ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11.In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FqT <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />�R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />�-O <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />�D <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />FT�V2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />L J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />r J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />150A/200A INDOOR <br />PANEL CENTER <br />00 #14 to lights & outlets <br />NEMA 1 <br />0 #12 to appliances and GFI <br />150 AMP/ <br />200 AMP <br />0 #10 to WH <br />01 #8 to Range <br />01 #6 to HVAC <br />79T <br />MAIN <br />0 <br />200 amp <br />150 amp <br />UNDERGROUND IDis <br />SERVICE BY POWER CO.---, <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />150=2/0 <br />200=4/0 in 2" Conduit <br />Bare Cu Ground <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />DEDICATED ' <br />RECEPTACLE FOR <br />MICROWAVE RANC <br />HOOD PER SPECS <br />1.5" VTR III 3" VTR <br />ICI \I` <br />I <br />I I <br />I I <br />I <br />I <br />� \I <br />\\_ 1113 VTR <br />PLUMBING RISER_ <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />LI <br />SWITCH FOR <br />DISPOSAL <br />DWI j <br />� 1 1 <br />\ I <br />:,KITCHEN <br />SPEC 3 & 4 KITCHEN <br />SCALE: %4'=1'-0" <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS <br />Cr <br />w W <br />H p <br />w Z J <br />�05 <br />m <br />IYUF=- <br />> O <br />A/C PAD <br />DISC. WP <br />GFI <br />A <br />NOOK <br />31-41 t. 3'-4" <br />I <br />TO LIGHTS <br />AND <br />SWITCH <br />ABOVE <br />G�II <br />6WN. <br />LANAI <br />ROUGH -IN FOR I <br />OPT. CLG. FAN/' <br />LIGHT PRE -WIRE <br />— , / <br />SWITCH OR <br />DISPOSAL 1 <br />FAMILY <br />L _ I <br />GFI <br />ITCHEN\ <br />I <br />REF <br />-31 I <br />PENDANT ROUGH -IN FOR I <br />AS PER OPT. CLG. FAN/ <br />SPECS LIGHT PRE -WIRE ' <br />/) <br />G � � <br />I / <br />l � � <br />n I / <br />DINING <br />PENDANT AS <br />PER SPECS <br />' <br />C.M. <br />I I <br />PWDR <br />—­� //1 <br />1'1'I'1'IT I'I'I'I'I'1'I'I'I'1'I'I'I <br />GFI @ 44" kWGFI @ 44" <br />7WH)A.F.F. A.F.F. <br />W.H. <br />1 <br />I <br />Z w----__� GARAGE <br />I t <br />v <br />O v L----- = GARAGE <br />>-.. (r LIGHT AS <br />LL v PER SPECS <br />w <br />>w <br />------------------OOP---------------j <br />GFI I <br />\—IRRIGATION I <br />GFI @ 44" <br />A.F.F. <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />FOYER <br />DB • \ <br />\ I <br />I \ <br />I <br />ENTRY <br />Fl \4—D13 & GFI TO <br />------- I BE ALIGNED <br />VERTICALLY <br />I <br />I <br />COACH LIGHTS /COACH LIGHTS <br />OR PREWIRE AS / OR PREWIRE AS <br />PER SPECS / PER SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I I <br />I I I <br />I I I <br />I I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />L--------------------------------------J <br />SECOND FLOOR ELECTRICAL PLAN <br />FIRST FLOOR ELECTRICAL PLAN — ELEV—B <br />ELEV—B <br />S <br />Z <br />_o <br />.r <br />c W <br />i <br />�O 4CM <br />wN <br />G ex. <br />y <br />Q � N <br />a aj <br />�CZ = e <br />3 3 rc <br />•°' cu c` <br />c <br />d <br />� CZ <br />cc <br />H Z <br />d U <br />CM <br />CN <br />0 <br />fV <br />M <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential <br />7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's <br />signature and seal. <br />sn <br />Ir <br />a <br />OE Sa <br />m r <br />04 N co N ft <br />Q <br />ao °� '`J "- <br />d% <br />W <br />yr20u, r LL W <br />0 a d <br />a <br />r0n <br />MLLLL a 0 Z <br />13 Z <br />z <br />mca 00� <br />L (6 O 0 � <br />O <br />N (O m J Q <br />W <br />�2"� J 0 Z <br />Z <br />L IL <br />w <br />CoLr) N Z 2 <br />M <br />(V U U) F- <br />O U ❑�❑ <br />Z <br />W <br />— C <br />Z oo <br />z o <br />Q V <br />J - <br />� <br />d � <br />Z a <br />- <br />(� <br />w <br />� <br />U <br />O <br />o <br />w <br />N <br />fa <br />r— <br />U <br />w A <br />�� <br />J E <br />L <br />U <br />U3 o <br />Q <br />• <br />�Q <br />N CA <br />I� <br />ti <br />o <br />cn <br />J <br />w <br />M <br />(") <br />U- <br />w i <br />O <br />Z <br />Z <br />Q <br />0 <br />y <br />ii <br />E V <br />wo <br />zo <br />oa <br />I� r0o <br />U <br />UO <br />O'U <br />o2 <br />Z <br />I,�� <br />`� <br />o <br /><o <br /><0 <br />ffZ <br />.w <br />C <br />o <br />U <br />mE <br />Y <br />Z <br />Z <br />m°� <br />J <br />m<w <br />8 <br />r <br />oa <br />z <br />gz <br />o <br />W <br />w <br />>0 <br />a <br />W <br />m <br />o <br />w ¢ <br />L O <br />d � <br />M <br />v <br />O0 <br />ila <br />3 <br />> cM <br />O <br />m <br />i <br />T <br />N <br />(U Lo <br />T <br />r <br />� a <br />co <br />N <br />a. <br />U') <br />m <br />O <br />_ <br />O <br />M <br />N N <br />T <br />N <br />Q <br />LO <br />T <br />M M <br />0 <br />z <br />E <br />yLO <br />Z <br />E N <br />c <br />(aE <br />d <br />U <br />y <br />Q Co <br />JOB <br />NO: <br />23-06123 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />