GENERAL NOTES ELECTRICAL SYMBOLS LEGEND <br />10.28.16 (SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS) ES06 <br />GENERAL POWER NOTES <br />20A WIRE SIZING SCHEDULE <br />10.28.16 EN08 <br />SYMBOL <br />DESCRIPTION <br />1. FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND <br />LABOR, FOR A COMPLETE INSTALLATION IN ALL RESPECTS, <br />READY FOR INTENDED USE AND IN STRICT ACCORDANCE WITH <br />/ <br />LIGHT FIXTURE <br />(WALL MOUNTED/CEILING MOUNTED) <br />LIGHT FIXTURE <br />NEC, NESC, STATE, AND LOCAL CODES, AND MANUFACTURER'S <br />RECOMMENDATIONS. PAY ALL NECESSARY FEES AND PERMITS. <br />LIGHT FIXTURE <br />A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS <br />THE ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR <br />EMERGENCY LIGHT <br />LIGHT FIXTURE <br />WALLS. <br />B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE. <br />NIGHT LIGHT <br />0 <br />ENCLOSED COOLER/FREEZER LIGHT <br />C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE <br />OPERATIONS. COORDINATE ALL DISRUPTIONS WITH <br />WALMART CONSTRUCTION MANAGER AND STORE MANAGER. <br />TRACK LIGHTING <br />D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESSES <br />BEFORE INSTALLING BOXES. FURNISH AND INSTALL <br />EXTENDED BOXES OR BOX EXTENDERS WHERE REQUIRED. <br />® <br />EXIT FIXTURE <br />(WALL MOUNTED CEILING MOUNTED) <br />E. CONTRACTOR SHALL VERIFY THAT ALL AFFECTED <br />EMERGENCY FIXTURE <br />PANELBOARDS HAVE CIRCUIT BREAKER KNOCKOUTS <br />PROPERLY COVERED AND THAT ALL TRIM IS IN GOOD <br />$ <br />SWITCH, SINGLE POLE <br />CONDITION, ALLOWING NO ACCESS TO LIVE PARTS. <br />$3 <br />SWITCH, 3-WAY <br />2. PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS: <br />A. FIRE RATED WALLS: SEAL PER SPECIFICATIONS FOR FIRE <br />STOPPING. <br />$4 <br />SWITCH, 4-WAY <br />B. NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL. <br />$K <br />SWITCH, KEYED <br />C. FREEZER/COOLER BOXES: SEAL WITH EXPANDING FOAM <br />SEALANT. <br />$D <br />SWITCH, DIMMER <br />D. EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR <br />SEALING REQUIREMENTS AT ALL EXTERIOR MOUNTED <br />$VS <br />SWITCH, VARIBLE SPEED <br />DEVICES, FIXTURES, ENCLOSURES, AND RACEWAY <br />PENETRATIONS. <br />3. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR <br />(SIZE PER NEC) IN PVC TYPE CONDUIT, POWER CIRCUITS, <br />$M <br />SWITCH, MANUAL MOTOR <br />ISOLATED GROUND CIRCUITS, OR AS SHOWN ON PLANS. <br />CONDUIT SHALL BE SIZED PER NEC BASED ON THWN 600 <br />$OS <br />SWITCH, OCCUPANCY SENSOR <br />VOLT COPPER SINGLE CONDUCTORS, PLUS THE EQUIPMENT <br />$$Og <br />SWITCH, BI-LEVEL OCCUPANCY SENSOR <br />GROUNDING CONDUCTOR. <br />4. WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM <br />OS R <br />❑/ <br />CEILING OCCUPANCY SENSOR AND ASSOCIATED RELAY <br />FINISHED FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED <br />OTHERWISE ON PLANS. COORDINATE THE STANDARD <br />MOUNTING HEIGHTS WITH MASONRY: <br />A. SWITCHES +44" <br />RECEPTACLE, DUPLEX <br />B. RECEPTACLES +20" <br />C. VOICE/DATA +20" <br />� <br />RECEPTACLE, DUPLEX, <br />MOUNTED HORIZONTALLY <br />5. WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT <br />IN CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING <br />RECEPTACLE, DOUBLE DUPLEX <br />DIAGRAMS. <br />RECEPTACLE, DUPLEX ISOLATED GROUND <br />6. CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE <br />PANELBOARD IDENTIFICATION SCHEDULES FOR PANELBOARDS <br />RECEPTACLE, DOUBLE DUPLEX, <br />AFFECTED BY REMODEL. <br />7. NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN <br />EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL <br />ISOLATED GROUND <br />n <br />RECEPTACLE, SIMPLEX TWIST LOCK, <br />MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT <br />`Y <br />L5-15R, UNO <br />RECEPTACLE, SIMPLEX TWIST LOCK, <br />PROTECTIVE DEVICES. <br />8. BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG <br />ISOLATED GROUND, L5-15R, UNO <br />RECEPTACLE, DUPLEX TWIST LOCK, <br />UNLESS NOTED OTHERWISE IN SCHEDULES. WHERE 20A <br />BRANCH CIRCUITS HAVE #8 AND LARGER WIRE SPECIFIED, #10 <br />L5-15R, LINO <br />AWG WIRE SHALL BE USED FOR THE FINAL CONNECTION <br />(15-FT MAXIMUM). <br />RECEPTACLE, DUPLEX TWIST LOCK, <br />ISOLATED GROUND, L5-15R, UNO <br />RECEPTACLE, SPECIAL <br />9. WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND <br />DERATE CURRENT CARRYING CONDUCTORS PER NEC. <br />RECEPTACLE, SIMPLEX <br />10. PROVIDE UL LISTED HANDLE TIES ON ALL MULTIWIRE BRANCH <br />CIRCUITS PER NEC REQUIREMENTS. <br />11. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE <br />RECEPTACLE, PLUG -MOLD <br />SHALL BE MADE TO BRIDGING OR JOIST WEB MEMBERS. <br />UTILIZE ONLY THE TOP AND BOTTOM CHORDS FOR <br />SUPPORTING THE ELECTRICAL SYSTEM INSTALLATIONS. <br />O <br />JUNCTION BOX <br />(WALL MOUNTED/CEILING MOUNTED) <br />Q <br />JUNCTION BOX, ALARM SYSTEM <br />(WALL MOUNTED/CEILING MOUNTED) <br />12. DEVICES SHOWN ON COOLER/FREEZER PANELS SHALL BE <br />SURFACE MOUNTED UNLESS NOTED OTHERWISE. REFER TO <br />ARCHITECTURAL DOCUMENTS FOR CONDUIT INSTALLATION AND <br />SEALING REQUIREMENTS. <br />® <br />ALARM JUNCTION BOX, <br />FOR REMOTE TEST/RESET <br />13. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM <br />(WALL MOUNTED/CEILING MOUNTED) <br />EQUIPMENT CONNECTION POINT <br />(PROVIDED WITH EQUIPMENT) <br />AND BRANCH CIRCUITS NOTED BY LEGEND SHALL BE <br />INSTALLED UNDER SLAB. ALL OTHER FEEDER AND BRANCH <br />CIRCUITS SHALL BE INSTALLED OVERHEAD. PROVIDE EXTERIOR <br />COATED GRC BENDS ON ALL CONDUIT RUNS THAT HAVE 45 <br />O, <br />NON -FUSED DISCONNECT <br />DEGREE BENDS OR GREATER. REF SPECIFICATIONS. <br />14. SEISMIC ZONE REQUIREMENTS: PROVIDE EXPANSION COUPLINGS <br />01 <br />FUSED DISCONNECT <br />AND BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY <br />LOCAL CODES. <br />SVATCHmIS <br />TRAVELERN�TRAL <br />CIRCUIT, CONCEALED IN WALLS OR <br />CEILING, E INDICATES EXISTING <br />15. EXISTING ELECTRICAL AND ALARM: <br />",ND <br />WIRING <br />CIRCUIT, CONCEALED IN FLOOR SLAB, <br />A. WHERE DEMOLITION OR NEW CONSTRUCTION INTERRUPTS <br />EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING"� <br />E INDICATES EXISTING WIRING <br />EQUIPMENT, DEVICES, OR LIGHTING TO REMAIN, BUT NOT <br />CIRCUIT, EXPOSED, <br />SHOWN ON DRAWINGS, PROVIDE LABOR AND MATERIALS TO <br />E INDICATES EXISTING WIRING <br />REWORK CIRCUITRY, AS REQUIRED, TO MAINTAIN EXISTING <br />OPERATION. <br />= <br />FLUSH MOUNTED PANELBOARD <br />B. IF DEMOLITION OR NEW CONSTRUCTION WILL DISRUPT <br />EXISTING UNDERGROUND SERVICES (ELECTRICAL, <br />SURFACE MOUNTED PANELBOARD <br />TELEPHONE, PARKING LOT LIGHTING CIRCUITRY, ETC.) <br />PROVIDE ALL MATERIALS AND LABOR AS REQUIRED TO <br />-/-d/- <br />VOICE/DATA, <br />REROUTE, SLEEVE, OR OTHERWISE REWORK THESE SERVICES <br />v <br />d = DATA ONLY, v = VOICE ONLY <br />TO MAINTAIN THEIR EXISTING OPERATION. <br />C. EXERCISE CAUTION AROUND ALARM AND SECURITY CABLES <br />Q <br />LOW VOLTAGE CABLE BOX FOR OTHER <br />DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM <br />AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO <br />® <br />VOICE/DATA, FLUSH FLOOR <br />THAT SYSTEMS REMAIN OPERATIONAL AT ALL TIMES. <br />D. DISPOSE OF ALL REMOVED MATERIALS, UNLESS OTHERWISE <br />MOTOR <br />NOTED. <br />16. EXISTING ELECTRICAL DEMOLITION: <br />0 <br />TELEPOWER POLE <br />A. GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL <br />EQUIPMENT CONDUIT, AND CONDUCTORS AS INDICATED ON <br />PUSH BUTTON <br />THE DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION. <br />REMOVE ALL PANELBOARDS, DISCONNECT SWITCHES, BOXES, <br />RELAYS, TIME SWITCHES, LIGHTS, DEVICES, ETC., WHICH <br />u <br />6 <br />BUZZER <br />WILL NOT BE REUSED. <br />B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT, <br />O <br />SMOKE DETECTOR <br />CONDUCTORS AND RELATED DEVICES SERVING SALES AREA <br />ENERGY MANAGEMENT <br />GONDOLAS BEING RELOCATED OR REMOVED. EXISTING <br />O <br />TEMPERATURE SENSOR <br />CONDUIT AND CONDUCTORS MAY BE REUSED FOR NEW <br />POWER DROPS WHERE SIZE, RATING, AND CONDITION MEET <br />O <br />THERMOSTAT <br />REQUIREMENTS INDICATED ON PLANS AND ALL U.L. <br />FIC1 <br />TIME CLOCK <br />RATINGS. REMOVE ALL