISTING
<br />15. EXISTING ELECTRICAL AND ALARM:
<br />",ND
<br />WIRING
<br />CIRCUIT, CONCEALED IN FLOOR SLAB,
<br />A. WHERE DEMOLITION OR NEW CONSTRUCTION INTERRUPTS
<br />EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING"�
<br />E INDICATES EXISTING WIRING
<br />EQUIPMENT, DEVICES, OR LIGHTING TO REMAIN, BUT NOT
<br />CIRCUIT, EXPOSED,
<br />SHOWN ON DRAWINGS, PROVIDE LABOR AND MATERIALS TO
<br />E INDICATES EXISTING WIRING
<br />REWORK CIRCUITRY, AS REQUIRED, TO MAINTAIN EXISTING
<br />OPERATION.
<br />=
<br />FLUSH MOUNTED PANELBOARD
<br />B. IF DEMOLITION OR NEW CONSTRUCTION WILL DISRUPT
<br />EXISTING UNDERGROUND SERVICES (ELECTRICAL,
<br />SURFACE MOUNTED PANELBOARD
<br />TELEPHONE, PARKING LOT LIGHTING CIRCUITRY, ETC.)
<br />PROVIDE ALL MATERIALS AND LABOR AS REQUIRED TO
<br />-/-d/-
<br />VOICE/DATA,
<br />REROUTE, SLEEVE, OR OTHERWISE REWORK THESE SERVICES
<br />v
<br />d = DATA ONLY, v = VOICE ONLY
<br />TO MAINTAIN THEIR EXISTING OPERATION.
<br />C. EXERCISE CAUTION AROUND ALARM AND SECURITY CABLES
<br />Q
<br />LOW VOLTAGE CABLE BOX FOR OTHER
<br />DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM
<br />AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO
<br />®
<br />VOICE/DATA, FLUSH FLOOR
<br />THAT SYSTEMS REMAIN OPERATIONAL AT ALL TIMES.
<br />D. DISPOSE OF ALL REMOVED MATERIALS, UNLESS OTHERWISE
<br />MOTOR
<br />NOTED.
<br />16. EXISTING ELECTRICAL DEMOLITION:
<br />0
<br />TELEPOWER POLE
<br />A. GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL
<br />EQUIPMENT CONDUIT, AND CONDUCTORS AS INDICATED ON
<br />PUSH BUTTON
<br />THE DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION.
<br />REMOVE ALL PANELBOARDS, DISCONNECT SWITCHES, BOXES,
<br />RELAYS, TIME SWITCHES, LIGHTS, DEVICES, ETC., WHICH
<br />u
<br />6
<br />BUZZER
<br />WILL NOT BE REUSED.
<br />B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT,
<br />O
<br />SMOKE DETECTOR
<br />CONDUCTORS AND RELATED DEVICES SERVING SALES AREA
<br />ENERGY MANAGEMENT
<br />GONDOLAS BEING RELOCATED OR REMOVED. EXISTING
<br />O
<br />TEMPERATURE SENSOR
<br />CONDUIT AND CONDUCTORS MAY BE REUSED FOR NEW
<br />POWER DROPS WHERE SIZE, RATING, AND CONDITION MEET
<br />O
<br />THERMOSTAT
<br />REQUIREMENTS INDICATED ON PLANS AND ALL U.L.
<br />FIC1
<br />TIME CLOCK
<br />RATINGS. REMOVE ALL UNUSED CONDUIT AND
<br />CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER
<br />FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS "SPARE".
<br />PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT
<br />ABBREVIATIONS
<br />BREAKER IN THE "OFF" POSITION.
<br />a, b, c LOWER CASE LETTERS INDICATE HD HAND DRYER
<br />SWITCHING CONFIGURATION IG ISOLATED GROUND
<br />C. CONDUIT AND WIRING TO BE ABANDONED IN CEILING
<br />AFC ABOVE FINISH COUNTER IRC INTER -REGISTER
<br />SPACES AND OTHER NON-PUBLIC AREAS (I.E., THROUGH
<br />AFF ABOVE FINISH FLOOR COMMUNICATION
<br />STOCKROOM AREA): CUT WIRING LOOSE AND REMOVE
<br />AFG ABOVE FINISH GRADE ISP IN-STORE PROCESSOR
<br />FROM RACEWAY(S), LEAVING RACEWAY(S) IN PLACE.
