ELECTRICAL SCOPE OF WORK
<br />-VERIFY EXISTING CONDITIONS.
<br />-DISCONNECT EXISTING ATM.
<br />-INSTALL NEW VAT SYSTEM HA1000-XLR WITH HEATER AND TWO-WAY
<br />VIDEO UNIT.
<br />-CONNECT CUSTOMER SIDE VAT TO CIRCUIT PREVIOUSLY USED
<br />FOR ATM.
<br />-IF EXISTING CIRCUIT IS GREATER THAN 20A, CHANGE OUT
<br />BREAKER TO 1-POLE 20A CIRCUIT WITH MATCHING AIC RATING.
<br />-REUSE DATA CONDUITS AS NEEDED.
<br />-CONNECT TELLER SIDE CONNECTIONS PER DETAIL.
<br />-UPDATE PANEL SCHEDULE OF MODIFIED PANEL.
<br />KEYED NOTES:
<br />Q DEMOLITION OF ATM: ATM TO BE REMOVED. COORDINATE DISCONNECTION OF POWER AND DATA WITH GC. DRESS AND LABEL CONDUITS AND
<br />WIRES FOR REUSE. REFER TO ELECTRICAL PLAN ON THIS SHEET FOR ADDITIONAL INFORMATION.
<br />j� AUDIO -VIDEO CABLES: PROVIDE 4"X4" J-BOX UNDER COUNTER IN OPERATOR KNEE SPACE FOR AUDIO/VIDEO CABLES. MAKE CONTINUOUS RUN
<br />FROM VAT CUSTOMER UNIT. SEE DETAILS ON SHEET E-2.1 FOR ADDITIONAL INFORMATION.
<br />QCAT5 INTERCONNECT: CONNECT CAT 5 CABLE FROM VAT OPERATOR UNIT TO 4X4 J-BOX IN OPERATOR KNEE SPACE. MAKE CONTINUOUS RUN
<br />FROM VAT CUSTOMER UNIT. SEE DETAILS ON SHEET E-2.1 FOR ADDITIONAL INFORMATION.
<br />OVAT UNIT: ROUTE CONDUIT AND WIRES AS REQUIRED FROM THE DEMOLITION TO NEW UNIT LOCATION. CONNECT VAT TO CIRCUIT INDICATED.
<br />REFER TO PANEL SCHEDULE FOR WIRE SIZING. CONFIRM WIRE SIZES ARE ADEQUATE CIRCUIT BREAKER.
<br />jD MONITOR: PROVIDE RECEPTACLE FOR MONITOR. CONNECT DATA FOR MONITOR FOR VAT UNIT.
<br />DEMOLITION NOTES:
<br />1. COORDINATION: DRAWINGS ARE TO BE USED ONLY AS A GUIDELINE FOR
<br />DEMOLITION. COORDINATE ALL DEMOLITION WORK WITH OTHER TRADES,
<br />WITH NEW WORK INDICATED ON CONSTRUCTION PLANS, AND WITH
<br />ACTUAL FIELD CONDITIONS.
<br />2. LOCKOUT/TAGOUT: VERIFY ALL SOURCES OF ELECTRICAL POWER TO
<br />AREA OF WORK ARE DISCONNECTED AND LOCKOUT/TAGOUT
<br />PROCEDURES ARE FOLLOWED PER OSHA REQUIREMENTS.
<br />3. NOT IN CONTRACT AREAS: LOCATE, IDENTIFY, AND PROTECT ELECTRICAL
<br />SERVICES (E.G. POWER, LIGHTING, CONTROL, COMMUNICATION,
<br />SECURITY, SIGNAL, LIFE SAFETY, AND FIRE ALARM) PASSING THROUGH
<br />DEMOLITION AREA AND SERVING OTHER AREAS OUTSIDE THE
<br />RENOVATION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE
<br />DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL
<br />TEMPORARY SERVICE FOR AFFECTED AREAS.
<br />4. CONTINUITY OF SERVICE: ANY CIRCUITS FEEDING THROUGH DEVICES OR
<br />EQUIPMENT BEING REMOVED, RELOCATED, REWORKED, OR ABANDONED
<br />AND SERVING OTHER ELECTRICAL DEVICES, AND/OR EQUIPMENT SHALL
<br />BE MAINTAINED BY REWORKING EXISTING WIRING TO RESTORE
<br />CONTINUITY OF THE INTERRUPTED CIRCUITS.
