ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />F�F <br />DUPLEX CONVENIENCE OUTLET <br />L z±�,. <br />F451-- <br />DUPLEX OUTLET ABOVE COUNTER <br />I <br />FE5,-W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />1_� <br />r'Z7'G . F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />d, . <br />FOUR-WAY SWITCH <br />_�>4 <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />�_o <br />WALL MOUNTED LIGHT FIXTURE <br />RECESSED LIGHT FIXTURE <br />+P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUSTFAN <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />FC H] <br />CHIMES (OPTIONAL) <br />�H <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SMOKE DETECTOR <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />1TV1 <br />TELEVISION (OPTIONAL) <br />FTV] 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />THERMOSTAT <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />_Z/ <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />OPT. CEILING FAN <br />GD <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />3" VTR JIL <br />JIL <br />OPT. <br />L LAV LAV <br />IHANSON <br />OX <br />BOX I <br />3 <br />W/C <br />LAV SHOWER <br />TUB/ <br />WIC SHOWER <br />STUDOR DBL SINK <br />VENTt Lj W1 DISP. <br />LAV I <br />W/C <br />PLUMBING RISER, <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS- <br />UNIT-C 1624 (1624) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1625 S.F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />1 5200 <br />TOTAL: 31878 <br />LOAD WATTS --- 240 VOLTS <br />r AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />M IN <br />1 � P Serial Cable <br />NEMA <br />L 3 <br />Power Co. Feed #4 Solid COPPER Ground <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 J518" Galvanized Drivoe'n Gruund' <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />C.O. <br />DB & GFI TO - <br />BE ALIGNED, <br />VERTICALLY <br />0 <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />DISCONNECT <br />1ST ELECTRICAL - UNIT-C 1624 <br />SCALE: X"=T-O" <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE <br />RANGE HOOD PER <br />— SPECS <br />F_ <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />-7 <br />2ND ELECTRICAL - UNIT-C 1624 <br />SCALE: Y4"=1'-0" <br />> 0 <br />0 <br />C%j <br />C= <br />CCL co X <br />M LL <br />'D C3 <br />C4 <br />co C) M <br />C: <br />W (D <br />0-s— C <br />. <br />. ..... ... E <br />0 <br />0 a) <br />C: <br />0— <br />> 0__Q <br />�E <br />��o 0 <br />Q.— <br />> <br />co <br />> <br />21- <br />0 4�; <br />71, <br />To the beat of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition, Engineers signature and seal is only <br />for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal, <br />W <br />E co 00 <br />0 8 C', <br />C:, C OD <br />0 <br />C: <br />al U <br />LL a- <br />c-, b, <br />c: , <br />Co LL U_ 'L'U 1.0 <br />13 <br />0 <br />_j W 0 <br />Z <br />of <br />:� 2 <br />1% <br />12 8) 0 <br />-Z % (� X c, _1 <br />W <br />W <br />0, 2 Y' 1� 'M < <br />U) <gr <br />Z <br />IL <br />IL <br />Ci <br />cc Z <br />LO <br />< < <br />0 C) 0 (D <br />No= W <br />13 11 E] <br />00 ID <br />N <br />< <br />W V) <br />W <br />(1) <br />(D <br />4--J <br />(0 <br />LLJ g <br />.Ei <br />0 <br />04 <br />L=,j <br />Rig <br />E <br />40; 0 <br />< 0 <br />C" <br />Z <br />< <br />M <br />__j <br />U_ <br />E <br />E <br />z <br />Z <br />E 8 <br />ca <br />0 <br />< <br />00 <br />0< <br />E <br />C14 M <br />C(D:) t <br />�z <br />< <br />�O <br />W, <br />0 <br />.0 <br />0, <br />Z <br />Z <br />C: <br />Z <br />C0 <br />0) <br />0 <br />'0 <br />0 <br />< <br />Z <br />LU <br />211- <br />0 <br />> C.0 <br />C%4 <br />L0 <br />C=) <br />C 4 <br />M <br />Co <br />":T <br />L0 <br />CN <br />60 <br />0 <br />U) <br />Q0 <br />0 <br />r— <br />N <br />LO <br />=3 <br />LO <br />04 <br />C) <br />LA-) <br />c6 <br />c) <br />E <br />CD <br />04 <br />0 <br />Z <br />Z <br />E T_ <br />(n <br />a) <br />0- <br />E <br />0 ;.j <br />0 <br />0 _j <br />�v <br />:� 0 1 <br />_j <br />JOB <br />NO: 21-01148-01143 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />11.2 <br />