<br />C CONDUIT LCU LIGHTING CONTROL UNIT
<br />CONDUIT TO BE ABANDONED IN WALLS OR FLOORS SHALL
<br />BE REMOVED BACK TO FINISHED SURFACE AND CAPPED
<br />INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT.
<br />CCT CIRCUIT K KEY OPERATED
<br />CF CEILING/CIRCULATION FAN N NEUTRAL
<br />D DATA NTS NOT TO SCALE
<br />EC ELECTRICAL CONTRACTOR P WITH PILOT LIGHT
<br />D. ALL CIRCUIT BREAKERS SERVING BRANCH CIRCUITS TO BE
<br />EF EXHAUST FAN RH RADIANT HEATER
<br />ABANDONED OR REMOVED SHALL REMAIN IN RESPECTIVE
<br />EP EXPLOSION PROOF RC REFRIGERATION
<br />PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE
<br />ETR EXISTING TO REMAIN CONTRACTOR
<br />ON DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK "SPARE"
<br />EWC ELECTRIC WATER COOLER SC SECURITY CAMERA
<br />CIRCUIT BREAKER IN THE "OFF" POSITION.
<br />FUT FUTURE SF SUPPLY FAN
<br />E. DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO
<br />SELECTIVE SITE DEMOLITION SPECIFICATION FOR
<br />GR GROUND TR TAMPER RESISTANTGFEP GROUND FAULT EQUIPMENT TYP TYPICAL
<br />PROTECTION WH WATER HEATER
<br />DISPOSAL OF LIGHT FIXTURE.
<br />GFI GROUND FAULT CIRCUIT WP WEATHERPROOF
<br />F. BUILDING COMPONENTS ABANDONED BY THE SCOPE OF
<br />WORK SHALL BE SECURED TO PREVENT FALLING,
<br />LOOSENING, OR CREATING DAMAGE OF ANY KIND IN THE
<br />FUTURE.
<br />INTERRUPTER WR WEATHER RESISTANT
<br />GF GABLE FAN UH UNIT HEATER
<br />LINO UNLESS NOTED
<br />OTHERWISE
<br />17. ETHERNET CABLE:
<br />A. FURNISH AND INSTALL JUNCTION BOXES AS SHOWN ON
<br />PLANS. PROVIDE CONDUIT AS REQUIRED BY LOCAL CODES
<br />AND/OR ORDINANCES.
<br />B. ETHERNET CABLE IS FURNISHED BY OTHERS.
<br />C. ELECTRICAL CONTRACTOR SHALL INSTALL CABLE IN POWER
<br />POLES.
<br />D. ELECTRICAL CONTRACTOR SHALL INSTALL OTHER CABLE AS
<br />DIRECTED BY WALMART CONSTRUCTION MANAGER.
<br />0
<br />^-----------------------.1
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />16.492
<br />CHECKOUTS
<br />AND COOLERS
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />(
<br />I
<br />I
<br />I
<br />I
<br />r
<br />I
<br />1
<br />EXISTING WALMART
<br />CVTCDIf1D CIrA1
<br />01 30.14 EN02
<br />1 • TELEPOWER POLE(S): MOUNT JUNCTION BOX(ES) TO TOP
<br />SIDE OF BOTTOM CHORD OF BAR JOIST. INSTALL
<br />FURNISHED PRE -WIRED POWER POLE AND TERMINATE
<br />PROVIDED FLEXIBLE CONDUIT AND WIRING TO JUNCTION
<br />BOX. PROVIDE UNISTRUT SUPPORTS AND HARDWARE TO
<br />SECURE TELEPOWER POLE PLUMB TO BUILDING
<br />STRUCTURE.
<br />2. PROVIDE LIQUID -TIGHT FLEXIBLE METAL CONDUIT AND
<br />WIRING FROM DISCONNECT SWITCH OR JUNCTION BOX TO
<br />EQUIPMENT KNOCKOUT OR ELECTRICAL CONNECTION
<br />POINT.
