Laserfiche WebLink
GENERAL INSTALLATION NOTES <br />1. Provide full mortar head and bed joints. <br />2. Shore filled lintels as required. <br />3. Installation of lintel must comply with the architectural and/or structural drawings. <br />4. U-Lintels are manufactured with 5-1/2" long notches at the ends to accommodate <br />vertical cell reinforcing and grouting. <br />5. All lintels meet or exceed U360 vertical deflection, except lintels 17'-4" and <br />longer with a nominal height of 8" meet or exceed U180. <br />6. Bottom field added rebar to be located at the bottom of the lintel cavity. <br />7. 7/32" diameter wire stirrups are welded to the bottom steel for mechanical anchorage. <br />8. Cast -in -place concrete may be provided in composite lintel in lieu of concrete <br />masonry units. <br />9. Safe load ratings based on rational design analysis per ACI 318 and ACI 530 <br />10. Product Approvals: Miami Dade County, Florida Nos.20-0630.16 and 20-0630.15. <br />11. The exterior surface of lintels installed in exterior concrete masonry walls shall have <br />a coating of stucco applied in accordance with ASTM C-926 or other approved <br />coating. <br />12. Lintels loaded simultaneously with verttcal (gravity and uplift) and horizontal (lateral) <br />loads shoud be checked for combine loading with the following equation: <br />Applied vertical load + Applied horizontal load G 1 .0 <br />a e vertical load Safe horizontal load - <br />GENERAL CONCRETE LINTEL SCHEDULE <br />APPROVED LINTEL MANUFACTURERS: CASTE-CRETE, QUALITY, LOTTS <br />817441B/1T8F40 113/1T 8RF400B/1T 8F321B/1T <br />FORM dr GROUT SOLID <br />W <br />p �' •:s• N <br />� J <br />O I 15 BAR CONT. <br />8F12-1 B/1T <br />V' LINTEL DETAIL <br />SCALE = N.T.S. <br />MI <br />MIN <br />ON <br />00 <br />M <br />=I <br />slow <br />No <br />F = FILLED WITH <br />GROUT / U = UNFILLED <br />R = RECESSED <br />QTY. OF #5 <br />REBAR @ BOTTOM <br />OF LINTEL CAVITY <br />a <br />8F 16- <br />B/1 T <br />¢ <br />00 <br />tNOMINAL. <br />QUANTITY OF <br />WIDTH <br />#5 REBAR AT <br />TOP <br />NOMINAL - <br />HEIGHT <br />MATERIALS <br />cTf pr�Tntels = 3500 psi. <br />2. fc prestressed lintels = 6000 psi. <br />3. grouted per ASTM C476 fg = 3000 psi w/ <br />4. maximum 318" aggregate and 8" to 11" slump. <br />5. Concrete masonry units (CMU) per ASTM C90 w/ <br />minimum net area compressive strength = 1900 psi. <br />6. Reber per ASTM A615 Grade 60. <br />Prestressing strand per ASTM A416 grade <br />7. 270 low relaxation. <br />7/32 wire per ASTM A510. <br />8. Mortar per ASTM C270 type M or S. <br />#5 REBAR <br />MIN. <br />(1) REQ'D <br />CLEAR <br />ALTERNATE POWERS <br />STEEL LINTEL <br />d ° <br />a <br />° <br />A ° <br />.M.U. <br />#5 REBAR AT TOP <br />°° ° <br />a <br />GROUT <br />MIN. (1) REQ'D <br />1-1/2" CLEAR <br />0 <br />a ° <br />n <br />e <br />° <br />5REBAR AT <br />=how <br />a <br />BOTTOM OF <br />w w <br />ul, <br />LINTEL CAVITY <br />V po to <br />OTTOM <br />t] tr �j X Lu <br />�-- <br />REINFORCING <br />PROVIDED IN <br />LINTEL <br />¢ ¢ Ci <br />Z LL Ci w ^n <br />¢ •' Q allo <br />0', <br />5 REBAR AT BOTTC <br />7-5/8"ACTUAL <br />'NOMINAL WIDTH <br />(VARIES) <br />to � a <br />AS INDICATED <br />LINTEL MINIMUM DEPTHS ARE CALLED OUT ON LINTEL PLAN. IF CONTRACTOR INSTALLS A DEEPER <br />LINTEL THAN INDICATED ON THE PLAN, DOING THIS INCREASES THE STRENGTH OF THE LINTEL AND IS <br />APPROVED WITHOUT ENGINEERING LETTER. IF A SMALLER LINTEL IS INSTALLED CONTACT E.O.R. FOR <br />APPROVAL. (SEE LINTEL PLAN FOR SCHEDULE) <br />16 GAUGE POWERS <br />STEEL BOXED LINTEL <br />POWERS STEEL BOXED LINTEL NOTES (ALT.) <br />ONLY IF NOTED ON LINTEL PLAN <br />1. Refer to manufacturers specifications for installation. <br />2. Contractor to provide proper protection of lintel to prevent rusting <br />Refer to manufacturers specifications. <br />3. If lintel is scratched or damaged refer to