r <br />ELECTRICAL PLAN SCALE: 1/4// _ 1-0° <br />AD <br />-_CT <br />200 AMP <br />SERVICE <br />SERVICE BY <br />POWER CO, <br />0 <br />(2) 4/0 COPPER <br />(1) 3/0 COPPER <br />2' CONDUIT I200 AMP <br />PANEL <br />TYPICAL ELECTRICAL <br />PANEL (20) CIRCUITS <br />#4 GROUND TO 1/20 ROD 10' DEEP <br />ALSO SERVICE IS BANDED TO <br />FOOTING STEEL <br />#12 COPPER TO <br />LIGHTS & OUTLETS <br />#10 COPPER TO <br />WATER HEATER <br />#4 COPPER TO <br />RANGE <br />#8 COPPER TO <br />A/C <br />GROUNDING ELECTRODE SYSTEM DETAIL <br />NFPA 70 NATIONAL ELECTRICAL CODE, 2015 EDITION <br />ELECTRICAL NOTES: <br />1 - ELECTRICAL RECEPTICALS SHALL BE NO MORE THAN <br />6' FROM ALL DOOR OPENINGS, 12' MAX, O.C., AND SHALL <br />BE WITHIN 25' FROM OUTSIDE A/C UNITS <br />2 - INCANDESCENT LIGHTS SHALL BE NO LESS THAN <br />12' AWAY FROM SHELVING, AND FLUORESCENT <br />LIGHTS SHALL BE NO LESS THAN 6' AWAY FROM <br />SHELVING <br />3 - SMOKE DETECTORS SHALL BE NO MORE THAN 36' <br />AWAY FROM CATHEDRAL PEAKS, NO LESS THAN 36' <br />FROM FORCED A/C AIR VENTS, NO LESS THAN 36' <br />FROM KITCHEN AND BATHROOM DOOR OPENINGS, NO <br />LESS THAN 4' AND NO MORE THAN 12' FROM THE CEILING <br />4 - WATER HEATERS THAT ARE NOT IN SIGHT OF AN <br />ELECTRICAL PANEL BOX SHALL REQUIRE A DISCONNECT <br />5 - GFI OUTLETS IN KITCHEN & GARAGE TO BE INSTALLED PER NEC, <br />6 - CIRCUITS MUST BE PROTECTED WITH <br />ARC FAULT BREAKERS. ONLY 15 & 20 AMP <br />CIRCUITS ARE PROTECTED, <br />7 - LOCATION OF OUTLETS MAY NEED TO BE ADJUSTED <br />DUE TO FIELD & FRAMING CONDITIONS ENCOUNTERED, <br />pON <br />C, <br />` No. 76061 <br />�; <br />01AT OF �<(/ <br />� //'S/ANAL E��. <br />''//ti111l\,\\ <br />PREMIER <br />SHEET 4 OF 5 <br />