ELECTRICAL SCOPE OF WORK <br />-VERIFY EXISTING CONDITIONS. <br />-DISCONNECT EXISTING ATM. <br />-INSTALL NEW VAT SYSTEM HA1000-XLR WITH HEATER AND TWO-WAY <br />VIDEO UNIT. <br />-CONNECT CUSTOMER SIDE VAT TO CIRCUIT PREVIOUSLY USED <br />FOR ATM. <br />-IF EXISTING CIRCUIT IS GREATER THAN 20A, CHANGE OUT <br />BREAKER TO 1-POLE 20A CIRCUIT WITH MATCHING AIC RATING. <br />-REUSE DATA CONDUITS AS NEEDED. <br />-CONNECT TELLER SIDE CONNECTIONS PER DETAIL. <br />-UPDATE PANEL SCHEDULE OF MODIFIED PANEL. <br />KEYED NOTES: <br />Q DEMOLITION OF ATM: ATM TO BE REMOVED. COORDINATE DISCONNECTION OF POWER AND DATA WITH GC. DRESS AND LABEL CONDUITS AND <br />WIRES FOR REUSE. REFER TO ELECTRICAL PLAN ON THIS SHEET FOR ADDITIONAL INFORMATION. <br />j� AUDIO -VIDEO CABLES: PROVIDE 4"X4" J-BOX UNDER COUNTER IN OPERATOR KNEE SPACE FOR AUDIO/VIDEO CABLES. MAKE CONTINUOUS RUN <br />FROM VAT CUSTOMER UNIT. SEE DETAILS ON SHEET E-2.1 FOR ADDITIONAL INFORMATION. <br />QCAT5 INTERCONNECT: CONNECT CAT 5 CABLE FROM VAT OPERATOR UNIT TO 4X4 J-BOX IN OPERATOR KNEE SPACE. MAKE CONTINUOUS RUN <br />FROM VAT CUSTOMER UNIT. SEE DETAILS ON SHEET E-2.1 FOR ADDITIONAL INFORMATION. <br />OVAT UNIT: ROUTE CONDUIT AND WIRES AS REQUIRED FROM THE DEMOLITION TO NEW UNIT LOCATION. CONNECT VAT TO CIRCUIT INDICATED. <br />REFER TO PANEL SCHEDULE FOR WIRE SIZING. CONFIRM WIRE SIZES ARE ADEQUATE CIRCUIT BREAKER. <br />jD MONITOR: PROVIDE RECEPTACLE FOR MONITOR. CONNECT DATA FOR MONITOR FOR VAT UNIT. <br />DEMOLITION NOTES: <br />1. COORDINATION: DRAWINGS ARE TO BE USED ONLY AS A GUIDELINE FOR <br />DEMOLITION. COORDINATE ALL DEMOLITION WORK WITH OTHER TRADES, <br />WITH NEW WORK INDICATED ON CONSTRUCTION PLANS, AND WITH <br />ACTUAL FIELD CONDITIONS. <br />2. LOCKOUT/TAGOUT: VERIFY ALL SOURCES OF ELECTRICAL POWER TO <br />AREA OF WORK ARE DISCONNECTED AND LOCKOUT/TAGOUT <br />PROCEDURES ARE FOLLOWED PER OSHA REQUIREMENTS. <br />3. NOT IN CONTRACT AREAS: LOCATE, IDENTIFY, AND PROTECT ELECTRICAL <br />SERVICES (E.G. POWER, LIGHTING, CONTROL, COMMUNICATION, <br />SECURITY, SIGNAL, LIFE SAFETY, AND FIRE ALARM) PASSING THROUGH <br />DEMOLITION AREA AND SERVING OTHER AREAS OUTSIDE THE <br />RENOVATION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE <br />DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL <br />TEMPORARY SERVICE FOR AFFECTED AREAS. <br />4. CONTINUITY OF SERVICE: ANY CIRCUITS FEEDING THROUGH DEVICES OR <br />EQUIPMENT BEING REMOVED, RELOCATED, REWORKED, OR ABANDONED <br />AND SERVING OTHER ELECTRICAL DEVICES, AND/OR EQUIPMENT SHALL <br />BE MAINTAINED BY REWORKING EXISTING WIRING TO RESTORE <br />CONTINUITY OF THE INTERRUPTED CIRCUITS. <br />5. LIFE SAFETY: EXISTING EMERGENCY LIGHTING, EGRESS LIGHTING, AND <br />FIRE ALARM SYSTEM AND NOTIFICATION APPLIANCES SHALL BE <br />SALVAGED, MAINTAINED