<br />5. LIFE SAFETY: EXISTING EMERGENCY LIGHTING, EGRESS LIGHTING, AND
<br />FIRE ALARM SYSTEM AND NOTIFICATION APPLIANCES SHALL BE
<br />SALVAGED, MAINTAINED IN PROPER OPERATION, AND RECONFIGURED AS
<br />REQUIRED TO COMPLY WITH APPLICABLE CODES AND STANDARDS FOR
<br />EACH PHASE OF CONSTRUCTION.
<br />6. CODE VIOLATIONS: NOTIFY ENGINEER UPON DISCOVERY OF ANY
<br />EXISTING CODE VIOLATIONS FOR CORRECTIVE ACTIONS.
<br />7. EXISTING CIRCUITRY: THE CONTRACTOR MAY REUSE EXISTING
<br />CIRCUITRY AS FIELD CONDITIONS PERMIT AND WHERE DESIGN INTENT
<br />CAN BE MET. EC SHALL VERIFY THAT TOTAL NEW LOAD DOES NOT
<br />EXCEED 80% OF THE BREAKER CONTINUOUS CURRENT RATING.
<br />8. COMPLETE REMOVAL: ELECTRICAL EQUIPMENT AND DEVICES SHALL BE
<br />REMOVED COMPLETE INCLUDING CONDUIT, WIRE, HANGERS, AND
<br />SUPPORTS BACK TO SOURCE.
<br />9. PROTECTION BARRIERS: PROTECT ADJACENT MATERIALS INDICATED TO
<br />REMAIN. INSTALL AND MAINTAIN DUST AND NOISE BARRIERS TO KEEP
<br />DIRT, DUST, AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS.
<br />REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION IS COMPLETE.
<br />10. SALVAGE FOR REUSE: EXISTING EQUIPMENT NOTED TO REMAIN OR BE
<br />RELOCATED SHALL BE SALVAGED, REPAIRED, AND CLEANED FOR FUTURE
<br />USE. REPLACE MISSING HARDWARE OR DAMAGED EQUIPMENT AS
<br />REQUIRED.
<br />11. STORAGE: CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL,
<br />PRESERVATION, STORAGE, AND PROTECTION OF ALL EQUIPMENT AND
<br />DEVICES DESIGNATED TO BE REMOVED AND REINSTALLED. EQUIPMENT
<br />SHALL BE STORED IN A MANNER TO AVOID DAMAGE UNTIL REINSTALLED.
<br />12. OWNER RETENTION: THE CONTRACTOR SHALL REMOVE ALL EQUIPMENT
<br />NOT INDICATED TO BE REUSED TO A DESIGNATED LOCATION AT THE
<br />PROJECT SITE. AFTER THE EQUIPMENT HAS BEEN ASSEMBLED FOR THE
<br />OWNER'S INSPECTION AND POSSIBLE RETENTION, ALL EQUIPMENT NOT
<br />TO BE RETAINED BY THE OWNER SHALL BE REMOVED FROM THE SITE BY
<br />THE CONTRACTOR.
<br />13. PANELBOARD CIRCUIT DIRECTORY: ALL PANELBOARDS SHALL BE
<br />FURNISHED WITH REVISED TYPEWRITTEN CIRCUIT DIRECTORY CARDS
<br />WITH THE EQUIPMENT AND SPACE SERVED PROPERLY DESIGNATED.
<br />EXISTING EQUIPMENT SHALL BE RE -IDENTIFIED AS REQUIRED TO
<br />COORDINATE WITH PROPOSED DESIGN.
<br />14. SPARED OUT CIRCUITS: BRANCH CIRCUIT BREAKERS MADE SPARE AS A
<br />RESULT OF DEMOLITION ACTIVITIES SHALL BE SWITCHED TO THE 'OFF'
<br />POSITION AND LABELED AS "SPARE".
<br />15. RAISED CEILINGS: WHERE ARCHITECTURAL CEILINGS ARE TO BE RAISED,
<br />THE EC SHALL REWORK EXISTING OVERHEAD CONDUIT AND
<br />CONDUCTORS, IF ANY, TO ALLOW FOR THE CEILING TO BE RAISED.
<br />16. HARD CEILINGS: WHERE NEW HARD CEILING IS TO BE INSTALLED, EC
<br />SHALL REWORK AND RELOCATE ALL JUNCTION BOXES OUT FROM ABOVE
<br />NEW HARD CEILING. NEW JUNCTION BOX LOCATIONS SHALL BE IN AN
<br />ACCESSIBLE AREA ABOVE CEILING.