<br />3. WHERE EQUIPMENT NAMEPLATE PROTECTIVE DEVICE
<br />RATING DIFFERS FROM SIZE PROVIDED, CHANGE OUT
<br />BRANCH CIRCUIT WIRING AND OVERCURRENT DEVICE TO
<br />APPROPRIATE RATING PER NEC.
<br />4• ELECTRONIC FIRE PROTECTION/SECURITY ALARM BOXES
<br />AND CONDUITS SHOWN ON POWER PLANS SHALL BE
<br />PROVIDED UNDER THIS CONTRACT. IN ADDITION, UNLESS
<br />NOTED OTHERWISE, THE FOLLOWING GENERAL NOTES
<br />APPLY:
<br />ALL ALARM JUNCTION BOXES SHALL BE
<br />4"X4"X2-1 /8" MINIMUM.
<br />B. ALARM RACEWAYS SHALL BE 3/4" MINIMUM WITH
<br />PULL WIRE AND INSULATING BUSHINGS AT END OF
<br />VERTICAL RACEWAY RUN.
<br />C. VERTICAL RACEWAYS FROM ALARM BOXES SHALL BE
<br />EITHER CONCEALED INSIDE WALL OR SURFACE
<br />MOUNTED (TO MATCH JUNCTION BOX MOUNTING). ALL
<br />VERTICAL RUNS SHALL BE TURNED 90-DEGREES AT
<br />TOP SIDE OF BOTTOM CHORD OF BAR JOIST AND
<br />EXTENDED HORIZONTALLY TO A LOCATION ACCESSIBLE
<br />BY VERTICAL FLOOR TYPE LIFT.
<br />5. UPON COMPLETION OF ELECTRICAL INSTALLATION AND
<br />PRIOR TO ENERGIZING CIRCUIT:
<br />A. INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE.
<br />B. PERFORM CONTINUITY TEST.
<br />C. VERIFY PROPER PHASING CONNECTION TO ALL THREE
<br />PHASE MOTOR LOADS.
<br />POWER DROP NOTES
<br />1. POWER DROPS WILL BE IDENTIFIED BY AN IPTV TAG OR
<br />POWER TAG, I.E. 44A, 46E, ETC. ALL CHECKOUT POWER
<br />SHALL BE CONSIDERED POWER DROPS.
<br />2. A REVISION OF THIS PLAN BASED ON THE FINAL
<br />MERCHANDISE LAYOUT MAY BE ISSUED TO SHOW FINAL
<br />LOCATIONS FOR THE POWER DROPS. IF THE MERCHANDISE
<br />PLAN DOES NOT CHANGE, THIS PLAN WILL NOT BE
<br />REISSUED. PROVIDE CIRCUITRY TO DISPLAY RACKS AS THE
<br />RACKS ARE SET. IN ADDITION, THE FOLLOWING POWER
<br />DROP NOTES APPLY:
<br />A. THERE WILL BE NO ADDITIONAL CHARGE FOR DROP
<br />RELOCATION WITHIN POWER DROP ZONES DEFINED ON
<br />DRAWING.
<br />B. AT CLOSE OF PROJECT THE GENERAL CONTRACTOR
<br />AND CONSTRUCTION MANAGER SHALL REVIEW
<br />ADDITIONAL OR DELETED POWER DROPS WITHIN EACH
<br />ZONE TO VERIFY ANY ADDITIONAL CHARGES OR
<br />CREDITS THAT APPLY DUE TO CHANGES.
<br />C. ADDING OR SUBTRACTING A POWER DROP TO ANY
<br />ZONE WILL RESULT IN A CHARGE OR CREDIT
<br />ACCORDING TO SPECIAL CONDITIONS.
<br />EN01 a
<br />3. PROVIDE JUNCTION BOX AND CIRCUITRY TO NEAREST
<br />JOIST ABOVE LOCATION SHOWN ON DRAWING. EXTEND
<br />CONDUIT AND CIRCUITRY FROM JUNCTION BOX TO ENDCAP
<br />OF DISPLAY RACK (AWAY FROM ACTION ALLEY).