Powers Steel for repair. <br />4. Lintel depth to match precast depth. One #5 Bar required at top <br />see lintel plan/details for bottom steel required. <br />5. A bonding agent must be applied to the Steel Box lintels prior to <br />applying the cementibuos coating. See contractor specifications <br />LINTEL PLAN NOTES: <br />1. THIS PLAN IS TO BE USED FOR STRUCTURAL <br />INFORMATION ONLY. <br />2. UNLESS NOTED OTHERWISE ALL LINTEL DEPTHS ARE <br />TO BE ASSUMED TO BE 16" MINIMUM DEPTH. <br />3. THE NUMBER OF COURSES OF MASONRY REQUIRED <br />BETWEEN THE LINTEL & THE BOND BEAM SHOULD BE <br />COORDINATED WITH THE ELEVATION DRAWINGS <br />4. THE CONTRACTOR IS RESPONSIBLE FOR <br />COORDINATING THE PROPER LINTEL HEIGHT. <br />5. LINTELS AT GARAGE DOOR OPENING ARE MINIMUM <br />DEPTH REQUIRED FOR THE DESIGN LOADS. THE <br />DEPTH MAY BE INCREASED IF REQUIRED FOR <br />PROPER LINTEL HEIGHT,G.C. COORDINATE. <br />POWER STEEL LINTEL IS AN ADEQUATE <br />SUBSTITUTION @ ALL LOCATIONS UNLESS <br />NOTED OTHERWISE AT OPENING LOCATION <br />2x8 #2 SYP STUDS @ 8" O.C. W/ (2) USP OR <br />SIMPSON MSTAM36 STRAPS EACH STUD ((1) <br />STRAPS EACH SIDE) CENTERED W/ (13) 10d <br />NAILS & (8) Y4"x1 J" TAPCONS OR TITENS <br />-CENTER OF STRAP @ T/WALL TYP. U.N.O. <br />2x8 #2 SYP P.T. BASE PLATE <br />W/ Y2" EPDXY ANCHOR OR Y2" <br />J BOLT W/ MIN. 7" EMBEDMENT @ <br />32" O.C. & 6" FROM EACH END <br />STRUCTURAL SHEATHING <br />ATTACHED PER NAILING <br />SCHEDULE <br />SEE PLAN <br />"T/VVALL <br />8" KNOCKOUT COURSE <br />W/ (1) #5 CONT. <br />SEE PLAN FOR FILLED CELL <br />SPACING <br />1 WALL SPLICE DETAIL <br />REVISED: 11/04/19 SCALE: 1" = V-0" <br />O O <br />5-10" LL 13'-0" LL <br />O <br />8'-0" LL <br />O <br />4'-6" LL <br />C <br />4'-6" LL <br />MIN.B <br />5'-8" LL <br />MIN. E <br />17'-4" LL <br />LINTEL PLAN - ELEV-B <br />SCALE: X"=V-O" <br />N <br />N <br />.r_` <br />� -o <br />o <br />owc <br />� C..,�� <br />N <br />co2 N = <br />Q N r0 <br />co <br />dazry <br />C <br />W Cz -C <br />u '- Q <br />3 to <br />n .as d a` <br />o 0 <br />cc <br />.2 <br />a .a <br />a E <br />a� <br />`' <br />4 thy+ R-' <br />. • .. • .. <br />�1 <br />•..��\\ �'I Y <br />IL <br />s f.o <br />3SIOv <br />111111111111100 <br />To the best of the ngineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential <br />7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers <br />signature and seal. <br />0) <br />W <br />a <br />c E <br />0 <br />8 <br />c <br />(5 c: N r <br />to <br />wV <br />M 0 <br />=� <br />a <br />LL W LL LL <br />a- <br />J <br />_ <br />0 <br />11 <br />w <br />-va, a Y <br />aa BA <br />t p SO <br />O � <br />Wo°'°' <br />Z <br />m <br />U) Cl)N Z Q J <br />/n <br />V= <br />N <br />OU <br />W <br />El ❑ <br />U R <br />Z <br />v <br />J <br />tl � <br />N <br />z v <br />CD � <br />u' <br />(6 <br />N <br />w <br />U <br />O <br />w $ <br />In <br />is y <br />�V) <br />®® <br />U <br />w <br />�- E <br />t � <br />U A <br />Q <br />w <br />M <br />M <br />� <br />o <br />Z <br />¢ <br />U <br />@ E <br />=o <br />gO <br />>� <br />a n <br />Q <br />tz <br />E U <br />oLL <br />z <br />=® <br />oa <br />H t6 <br />E <br />A <br />00 <br />oZ <br />Zo <br />CO (� <br />�- <br />< Z <br />w z <br />7 <br />C: <br />,= <br />q om <br />o� <br />W f <br />s� <br />Z <br />z <br />my <br />Nm<w <br />�z <br />8 <br />O f <br />0 <br />, U <br />"� <br />a <br />u�w <br />W <br />a <br />M <br />W <br />M_ <br />>� <br />o <br />w� <br />_< <br />°1 <br />�� <br />'M <br />J <br />O <br />a; <br />to <br />c9 <br />^, <br />T <br />L <br />CV <br />(o � <br />T <br />T <br />CL-° <br />LO <br />a) <br />CMV <br />Lo <br />N <br />�' <br />r <br />Q <br />to <br />t0 LC) <br />EM <br />m <br />T <br />w to <br />o <br />Z <br />Z <br />E CV <br />4 <br />cc <br />o <br />C <br />JOB <br />NO : <br />23-06123 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />7 <br />