<br />DEMOLITION / NEW WORK LEGEND:
<br />DISCONNECT AND REMOVE/RELOCATE EXISTING DEVICES, FIXTURES, AND
<br />EQUIPMENT TO ACCOMMODATE THE PROPOSED DESIGN INTENT. REFER TO THE
<br />FULL SET OF DEMOLITION AND PROPOSED PLANS FROM ALL TRADES FOR
<br />ADDITIONAL NOTES AND REQUIREMENTS. ALL DEVICES, FIXTURES, AND
<br />EQUIPMENT SHOWN ON THE PROPOSED ELECTRICAL PLANS ARE NEW UNLESS
<br />NOTED OTHERWISE WITH THE BELOW DESIGNATIONS.
<br />(d) SUBSCRIPT DENOTES EXISTING TO BE REMOVED. DISCONNECT AND
<br />REMOVE WIRE AND CONDUIT BACK TO SOURCE. MAINTAIN SERVICE TO
<br />REMAINING DEVICES.
<br />(e) SUBSCRIPT DENOTES EXISTING TO REMAIN. MAINTAIN SERVICE VIA
<br />EXISTING CIRCUIT.
<br />(n) SUBSCRIPT DENOTES NEW.
<br />(r) SUBSCRIPT DENOTES EXISTING TO BE RELOCATED. MATCH EXISTING
<br />WIRING AND CONDUIT AND EXTEND TO PROPOSED LOCATION. WIRING
<br />DEVICES SHALL BE PROVIDED WITH NEW DEVICES AND COVER PLATES
<br />TO MATCH NEW WORK. LIGHT FIXTURES SHALL BE CLEANED AND
<br />RE-LAMPED.
<br />(er) SUBSCRIPT DENOTES EXISTING DEVICE/FIXTURE TO BE REPLACED IN
<br />SAME LOCATION AS EXISTING. DISCONNECT AND REMOVE EXISTING
<br />DEVICE/FIXTURE AND MAINTAIN SERVICE VIA EXISTING CIRCUIT.
<br />RECONNECT NEW DEVICE/FIXTURE TO EXISTING CIRCUIT. WIRING
<br />DEVICES SHALL BE REPLACED WITH NEW DEVICES AND COVER PLATES
<br />TO MATCH NEW WORK. LIGHT FIXTURES SHALL BE REPLACED WITH
<br />NEW FIXTURES PER LIGHTING FIXTURE SCHEDULE.
<br />— — — — DASHED LINES INDICATE EXISTING TO BE REMOVED, EXISTING TO BE
<br />RELOCATED, OR EXISTING TO BE REPLACED ON DEMOLITION PLAN.
<br />DARK LINES INDICATE NEW, EXISTING TO BE RELOCATED, OR EXISTING
<br />TO BE REPLACED ON PROPOSED PLAN.
<br />LIGHT LINES INDICATE EXISTING TO REMAIN.
<br />GRAY SHADED AREAS INDICATE "NOT IN CONTRACT (N.I.C.)" AREAS.
<br />MAINTAIN CONTINUITY OF EXISTING SERVICES.
<br />N
<br />o
<br />N
<br />O
<br />2
<br />t0
<br />0
<br />(9
<br />z
<br />U
<br />a
<br />z
<br />z
<br />v
<br />aCK
<br />N
<br />�
<br />o
<br />A
<br />W
<br />j
<br />�
<br />a
<br />0
<br />U-
<br />w
<br />7)
<br />U)
<br />0
<br />z
<br />INFINITY ENGINEERING
<br />GROUP, LLC
<br />1208 East Kennedy Boulevard
<br />Suite 230
<br />Tampa, Florida 33602
<br />[p]: 813.434.4770
<br />[ff']. 813.445.4211
<br />www.iegroup.net
<br />EL Vert. of Autln. No. 27889
<br />IM
<br />ANDREW MOHR, P.E.
<br />FIL .9NQ- 753077
<br />MO
<br />`G
<br />s®,�SSj0v°rr ,
<br />d'
<br />U0
<br />M
<br />M
<br />U)
<br />LL
<br />Z
<br />O
<br />J
<br />J
<br />J
<br />o-
<br />Q
<br />=
<br />N
<br />U
<br />�
<br />OJO
<br />U
<br />NW
<br />a.
<br />Q
<br />W
<br />Q
<br />N
<br />o
<br />J
<br />W
<br />a
<br />co
<br />00
<br />�
<br />a)
<br />c
<br />z
<br />v
<br />F-
<br />U
<br />N
<br />O
<br />d
<br />N
<br />L
<br />�
<br />Project No.
<br />Sheet
<br />280-22.00
<br />E-1 1
<br />Date
<br />AS NOTED
<br />•
<br />Scale
<br />AS NOTED
<br />
|