<br />4. PROVIDE CONDUIT, RECEPTACLE(S) AND FINAL
<br />CONNECTIONS AT DISPLAY RACK SHELVING PER POWER
<br />DROP SCHEDULE UNLESS NOTED OTHERWISE ON DRAWING.
<br />VERIFY EXACT HEIGHT AND LOCATION OF RECEPTACLE(S)
<br />WITH STORE PLANNING SET-UP SUPERVISOR PRIOR TO
<br />INSTALLATION.
<br />5. POWER DROPS FED FROM TRACK BUSWAY:
<br />INSTALL PLUG-IN UNIT IF REQUIRED ON TRACK
<br />BUSWAY AT POINT NEAREST TO POWER DROP(S)
<br />NOTE:
<br />RECEPTACLES, SWITCHES, DATA BOXES AND THEIR
<br />CORRESPONDING COVER PLATES SHALL BE WHITE NYLON.
<br />POWER DROP SCHEDULE
<br />NO. I DESCRIPTION
<br />PD2 MOUNT RECEPTACLE(S) ON BASE OF
<br />DISPLAY UNIT(S)
<br />PD3 PROVIDE DIRECT CONNECTION TO
<br />EQUIPMENT
<br />ALL WIRE SIZES SHOWN ON PANEL SCHEDULES ARE
<br />INTENDED TO BE MINIMUM ACCEPTABLE WIRE SIZE.
<br />THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE
<br />WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT).
<br />LENGTHS (IN FEET) ARE INTENDED TO BE MAXIMUM.
<br />120 VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1-5 AMPS
<br />200 FT.
<br />325 FT.
<br />490 FT.
<br />770 FT.
<br />6-10 AMPS
<br />100 FT.
<br />160 FT.
<br />245 FT.
<br />385 FT.
<br />11-15 AMPS
<br />1 70 FT.
<br />110 FT.
<br />1 165 FT.
<br />1 255 FT.
<br />277 VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1-5 AMPS
<br />480 FT.
<br />760 FT.
<br />1170 FT.
<br />1865 FT.
<br />6-10 AMPS
<br />240 FT,
<br />380 FT.
<br />585 FT.
<br />930 FT.
<br />11-15 AMPS
<br />160 FT.
<br />250 FT.
<br />390 FT.
<br />620 FT.
<br />1lt01to
<br />11.19.10 EN09
<br />ARRANGE ALL WORK THAT REQUIRES POWER INTERRUPTIONS
<br />TO THE STORE TO BE ACCOMPLISHED AFTER NORMAL STORE
<br />BUSINESS HOURS. NOTIFY THE STORE MANAGER AND THE
<br />WALMART CONSTRUCTION MANAGER A MINIMUM OF 48 HOURS
<br />IN ADVANCE OF ALL STORE POWER INTERRUPTIONS. STORE
<br />MANAGER MUST ALLOW FOR POWERING DOWN OF COMPUTER
<br />SYSTEMS, MOVING AFFECTED PRODUCT, MODIFICATION OF
<br />WALMART AFTER-HOURS WORK SCHEDULES, COORDINATION
<br />WITH OTHER TRADES, AND OTHER CRITICAL SCHEDULING
<br />CONCERNS. PROVIDE TEMPORARY POWER AS REQUIRED.
<br />INSTALLATION OF NEW EQUIPMENT SHALL BE COMPLETED AND
<br />THE POWER SYSTEM TESTED AND RE -ENERGIZED PRIOR TO
<br />START OF BUSINESS THE FOLLOWING MORNING NO LATER
<br />THAN A TIME ESTABLISHED BY THE STORE MANAGER AND
<br />THE WALMART CONSTRUCTION MANAGER.
<br />16.125
<br />16.131
<br />��IAfa
<br />16.411
<br />16.414
<br />16.470
<br />Eaq 16.902
<br />ELECTRICAL KEYNOTES
<br />EXISTING LIGHT FIXTURES TO REMAIN UNLESS
<br />NOTED OTHERWISE.
<br />CONNECT TO EXISTING CIRCUIT. E.C. SHALL
<br />VERIFY PRIOR TO ROUGH -IN THAT EXISTING
<br />CIRCUIT HAS SPARE CAPACITY TO
<br />ACCOMMODATE ADDITIONAL LOAD.