IN PROPER OPERATION, AND RECONFIGURED AS <br />REQUIRED TO COMPLY WITH APPLICABLE CODES AND STANDARDS FOR <br />EACH PHASE OF CONSTRUCTION. <br />6. CODE VIOLATIONS: NOTIFY ENGINEER UPON DISCOVERY OF ANY <br />EXISTING CODE VIOLATIONS FOR CORRECTIVE ACTIONS. <br />7. EXISTING CIRCUITRY: THE CONTRACTOR MAY REUSE EXISTING <br />CIRCUITRY AS FIELD CONDITIONS PERMIT AND WHERE DESIGN INTENT <br />CAN BE MET. EC SHALL VERIFY THAT TOTAL NEW LOAD DOES NOT <br />EXCEED 80% OF THE BREAKER CONTINUOUS CURRENT RATING. <br />8. COMPLETE REMOVAL: ELECTRICAL EQUIPMENT AND DEVICES SHALL BE <br />REMOVED COMPLETE INCLUDING CONDUIT, WIRE, HANGERS, AND <br />SUPPORTS BACK TO SOURCE. <br />9. PROTECTION BARRIERS: PROTECT ADJACENT MATERIALS INDICATED TO <br />REMAIN. INSTALL AND MAINTAIN DUST AND NOISE BARRIERS TO KEEP <br />DIRT, DUST, AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS. <br />REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION IS COMPLETE. <br />10. SALVAGE FOR REUSE: EXISTING EQUIPMENT NOTED TO REMAIN OR BE <br />RELOCATED SHALL BE SALVAGED, REPAIRED, AND CLEANED FOR FUTURE <br />USE. REPLACE MISSING HARDWARE OR DAMAGED EQUIPMENT AS <br />REQUIRED. <br />11. STORAGE: CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL, <br />PRESERVATION, STORAGE, AND PROTECTION OF ALL EQUIPMENT AND <br />DEVICES DESIGNATED TO BE REMOVED AND REINSTALLED. EQUIPMENT <br />SHALL BE STORED IN A MANNER TO AVOID DAMAGE UNTIL REINSTALLED. <br />12. OWNER RETENTION: THE CONTRACTOR SHALL REMOVE ALL EQUIPMENT <br />NOT INDICATED TO BE REUSED TO A DESIGNATED LOCATION AT THE <br />PROJECT SITE. AFTER THE EQUIPMENT HAS BEEN ASSEMBLED FOR THE <br />OWNER'S INSPECTION AND POSSIBLE RETENTION, ALL EQUIPMENT NOT <br />TO BE RETAINED BY THE OWNER SHALL BE REMOVED FROM THE SITE BY <br />THE CONTRACTOR. <br />13. PANELBOARD CIRCUIT DIRECTORY: ALL PANELBOARDS SHALL BE <br />FURNISHED WITH REVISED TYPEWRITTEN CIRCUIT DIRECTORY CARDS <br />WITH THE EQUIPMENT AND SPACE SERVED PROPERLY DESIGNATED. <br />EXISTING EQUIPMENT SHALL BE RE -IDENTIFIED AS REQUIRED TO <br />COORDINATE WITH PROPOSED DESIGN. <br />14. SPARED OUT CIRCUITS: BRANCH CIRCUIT BREAKERS MADE SPARE AS A <br />RESULT OF DEMOLITION ACTIVITIES SHALL BE SWITCHED TO THE 'OFF' <br />POSITION AND LABELED AS "SPARE". <br />15. RAISED CEILINGS: WHERE ARCHITECTURAL CEILINGS ARE TO BE RAISED, <br />THE EC SHALL REWORK EXISTING OVERHEAD CONDUIT AND <br />CONDUCTORS, IF ANY, TO ALLOW FOR THE CEILING TO BE RAISED. <br />16. HARD CEILINGS: WHERE NEW HARD CEILING IS TO BE INSTALLED, EC <br />SHALL REWORK AND RELOCATE ALL JUNCTION BOXES OUT FROM ABOVE <br />NEW HARD CEILING. NEW JUNCTION BOX LOCATIONS SHALL BE IN AN <br />ACCESSIBLE AREA ABOVE CEILING. <br />DEMOLITION / NEW WORK LEGEND: <br />DISCONNECT AND REMOVE/RELOCATE EXISTING