HVAC NOTES <br />1. All equipment is new, air handlers located on steel channell, supported from deck above with concrete deck anchors. <br />Bottom of plenum box of return held 2" off bottom of stand with emergency condensate drain pan extending out 3" on all <br />four sides with emergency overflow shut down switch on condensate overflow mounted on emergency pan. <br />2. rectangular ductwork to be 1.5" fiberous duetboard, Joints to be sealed with pressure sensitive "UL" 181 silver tape and <br />staples as recommended by manufacuterer. Round ductwork to be R-6 flex duct using silver tape, "UV 181 and nylon panduit <br />straps at Crown dampened collar. <br />3. All duct sizes are clear inside dimensions, allow for 1.5" R-6 fiberglass ductwork. <br />4. Rectangular ductwork to be hung with 2" u-channel & minimum 12-gauge wire on 6' centers and flex duct to be hung with 2" <br />metal strap on 5' centers and at elbow down to air distribution as needed. All duct materials and installation of same to comply <br />with section 503 of Florida Energy code for Building Construction effective March 1, 2002, <br />5. Smoke detectors shall be installed in return duct to shut down system, located prior to introduction of ventilation outside air. <br />6. Coordinate location of air distribution with ceiling grid and lights. <br />7. Contractor test and balance of systems to within 10% of design airflows shown and submit air balance report and equipment <br />performance to owner upon completion. <br />g. Thermostats to be mounted at 52" AFF. <br />4 TON, 13 SEER (MIN.) <br />7.8 HSPF (MIN.) CONDENSER <br />TYPICAL C SLAB <br />SLAB TO BE 4" <br />WIDER THEN THE <br />UNIT. <br />4 TON, 13 SEER (MIN.) <br />7.8 HSPF (MIN.) CONDENSER <br />TYPICAL A& SLAB <br />SLAB TO BE 4" <br />WIDER THEN THE <br />UNIT. <br />V '" 'tt►ettaar►rae <br />s Z/�, • •�i E N •", "7" i <br />�+ No.42712 <br />®•,'EJ STATE OF <br />�eie�I C�C1 ' 4 0 R \'O �i-N�Kle <br />S/QfVA` E�,+, <br />SYSTEM #1 & 2 HVAC NOTES <br />DETAILS AND SCHEDULES <br />SYSTEM #1 & #2 DESCRIPTION — 4.0 Ton Package Heat Pump <br />EQUIPMENT SCHEDULE: TRANE XL15i <br />13 SEER HEAT PUMP SYSTEM with "R-41OA" refrigerant <br />AH MD GAF2AOA34821SA HEAT PUMP <br />CU MD# 4TWX5048A <br />BTUH COOLING CAPACITY 48,000 SEER 13.00 MIN. HSPF 7.8 MIN <br />BTUH HEATING CAPACITY 48,000 <br />BLOWER SPEED CFM 0 .3" WC Cooling 1600 Heating 1600 <br />ELECTRICAL REQUIREMENTS <br />AH-1 MINIMUM AMPACITY 32.5 MAX FUSE 50 AMPS <br />CU-1 MCA 35 MOCP 40 AMPS VOLTS 120 240 1 60 <br />PIPING SIZE 3 8" LIQUID 1 1 8" SUCTION wZ 1 2" INSULATION <br />3 4" CONDENSATE DRAIN <br />CONTROLS: Programmable Thermostat <br />FILTER TYPE: 1" pleated throw —a —ways <br />DUCT SYSTEM: R-6 fiberglass/foil—flex w/Crown #1580 register boxes, <br />damper collars, and Air Mate grilles. All joints sealed with Fasson #0801 <br />pressure sensitive tape. <br />All work shall conform to the requirements of the Current Florida Unified <br />Mechanical Code, 2008 National Electrical Code, and all Pasco <br />Country Codes. <br />Note: General Contractor has the option of utilizing an Equivalent Manufacturers HVAC <br />Package Heat Pump System. <br />FEN <br />• • • • fe� <br />MENI <br />llA •�i a • M.10 <br />a • • �'. <br />' <br />... <br />• <br />---------------------- <br />.. <br />• <br />if <br />. <br />��//IMMMMI%///� <br />® <br />• _ <br />�I <br />o <br />INSULATED OR STORM <br />ice• + <br />...�i <br />IM <br />VIN �,JIM <br />1. PLANS INDICATE THE GENERAL LAYOUT AND LOCATION OF THE MECHANICAL SYSTEM COMPONENTS. <br />UNLESS SPECIFIED DIMENSIONS ARE NOTED, THE ACTUAL LOCATION OF THOSE COMPONENTS SHALL BE <br />DETERMINED IN THE FIELD IN COORDINATION WITH THE WORK OF OTHER TRADES, THE USE OF <br />MANUFACTURER'S SHOP DRAWINGS AND SIMILAR CERTIFIED DATA. <br />2. CONSTRUCTION SHALL COMPLY WITH LOCAL BUILDING CODES ADOPTED AT THE TIME OF PERMIT <br />APPLICATION AND THE 2010 FLORIDA UNIFIED BUILDING CODE, FLORIDA MECHANICAL AND <br />ENERGY CODES. <br />3, SUBMIT SHOP DRAWINGS OF ALL EQUIPMENT AND MATERIAL FOR REVIEW. INSTALL AND TEST ALL <br />EQUIPMENT AND MATERIAL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. <br />4. DUCTWORK, AIR DEVICES AND OTHER ITEMS OF THE AIR DISTRIBUTION SYSTEM SHALL BE SUPPORTED <br />DIRECTLY FROM THE BUILDING STRUCTURE AND NOT TO THE CEILING OR CEILING SUSPENSION SYSTEM. <br />COORDINATE LOCATION OF ALL AIR DEVICES. WALL CAPS, ROOF CAPS AND LOUVERS WITH ELECTRICAL, <br />ARCHITECTURAL AND PLUMBING WORK. <br />5. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF <br />"SMACNA" DUCT CONSTRUCTION STANDARDS AND COMPLY WITH THE LATEST "NFPA" 90A REQUIREMENTS. <br />6. ALL DUCT DINIENSION AS SHOWN ON THE DRAWINGS ARE CLEAR INSIDE DIMENSIONS. ADD 3" FOR <br />EXTERIOR DUCT DIMENSIONS. <br />7. ALL FLEXIBLE DUCT SHALL BE CLASS 1 R-6 INSULATED REINFORCED METALIZED JACKET, AIR —TIGHT, <br />INNER CORE, WITH ENCAPSULATED WIRE HELIX. <br />8. ALL WALL MOUNTED THERMOSTATS SHALL BE INSTALLED AT A CENTER LINE ELEVATION OF 54" ABOVE <br />FINISHED FLOOR UNLESS NOTED ON DRAWINGS. LOCATION OF THERMOSTAT SHALL BE COORDINATED WITH <br />OTHER TRADES FOR A NEAT APPEARANCE, FINAL LOCATION OF THE THERMOSTAT SHALL BE SUBJECT TO <br />APPROVAL OF THE ARCHITECT OR HIS REPRESENTATIVE IN THE FIELD. <br />9. PROVIDE A CONDENSATE DRAIN SYSTEM PER THE 2001 FLORIDA MECHANICAL CODE SECTION 307. <br />a. PROVIDE P—TRAPS AT ALL CONDENSATE DRAIN LINES. SLOPE DRAIN LINES TOWARD THE POINT OF DISCHARGE. <br />b. (MINIMUM 1 /8" PER FOOT). INSULATE DRAIN LINES WITH 1 /2" THICK CLOSED CELL <br />RUBBER PIPE INSULATION. <br />c. CONDENSATE LINES TO BE PVC. LINES TO BE A MINIMUM OF 3/4" diameter. <br />EXTEND TERMINATION OF DRAINS 12" FROM THE EXTERIOR WALL TO GREEN AREA. <br />10. PROVIDE REINFORCED CONCRETE EQUIPMENT PADS FOR THE CONDENSINIG UNITS. PADS TO BE SIZED <br />AND SPACED TO PROVIDE MANUFACTURER'S REQUIRED SERVICE CLEARANCES. <br />Digitally signed by <br />William H Roberts, <br />DN: cn=William H <br />Roberts, PE, o=EGI, <br />ou=Engineering, <br />email=rroberts.eg i <br />@gmail.com, c=US <br />Date: 2013.09.01 <br />16:52:37 <br />DO NOT SCALE DRAWINGS <br />1/2"X6" — <br />STAi2TrN& COLLAR <br />PANT ALKYD GLOSS —� <br />LACK. ADJUSTABLE <br />STAND CAN BE <br />SUBMTED IN PLACE OF <br />STEEL STAND ON THREE <br />TON AND UNDER COOLING <br />SYSTEMS. <br />2"x2"' PLATE, sET oN CflRIcjRUBBEI <br />1ABRATIOM PADS IN EMERGENCY DRAIN <br />PAN WITH FLOAT SNATCH SHUTDOWN. <br />The contractor shall verify all plans and existing dimensions <br />and conditions on the job site and shall immediately notify <br />the engineer in writing of any discrepancies before <br />proceeding with the work or be responsible for same. <br />I HEREBY CERTIFY: <br />THAT THE CONSTRUCTION PLANS SHOWN ARE IN COMPLIANCE <br />WITH CHAPTER 16, SECTION 1609 OF THE 2010 FLORIDA BUILDING CODE <br />FOR 150 MPH ULTIMATE DESIGN WIND SPEED (RISK CATEGORY II) <br />ALONG WITH THE ENTIRE 2010 FLORIDA BUILDING CODE, RESIDENTIAL. <br />EGI—ENGINEERING GREAT IDEAS, LLC <br />William H. Roberts, P.E. <br />1808 James Redman Parkway <br />No. 306 <br />Plant City, Florida 33563 <br />P.E. #42712 <br />TEL (813) 334-0271 <br />CA #29098 <br />8-26-13 <br />DATE <br />OT VAUD WITHOUT FOR SEAT. OR STAMP) <br />rw" <br />A <br />j <br />■ <br />m■.■■■m <br />NNINEEMEMM11 <br />.. <br />■o <br />■r <br />mo <br />■O <br />■M! <br />■o <br />■o <br />No <br />r <br />No <br />No <br />■O <br />- t <br />■o <br />ON <br />■0 <br />■o <br />■o <br />■E <br />_ _ <br />- <br />■o <br />No, <br />AM <br />■0 <br />No <br />; ' <br />:- <br />ON! <br />No <br />■� <br />00 <br />ON <br />E <br />No <br />No <br />■' <br />�. <br />■■■m■■■MENOMINEE <br />it <br />I <br />s <br />• <br />r � <br />i <br />i <br />i <br />DRAVN <br />CLEM TRAUTWEIN <br />SCALD <br />1/4" = 1'—O» <br />CkMCKED & APPROVLD <br />CET 8-22-13 <br />C13542 <br />SHEET 9 OF 14 <br />rroberts.egiOgmail.com trautwein—clem@outlook.com <br />