<br />AUTOMATIC DOOR OPERATOR: VERIFY LOCATION
<br />WITH MANUFACTURER'S RECOMMENDATIONS PRIOR
<br />TO INSTALLATION. ALL CONDUIT AND WIRING
<br />SHALL BE CONCEALED AT MAIN ENTRANCE DOORS.
<br />PICKUP KIOSK: MOUNT JUNCTION BOX AT
<br />STRUCTURE AND ROUTE 1-1/2" CONDUIT FROM
<br />STRUCTURE TO KIOSK TERMINATION COMPARTMENT.
<br />EXTEND CONDUCTORS IN 1 /2" FLEXIBLE METAL
<br />CONDUIT ROUTED WITHIN THE 1-1/2" CONDUIT TO
<br />MAINTAIN NEC REQUIRED SEPARATION OF POWER
<br />AND DATA. COORDINATE LOCATION WITH KIOSK
<br />INSTALLER PRIOR TO ROUGH -IN.
<br />ORDER READY BOARD: MOUNT JUNCTION BOX
<br />AT STRUCTURE. AFTER INSTALLATION OF DROP
<br />POLE AND TV COMPONENT TRAY, EXTEND
<br />CONDUCTORS IN 1/2" FLEXIBLE METAL CONDUIT
<br />ROUTED WITHIN DROP POLE TO TV COMPARTMENT
<br />TRAY TO MAINTAIN NEC REQUIRED SEPARATION
<br />OF POWER AND DATA. PROVIDE 120V 20A DUPLEX
<br />RECEPTACLE AND FINAL TERMINATION AT TV
<br />COMPONENT TRAY.
<br />FURNISH AND INSTALL NEW 20 AMP, 120 VOLT
<br />CIRCUIT(S). FEED FROM PANELBOARD AS
<br />INDICATED. PROVIDE 20A-1 P CIRCUIT BREAKER
<br />IF NEEDED. E.C. SHALL MATCH MANUFACTURER,
<br />TYPE AND AIC RATINGS OF EXISTING CIRCUIT
<br />BREAKERS. E.C. SHALL VERIFY PRIOR TO
<br />ROUGH -IN THAT EXISTING PANELBOARD HAS
<br />SPARE CAPACITY TO ACCOMMODATE ADDITIONAL
<br />LOAD.
<br />E.C. SHALL COORDINATE WITH GENERAL
<br />CONTRACTOR AND ARCHITECTURAL DEMOLITION
<br />PLANS THE EXTENT OF ELECTRICAL DEMOLITION.
<br />REMOVE CONDUITS AND WIRES ALL THE WAY BACK
<br />TO ORIGINATING JUNCTION BOXES OR
<br />PANELBOARDS. DEMOLITION SHALL NOT AFFECT
<br />ACTIVE CIRCUITS. LABEL DEMOLISHED CIRCUITS)
<br />IN PANELBOARDS AS "SPARE". COORDINATE EXACT
<br />REQUIREMENTS WITH EXISTING CONDITIONS PRIOR
<br />TO BID.
<br />EXTERIOR SIGN POWER: WHERE ELECTRICAL
<br />CONNECTIONS FOR SIGNAGE OCCUR BELOW ROOF
<br />LINE, MOUNT JUNCTION BOX(ES) TO WALL AT
<br />SIGN CONNECTION POINT AND PROVIDE 3/4"
<br />CONDUIT TO CONTROL BOX FOR LOW VOLTAGE
<br />WIRING (INSTALLED BY OTHERS). REFER TO
<br />ARCHITECTURAL DRAWINGS FOR EXACT SIGN
<br />LOCATIONS) PRIOR TO INSTALLATION. WHERE
<br />ELECTRICAL CONNECTIONS FOR SIGNAGE OCCUR
<br />ABOVE ROOF LINE, PROVIDE UNISTRUT TO MOUNT
<br />JUNCTION BOXES TO BACK SIDE OF PARAPET AND
<br />PROVIDE 3/4" CONDUIT TO CONTROL BOX FOR LOW
<br />VOLTAGE WIRING (INSTALLED BY OTHERS).
<br />PROVIDE ONLY ONE PENETRATION THROUGH THE
<br />ROOF. REF ARCHITECTURAL EXTERIOR WALL
<br />SECTIONS AND SIGN ATTACHMENT FOR ROOF AND
<br />PARAPET PENETRATION REQUIREMENTS.
<br />i- — — �, I I - n 1 ¢ : i .f �l .......c. f..f $.,.. �... r rn ly ,/.: �r. I ••,:.;i. r j -1 - 1 -
<br />T�
<br />E..T."�».
<br />•
<br />.. ...... . . . .
<br />:
<br />:
<br />::.
<br />I�•vx, x��F
<br />Is f I 5 s 'ate I:�,..d�.:�::�r, :�se�is.-�<�i;�.<.tu.::�'::::�✓:!,� I I I I I I I I I I�.. � ^^ I�� s i '�€
<br />W.Fj
<br />I+ H� 11
<br />e• � r
<br />................ . . . . . . .
<br />r
<br />:� z 's i • .... i.....r::�vf�<,xra�iahes�?�✓��.�.... I I I I I I I I ( I I
<br />KEY PLAN-
<br />1/64"=l'-Olt
<br />EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
<br />DRAWINGS AND MAY NOT REFLECT EXACT A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
<br />"AS -BUILT" CONDITIONS. CONTRACTOR SHALL FIELD SPECIFICATIONS IN THEIR RELATED FIELD. THE
<br />VERIFY ALL EXISTING CONDITIONS PRIOR TO FAILURE TO ACQUAINT HIMSELF WITH THIS
<br />SUBMITTING FINAL BIDS. CONTRACTOR SHALL KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY
<br />CAREFULLY COORDINATE NEW WORK AND DEMOLITION OF PERFORMING HIS WORK PROPERLY. NO
<br />WITH ALL OTHER DISCIPLINES AND EXISTING ADDITIONAL COMPENSATION SHALL BE ALLOWED
<br />CONDITIONS. BECAUSE OF CONDITIONS THAT OCCUR DUE
<br />TO FAILURE TO FAMILIARIZE WORKERS WITH THIS
<br />KNOWLEDGE.
<br />W C NI-ZW F-o<N
<br />N 0W yOW� ON M2
<br />ZW~ UF�
<br />Z � a <
<br />� <a o�ooN=�<�W
<br />�yZzacJaWicFio=o
<br />Ii a- J aOFZ�� >WFI-
<br />yc� Nnwa�Xv�w$�<r
<br />Z
<br />O30 �44ll �z �<
<br />Zfa!! adow. F(n��0w zo
<br />J� �I`�.RFrN2ycoi
<br />a o
<br />0 oo=QWo�WazWm
<br />_ NWdZr9OWw00a,0>-
<br />�Dkid o�iamzaawoax
<br />*y
<br />o
<br />o
<br />o
<br />H�
<br />O N
<br />m
<br />...
<br />Wz
<br />V1 N
<br />CI V
<br />N
<br />QzaN
<br />Z
<br />W
<br />c
<br />P2
<br />W N
<br />^OX
<br />FQ
<br />M
<br />Z
<br />r
<br />V
<br />0
<br />U
<br />O 0
<br />�
<br />O O
<br />o
<br />00
<br />a
<br />-�
<br />�
<br />N
<br />N
<br />U
<br />0
<br />CD
<br />O
<br />�
<br />� O
<br />0
<br />�i
<br />LIJ
<br />o
<br />cat
<br />O
<br />o
<br />0
<br />N
<br />W
<br />GQ
<br />z
<br />Oq
<br />0
<br />ISSUE BLOCK
<br />CHECKED BY:
<br />HLW
<br />DRAWN BY:
<br />WN
<br />PROTO:
<br />LCC
<br />PROTO CYCLE:
<br />12/30/17
<br />DOCUMENT DATE:
<br />02/16/17
<br />THIS ITEM HAS BEEN
<br />ELECTRONICALLY SIGNED AND
<br />SEALED BY VINCENT G.
<br />MASIL€ONIS
<br />ON THE DATE LISTED BELOW
<br />USING A DIGITAL SIGNATURE.