UNUSED CONDUIT AND <br />CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER <br />FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS "SPARE". <br />PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT <br />ABBREVIATIONS <br />BREAKER IN THE "OFF" POSITION. <br />a, b, c LOWER CASE LETTERS INDICATE HD HAND DRYER <br />SWITCHING CONFIGURATION IG ISOLATED GROUND <br />C. CONDUIT AND WIRING TO BE ABANDONED IN CEILING <br />AFC ABOVE FINISH COUNTER IRC INTER -REGISTER <br />SPACES AND OTHER NON-PUBLIC AREAS (I.E., THROUGH <br />AFF ABOVE FINISH FLOOR COMMUNICATION <br />STOCKROOM AREA): CUT WIRING LOOSE AND REMOVE <br />AFG ABOVE FINISH GRADE ISP IN-STORE PROCESSOR <br />FROM RACEWAY(S), LEAVING RACEWAY(S) IN PLACE. <br />C CONDUIT LCU LIGHTING CONTROL UNIT <br />CONDUIT TO BE ABANDONED IN WALLS OR FLOORS SHALL <br />BE REMOVED BACK TO FINISHED SURFACE AND CAPPED <br />INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT. <br />CCT CIRCUIT K KEY OPERATED <br />CF CEILING/CIRCULATION FAN N NEUTRAL <br />D DATA NTS NOT TO SCALE <br />EC ELECTRICAL CONTRACTOR P WITH PILOT LIGHT <br />D. ALL CIRCUIT BREAKERS SERVING BRANCH CIRCUITS TO BE <br />EF EXHAUST FAN RH RADIANT HEATER <br />ABANDONED OR REMOVED SHALL REMAIN IN RESPECTIVE <br />EP EXPLOSION PROOF RC REFRIGERATION <br />PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE <br />ETR EXISTING TO REMAIN CONTRACTOR <br />ON DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK "SPARE" <br />EWC ELECTRIC WATER COOLER SC SECURITY CAMERA <br />CIRCUIT BREAKER IN THE "OFF" POSITION. <br />FUT FUTURE SF SUPPLY FAN <br />E. DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO <br />SELECTIVE SITE DEMOLITION SPECIFICATION FOR <br />GR GROUND TR TAMPER RESISTANTGFEP GROUND FAULT EQUIPMENT TYP TYPICAL <br />PROTECTION WH WATER HEATER <br />DISPOSAL OF LIGHT FIXTURE. <br />GFI GROUND FAULT CIRCUIT WP WEATHERPROOF <br />F. BUILDING COMPONENTS ABANDONED BY THE SCOPE OF <br />WORK SHALL BE SECURED TO PREVENT FALLING, <br />LOOSENING, OR CREATING DAMAGE OF ANY KIND IN THE <br />FUTURE. <br />INTERRUPTER WR WEATHER RESISTANT <br />GF GABLE FAN UH UNIT HEATER <br />LINO UNLESS NOTED <br />OTHERWISE <br />17. ETHERNET CABLE: <br />A. FURNISH AND INSTALL JUNCTION BOXES AS SHOWN ON <br />PLANS. PROVIDE CONDUIT AS REQUIRED BY LOCAL CODES <br />AND/OR ORDINANCES. <br />B. ETHERNET CABLE IS FURNISHED BY OTHERS. <br />C. ELECTRICAL CONTRACTOR SHALL INSTALL CABLE IN POWER <br />POLES. <br />D. ELECTRICAL CONTRACTOR SHALL INSTALL OTHER CABLE AS <br />DIRECTED BY WALMART CONSTRUCTION MANAGER. <br />0 <br />^-----------------------.1 <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />16.492 <br />CHECKOUTS <br />AND COOLERS <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />( <br />I <br />I <br />I <br />I <br />r <br />I <br />1 <br />EXISTING WALMART <br />CVTCDIf1D CIrA1 <br />01 30.14 EN02 <br />1 • TELEPOWER POLE(S): MOUNT JUNCTION BOX(ES) TO TOP <br />SIDE OF BOTTOM CHORD OF BAR JOIST. INSTALL <br />FURNISHED PRE -WIRED POWER POLE AND TERMINATE <br />PROVIDED FLEXIBLE CONDUIT AND WIRING TO JUNCTION <br />BOX. PROVIDE UNISTRUT SUPPORTS AND HARDWARE TO <br />SECURE TELEPOWER POLE PLUMB TO BUILDING <br />STRUCTURE. <br />2. PROVIDE LIQUID -TIGHT FLEXIBLE METAL CONDUIT AND <br />WIRING FROM DISCONNECT SWITCH OR JUNCTION BOX TO <br />EQUIPMENT KNOCKOUT OR ELECTRICAL CONNECTION <br />POINT. <br />3. WHERE EQUIPMENT NAMEPLATE PROTECTIVE DEVICE <br />RATING DIFFERS FROM SIZE PROVIDED, CHANGE OUT <br />BRANCH CIRCUIT WIRING AND OVERCURRENT DEVICE TO <br />APPROPRIATE RATING PER NEC. <br />4• ELECTRONIC FIRE PROTECTION/SECURITY ALARM BOXES <br />AND CONDUITS SHOWN ON POWER PLANS SHALL BE <br />PROVIDED UNDER THIS CONTRACT. IN ADDITION, UNLESS <br />NOTED OTHERWISE, THE FOLLOWING GENERAL NOTES <br />APPLY: <br />ALL ALARM JUNCTION BOXES SHALL BE <br />4"X4"X2-1 /8" MINIMUM. <br />B. ALARM RACEWAYS SHALL BE 3/4" MINIMUM WITH <br />PULL WIRE AND INSULATING BUSHINGS AT END OF <br />VERTICAL RACEWAY RUN. <br />C. VERTICAL RACEWAYS FROM ALARM BOXES SHALL BE <br />EITHER CONCEALED INSIDE WALL OR SURFACE <br />MOUNTED (TO MATCH JUNCTION BOX MOUNTING). ALL <br />VERTICAL RUNS SHALL BE TURNED 90-DEGREES AT <br />TOP SIDE OF BOTTOM CHORD OF BAR JOIST AND <br />EXTENDED HORIZONTALLY TO A LOCATION ACCESSIBLE <br />BY VERTICAL FLOOR TYPE LIFT. <br />5. UPON COMPLETION OF ELECTRICAL INSTALLATION AND <br />PRIOR TO ENERGIZING CIRCUIT: <br />A. INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE. <br />B. PERFORM CONTINUITY TEST. <br />C. VERIFY PROPER PHASING CONNECTION TO ALL THREE <br />PHASE MOTOR LOADS. <br />POWER DROP NOTES <br />1. POWER DROPS WILL BE IDENTIFIED BY AN IPTV TAG OR <br />POWER TAG, I.E. 44A, 46E, ETC. ALL CHECKOUT POWER <br />SHALL BE CONSIDERED POWER DROPS. <br />2. A REVISION OF THIS PLAN BASED ON THE FINAL <br />MERCHANDISE LAYOUT MAY BE ISSUED TO SHOW FINAL <br />LOCATIONS FOR THE POWER DROPS. IF THE MERCHANDISE <br />PLAN DOES NOT CHANGE, THIS PLAN WILL NOT BE <br />REISSUED. PROVIDE CIRCUITRY TO DISPLAY RACKS AS THE <br />RACKS ARE SET. IN ADDITION, THE FOLLOWING POWER <br />DROP NOTES APPLY: <br />A. THERE WILL BE NO ADDITIONAL CHARGE FOR DROP <br />RELOCATION WITHIN POWER DROP ZONES DEFINED ON <br />DRAWING. <br />B. AT CLOSE OF PROJECT THE GENERAL CONTRACTOR <br />AND CONSTRUCTION MANAGER SHALL REVIEW <br />ADDITIONAL OR DELETED POWER DROPS WITHIN EACH <br />ZONE TO VERIFY ANY ADDITIONAL CHARGES OR <br />CREDITS THAT APPLY DUE TO CHANGES. <br />C. ADDING OR SUBTRACTING A POWER