ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES. - <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with LIL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in LIL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />LIL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FEPF- <br />DUPLEX OUTLET ABOVE COUNTER <br />WEATHERPROOF DUPLEX OUTLET <br />W.P. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />G.F.I. <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />j3 THREE-WAY SWITCH <br />?4. FOUR-WAY SWITCH <br />$R RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />O RECESSED LIGHT FIXTURE <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />P.C. <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH CHIMES (OPTIONAL) <br />�BP PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD SMOKE DETECTOR <br />CM SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB TELEPHONE/USB (OPTIONAL) <br />© TELEVISION (OPTIONAL) <br />© 2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O THERMOSTAT <br />�]M ELECTRIC METER <br />owl ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />L J <br />� a CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G T J OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />150A/200A INDOOR <br />PANEL CENTER <br />�5 <br />200 amp <br />150 amp <br />UNDERGROUND pis <br />SERVICE BY POWER Co. <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />t to lights & outlets <br />? to appliances and GFI <br />l to WH <br />to Range <br />to HVAC <br />200=4/0 in 2" Conduit <br />4 Bare Cu Ground <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS— <br />!�-----LANAT-----1 <br />I ��\ /�> I <br />I I <br />GFI I I <br />l.l•I. \ I <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS— <br />AC PAD <br />WP <br />GFI DISC. <br />h <br />I <br />1 DINING <br />C5150\ y 6-0" <br />LIGHT AS PER <br />SPECS <br />U.C. OUTLET <br />SWITCH FOR <br />DISPOSAL <br />SPEC 3 & 4 KITCHEN <br />GF PENDANT <br />LIGHT PER <br />- SPECS <br />/ GREAT RM <br />- GFII r j 0 GI <br />_ I 12a I U.C. OUTLET FOR OR OPT. • <br />o Y_ I <br />I � '_ �� Eo I I GF I I(/� FAN/LIGHT <br />1 I SWITCH FOR t OPT. CLG. FAN/ <br />II <br />DISPOSAL I \LIGHT PRE -WIRE <br />GFII - - I - — <br />I II <br />wcr - - GF f / <br />�L� ` • <br />o <br />1'-8" N 1'-10" I <br />I I 3 <br />- • <br />1 I I T L S I I I I I <br />I S 1 1 HI N I I <br />DR <br />L L_ M I I I I 1 11 - - - - - - <br />• Fin <br />- - • <br />GFI @44" FOYER - <br />W.H. A.F.F. <br />� I <br />- Z W I <br />F- d <br />vQ I • • • <br />1` / <br />GARAGE <br />I <br />WP <br />U LIGHT AS <br />PER SPECS <br />GFI <br />• <br />> w \ / <br />,GARAGE <br />GARAGE- / <br />DOOR <br />GFI <br />Ir-------------------------- ---� <br />a <br />I I I <br />I IRRIGATION GFI I <br />. <br />I @ 44" A.F.F. j <br />' <br />• <br />I I <br />I \ <br />I I <br />I � I <br />I � I <br />as <br />------------------------------ <br />COACH LIGHTS <br />OR PREWIRE AS <br />` PER SPECS <br />'W LJI <br />WP DB <br />GFII I <br />I I <br />I I <br />I I <br />0 I I <br />I I <br />I I <br />ENTRY <br />I I <br />I I <br />I I <br />r-i <br />I( II <br />ALT I I <br />I AC PAD I <br />Il 11 <br />F-------------------- 1 <br />I I <br />I I <br />I 1 <br />I I <br />I I <br />I I <br />I I <br />I 1 <br />I I <br />I I <br />— — — — — — — — — — <br />I �p�IC <br />RECEPT. FOR y <br />ALARM SYSTEM <br />Le- --_J <br />OWNER'S <br />SUITE <br />/ OPT. CLG. FAN/ <br />I / LIGHT PRE -WIRE <br />1.5" VTR 3" VTR IIII <br />III � I <br />�I I <br />I I <br />I I <br />I I <br />I r� <br />I I �A <br />3" VTR lil_ <br />I � I <br />S.D. WC V 3„ <br />o 3„ <br />/ /OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />-2BA j2 <br />PROVIDE PHONE / CABLE <br />AND OUTLET AT TECH BEDROOM 4 <br />CENTER / S.D. <br />PLUMBING RISER - <br />SCALE: NTS NOTE. PLUMBING RISER IS SCHEMATIC TO <br />3 4 1 BE VERIFIED WITH PLUMBER <br />o T I <br />- I S I H WI <br />G AU g L I <br />GFI @ <br />44" A.F.F. t H A\A <br />I <br />OPT. CLG. FAN I <br />LIGHT PRE -WIRE <br />BEDROOM 3 <br />I� <br />I OPT. CLG. FAN/ <br />SIGHT PRE -WIRE <br />BEDROOM 2 <br />I � <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />L------------------------------------ J <br />IIt <br />3" <br />ELECTRICAL PLAN <br />SCALE: /4"=V-0" <br />N <br />N <br />c <br />N <br />> <br />> W <br />� V N <br />�- <br />.y <br />N O O 1p <br />a7 c r c <br />CD <br />CD <br />� <br />3 <br />°> u d <br />N Q� <br />c E <br />�O o <br />a C+ <br />w <br />C'M <br />N <br />N <br />N <br />=P'. <br />� I`f <br />To the best of the Engineers knowledge, Information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition. Engineers signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />W vE <br />Q p Cl) <br />- <br />V ;; ie o��o <br />c � L0 <br />(�N0`�• <br />M v LL <br />a C <br />' <br />-j LL W <br />J LL LL Q. <br />2 Y <br />Z z � <br />W z m r13 0 <br />- ;; O <br />W - ZO o m <br />Z N N Z Q 10-- <br />IL <br />OU <br />W o0 <br />z pNp pQM <br />L7 pp <br />z <br />$ <br />Q <br />t✓1 z � <br />� � o <br />fU) <br />�6 W <br />U � <br />c g <br />�N <br />R <br />LU � <br />� <br />� ice•,.. <br />c <br />Q Y <br />� <br />o <br />� <br />J� <br /><Z <br />w <br />E <br />O <br />Q N <br />p <br />� V <br />W z <br />Ka <br />oa <br />H tp <br />M0 <br />U0 <br />�Z <br />�¢ <br />Z <br />,c <br />ro <br />�� <br />w= <br />�w <br />to rD <br />¢ <br />i <br />.01 <br />W M <br />m 0 <br />° <br />ZF <br />Z1, <br />m <br />5 J <br />` <br />a w <br />�z <br />tJ) <br />Fm <br />a <br />no <br />W <br />Z <br />= <br />Z <br />o <br />0 <br />IIIIIIIIIII' <br />M <br />r <br />N <br />0 <br />003 <br />`� <br />Lin <br />J <br />O <br />T <br />� <br />N <br />N <br />CID LO 0. <br />N $ <br />N <br />J <br />Wm <br />N <br />Ln <br />0 <br />� <br />o Y <br />O <br />-0 ccv N <br />N <br />LO <br />T <br />Q CD <br />r <br />ci <br />M <br />t N <br />N �; <br />c <br />Z <br />Z <br />E N 42) <br />E 13 <br />a <br />U Q O <br />JOB <br />NO: 23-04653 <br />SCALE : AS NOTED <br />SHEEP NO. <br />3 <br />