DEVICES, FIXTURES, AND <br />EQUIPMENT TO ACCOMMODATE THE PROPOSED DESIGN INTENT. REFER TO THE <br />FULL SET OF DEMOLITION AND PROPOSED PLANS FROM ALL TRADES FOR <br />ADDITIONAL NOTES AND REQUIREMENTS. ALL DEVICES, FIXTURES, AND <br />EQUIPMENT SHOWN ON THE PROPOSED ELECTRICAL PLANS ARE NEW UNLESS <br />NOTED OTHERWISE WITH THE BELOW DESIGNATIONS. <br />(d) SUBSCRIPT DENOTES EXISTING TO BE REMOVED. DISCONNECT AND <br />REMOVE WIRE AND CONDUIT BACK TO SOURCE. MAINTAIN SERVICE TO <br />REMAINING DEVICES. <br />(e) SUBSCRIPT DENOTES EXISTING TO REMAIN. MAINTAIN SERVICE VIA <br />EXISTING CIRCUIT. <br />(n) SUBSCRIPT DENOTES NEW. <br />(r) SUBSCRIPT DENOTES EXISTING TO BE RELOCATED. MATCH EXISTING <br />WIRING AND CONDUIT AND EXTEND TO PROPOSED LOCATION. WIRING <br />DEVICES SHALL BE PROVIDED WITH NEW DEVICES AND COVER PLATES <br />TO MATCH NEW WORK. LIGHT FIXTURES SHALL BE CLEANED AND <br />RE-LAMPED. <br />(er) SUBSCRIPT DENOTES EXISTING DEVICE/FIXTURE TO BE REPLACED IN <br />SAME LOCATION AS EXISTING. DISCONNECT AND REMOVE EXISTING <br />DEVICE/FIXTURE AND MAINTAIN SERVICE VIA EXISTING CIRCUIT. <br />RECONNECT NEW DEVICE/FIXTURE TO EXISTING CIRCUIT. WIRING <br />DEVICES SHALL BE REPLACED WITH NEW DEVICES AND COVER PLATES <br />TO MATCH NEW WORK. LIGHT FIXTURES SHALL BE REPLACED WITH <br />NEW FIXTURES PER LIGHTING FIXTURE SCHEDULE. <br />— — — — DASHED LINES INDICATE EXISTING TO BE REMOVED, EXISTING TO BE <br />RELOCATED, OR EXISTING TO BE REPLACED ON DEMOLITION PLAN. <br />DARK LINES INDICATE NEW, EXISTING TO BE RELOCATED, OR EXISTING <br />TO BE REPLACED ON PROPOSED PLAN. <br />LIGHT LINES INDICATE EXISTING TO REMAIN. <br />GRAY SHADED AREAS INDICATE "NOT IN CONTRACT (N.I.C.)" AREAS. <br />MAINTAIN CONTINUITY OF EXISTING SERVICES. <br />N <br />o <br />N <br />O <br />2 <br />t0 <br />0 <br />(9 <br />z <br />U <br />a <br />z <br />z <br />v <br />aCK <br />N <br />� <br />o <br />A <br />W <br />j <br />� <br />a <br />0 <br />U- <br />w <br />7) <br />U) <br />0 <br />z <br />INFINITY ENGINEERING <br />GROUP, LLC <br />1208 East Kennedy Boulevard <br />Suite 230 <br />Tampa, Florida 33602 <br />[p]: 813.434.4770 <br />[ff']. 813.445.4211 <br />www.iegroup.net <br />EL Vert. of Autln. No. 27889 <br />IM <br />ANDREW MOHR, P.E. <br />FIL .9NQ- 753077 <br />MO <br />`G <br />s®,�SSj0v°rr , <br />d' <br />U0 <br />M <br />M <br />U) <br />LL <br />Z <br />O <br />J <br />J <br />J <br />o- <br />Q <br />= <br />N <br />U <br />� <br />OJO <br />U <br />NW <br />a. <br />Q <br />W <br />Q <br />N <br />o <br />J <br />W <br />a <br />co <br />00 <br />� <br />a) <br />c <br />z <br />v <br />F- <br />U <br />N <br />O <br />d <br />N <br />L <br />� <br />Project No. <br />Sheet <br />280-22.00 <br />E-1 1 <br />Date <br />AS NOTED <br />• <br />Scale <br />AS NOTED <br />