DROP TO ANY <br />ZONE WILL RESULT IN A CHARGE OR CREDIT <br />ACCORDING TO SPECIAL CONDITIONS. <br />EN01 a <br />3. PROVIDE JUNCTION BOX AND CIRCUITRY TO NEAREST <br />JOIST ABOVE LOCATION SHOWN ON DRAWING. EXTEND <br />CONDUIT AND CIRCUITRY FROM JUNCTION BOX TO ENDCAP <br />OF DISPLAY RACK (AWAY FROM ACTION ALLEY). <br />4. PROVIDE CONDUIT, RECEPTACLE(S) AND FINAL <br />CONNECTIONS AT DISPLAY RACK SHELVING PER POWER <br />DROP SCHEDULE UNLESS NOTED OTHERWISE ON DRAWING. <br />VERIFY EXACT HEIGHT AND LOCATION OF RECEPTACLE(S) <br />WITH STORE PLANNING SET-UP SUPERVISOR PRIOR TO <br />INSTALLATION. <br />5. POWER DROPS FED FROM TRACK BUSWAY: <br />INSTALL PLUG-IN UNIT IF REQUIRED ON TRACK <br />BUSWAY AT POINT NEAREST TO POWER DROP(S) <br />NOTE: <br />RECEPTACLES, SWITCHES, DATA BOXES AND THEIR <br />CORRESPONDING COVER PLATES SHALL BE WHITE NYLON. <br />POWER DROP SCHEDULE <br />NO. I DESCRIPTION <br />PD2 MOUNT RECEPTACLE(S) ON BASE OF <br />DISPLAY UNIT(S) <br />PD3 PROVIDE DIRECT CONNECTION TO <br />EQUIPMENT <br />ALL WIRE SIZES SHOWN ON PANEL SCHEDULES ARE <br />INTENDED TO BE MINIMUM ACCEPTABLE WIRE SIZE. <br />THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE <br />WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT). <br />LENGTHS (IN FEET) ARE INTENDED TO BE MAXIMUM. <br />120 VOLT <br />#12 <br />#10 <br />#8 <br />#6 <br />1-5 AMPS <br />200 FT. <br />325 FT. <br />490 FT. <br />770 FT. <br />6-10 AMPS <br />100 FT. <br />160 FT. <br />245 FT. <br />385 FT. <br />11-15 AMPS <br />1 70 FT. <br />110 FT. <br />1 165 FT. <br />1 255 FT. <br />277 VOLT <br />#12 <br />#10 <br />#8 <br />#6 <br />1-5 AMPS <br />480 FT. <br />760 FT. <br />1170 FT. <br />1865 FT. <br />6-10 AMPS <br />240 FT, <br />380 FT. <br />585 FT. <br />930 FT. <br />11-15 AMPS <br />160 FT. <br />250 FT. <br />390 FT. <br />620 FT. <br />1lt01to <br />11.19.10 EN09 <br />ARRANGE ALL WORK THAT REQUIRES POWER INTERRUPTIONS <br />TO THE STORE TO BE ACCOMPLISHED AFTER NORMAL STORE <br />BUSINESS HOURS. NOTIFY THE STORE MANAGER AND THE <br />WALMART CONSTRUCTION MANAGER A MINIMUM OF 48 HOURS <br />IN ADVANCE OF ALL STORE POWER INTERRUPTIONS. STORE <br />MANAGER MUST ALLOW FOR POWERING DOWN OF COMPUTER <br />SYSTEMS, MOVING AFFECTED PRODUCT, MODIFICATION OF <br />WALMART AFTER-HOURS WORK SCHEDULES, COORDINATION <br />WITH OTHER TRADES, AND OTHER CRITICAL SCHEDULING <br />CONCERNS. PROVIDE TEMPORARY POWER AS REQUIRED. <br />INSTALLATION OF NEW EQUIPMENT SHALL BE COMPLETED AND <br />THE POWER SYSTEM TESTED AND RE -ENERGIZED PRIOR TO <br />START OF BUSINESS THE FOLLOWING MORNING NO LATER <br />THAN A TIME ESTABLISHED BY THE STORE MANAGER AND <br />THE WALMART CONSTRUCTION MANAGER. <br />16.125 <br />16.131 <br />��IAfa <br />16.411 <br />16.414 <br />16.470 <br />Eaq 16.902 <br />ELECTRICAL KEYNOTES <br />EXISTING LIGHT FIXTURES TO REMAIN UNLESS <br />NOTED OTHERWISE. <br />CONNECT TO EXISTING CIRCUIT. E.C. SHALL <br />VERIFY PRIOR TO ROUGH -IN THAT EXISTING <br />CIRCUIT HAS SPARE CAPACITY TO <br />ACCOMMODATE ADDITIONAL LOAD. <br />AUTOMATIC DOOR OPERATOR: VERIFY LOCATION <br />WITH MANUFACTURER'S RECOMMENDATIONS PRIOR <br />TO INSTALLATION. ALL CONDUIT AND WIRING <br />SHALL BE CONCEALED AT MAIN ENTRANCE DOORS. <br />PICKUP KIOSK: MOUNT JUNCTION BOX AT <br />STRUCTURE AND ROUTE 1-1/2" CONDUIT FROM <br />STRUCTURE TO KIOSK TERMINATION COMPARTMENT. <br />EXTEND CONDUCTORS IN 1 /2" FLEXIBLE METAL <br />CONDUIT ROUTED WITHIN THE 1-1/2" CONDUIT TO <br />MAINTAIN NEC REQUIRED SEPARATION OF POWER <br />AND DATA. COORDINATE LOCATION WITH KIOSK <br />INSTALLER PRIOR TO ROUGH -IN. <br />ORDER READY BOARD: MOUNT JUNCTION BOX <br />AT STRUCTURE. AFTER INSTALLATION OF DROP <br />POLE AND TV COMPONENT TRAY, EXTEND <br />CONDUCTORS IN 1/2" FLEXIBLE METAL CONDUIT <br />ROUTED WITHIN DROP POLE TO TV COMPARTMENT <br />TRAY TO MAINTAIN NEC REQUIRED SEPARATION <br />OF POWER AND DATA. PROVIDE 120V 20A DUPLEX <br />RECEPTACLE AND FINAL TERMINATION AT TV <br />COMPONENT TRAY. <br />FURNISH AND INSTALL NEW 20 AMP, 120 VOLT <br />CIRCUIT(S). FEED FROM PANELBOARD AS <br />INDICATED. PROVIDE 20A-1 P CIRCUIT BREAKER <br />IF NEEDED. E.C. SHALL MATCH MANUFACTURER, <br />TYPE AND AIC RATINGS OF EXISTING CIRCUIT <br />BREAKERS. E.C. SHALL VERIFY PRIOR TO <br />ROUGH -IN THAT EXISTING PANELBOARD HAS <br />SPARE CAPACITY TO ACCOMMODATE ADDITIONAL <br />LOAD. <br />E.C. SHALL COORDINATE WITH GENERAL <br />CONTRACTOR AND ARCHITECTURAL DEMOLITION <br />PLANS THE EXTENT OF ELECTRICAL DEMOLITION. <br />REMOVE CONDUITS AND WIRES ALL THE WAY BACK <br />TO ORIGINATING JUNCTION BOXES OR <br />PANELBOARDS. DEMOLITION SHALL NOT AFFECT <br />ACTIVE CIRCUITS. LABEL DEMOLISHED CIRCUITS) <br />IN PANELBOARDS AS "SPARE". COORDINATE EXACT <br />REQUIREMENTS WITH EXISTING CONDITIONS PRIOR <br />TO BID. <br />EXTERIOR SIGN POWER: WHERE ELECTRICAL <br />CONNECTIONS FOR SIGNAGE OCCUR BELOW ROOF <br />LINE, MOUNT JUNCTION BOX(ES) TO WALL AT <br />SIGN CONNECTION POINT AND PROVIDE 3/4" <br />CONDUIT TO CONTROL BOX FOR LOW VOLTAGE <br />WIRING (INSTALLED BY OTHERS). REFER TO <br />ARCHITECTURAL DRAWINGS FOR EXACT SIGN <br />LOCATIONS) PRIOR TO INSTALLATION. WHERE <br />ELECTRICAL CONNECTIONS FOR SIGNAGE OCCUR <br />ABOVE ROOF LINE, PROVIDE UNISTRUT TO MOUNT <br />JUNCTION BOXES TO BACK SIDE OF PARAPET AND <br />PROVIDE 3/4" CONDUIT TO CONTROL BOX FOR LOW <br />VOLTAGE WIRING (INSTALLED BY OTHERS). <br />PROVIDE ONLY ONE PENETRATION THROUGH THE <br />ROOF. REF ARCHITECTURAL EXTERIOR WALL <br />SECTIONS AND SIGN ATTACHMENT FOR ROOF AND <br />PARAPET PENETRATION REQUIREMENTS. <br />i- — — �, I I - n 1 ¢ : i .f �l .......c. f..f $.,.. �... r rn ly ,/.: �r. I ••,:.;i. r j -1 - 1 - <br />T� <br />E..T."�». <br />• <br />.. ...... . . . . <br />: <br />: <br />::. <br />I�•vx, x��F <br />Is f I 5 s 'ate I:�,..d�.:�::�r, :�se�is.-�<�i;�.<.tu.::�'::::�✓:!,� I I I I I I I I I I�.. � ^^ I�� s i '�€ <br />W.Fj <br />I+ H� 11 <br />e• � r <br />................ . . . . . . . <br />r <br />:� z 's i • .... i.....r::�vf�<,xra�iahes�?�✓��.�.... I I I I I I I I ( I I <br />KEY PLAN- <br />1/64"=l'-Olt <br />EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING <br />DRAWINGS AND MAY NOT REFLECT EXACT A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND <br />"AS -BUILT" CONDITIONS. CONTRACTOR SHALL FIELD SPECIFICATIONS IN THEIR RELATED FIELD. THE <br />VERIFY ALL EXISTING CONDITIONS PRIOR TO FAILURE TO ACQUAINT HIMSELF WITH THIS <br />SUBMITTING FINAL BIDS. CONTRACTOR SHALL KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY <br />CAREFULLY COORDINATE NEW WORK AND DEMOLITION OF PERFORMING HIS WORK PROPERLY. NO <br />WITH ALL OTHER DISCIPLINES AND EXISTING ADDITIONAL COMPENSATION SHALL BE ALLOWED <br />CONDITIONS. BECAUSE OF CONDITIONS THAT OCCUR DUE <br />TO FAILURE TO FAMILIARIZE WORKERS WITH THIS <br />KNOWLEDGE. <br />W C NI-ZW F-o<N <br />N 0W yOW� ON M2 <br />ZW~ UF� <br />Z � a < <br />� <a o�ooN=�<�W <br />�yZzacJaWicFio=o <br />Ii a- J aOFZ�� >WFI- <br />yc� Nnwa�Xv�w$�<r <br />Z <br />O30 �44ll �z �< <br />Zfa!! adow. F(n��0w zo <br />J� �I`�.RFrN2ycoi <br />a o <br />0 oo=QWo�WazWm <br />_ NWdZr9OWw00a,0>- <br />�Dkid o�iamzaawoax <br />*y <br />o <br />o <br />o <br />H� <br />O N <br />m <br />... <br />Wz <br />V1 N <br />CI V <br />N <br />QzaN <br />Z <br />W <br />c <br />P2 <br />W N <br />^OX <br />FQ <br />M <br />Z <br />r <br />V <br />0 <br />U <br />O 0 <br />� <br />O O <br />o <br />00 <br />a <br />-� <br />� <br />N <br />N <br />U <br />0 <br />CD <br />O <br />� <br />� O <br />0 <br />�i <br />LIJ <br />o <br />cat <br />O <br />o <br />0 <br />N <br />W <br />GQ <br />z <br />Oq <br />0 <br />ISSUE BLOCK <br />CHECKED BY: <br />HLW <br />DRAWN BY: <br />WN <br />PROTO: <br />LCC <br />PROTO CYCLE: <br />12/30/17 <br />DOCUMENT DATE: <br />02/16/17 <br />THIS ITEM HAS BEEN <br />ELECTRONICALLY SIGNED AND <br />SEALED BY VINCENT G. <br />MASIL€ONIS <br />ON THE DATE LISTED BELOW <br />USING A DIGITAL SIGNATURE. <br />PRINTED COPIES OF THIS <br />DOCUMENT ARE NOT <br />CONSIDERED SIGNED AND <br />SEALED AND THE SIGNATURE <br />MUST BE VERIFIER ON ANY <br />ELECTRONIC COPIES. <br />Feb 1.5 2017 <br />V►NCENT G. MASILIONIS <br />LICENSE # 68913 <br />Feb 15 2017 <br />POWER <br />PLAN <br />1 LIT SIGNAGE <br />