Laserfiche WebLink
I I I 1 L' u. 11 1 <br />SPECIFICATIONS <br />DIVISION ONE - GENERAL REQUIREMENTS <br />SECTION 01010 - SUMMARY OF THE WORK <br />1. The work includes new construction of a commercial building all in <br />accordance with the Contract Documents. <br />2. The performance of all construction under this contract shall conform <br />to all applicable local codes and ordinances and the Federal <br />Occupational Safety and Health Standard. <br />3. The Contractor must exercise proper precaution to verify figures shown <br />on the drawings and must notify the Architect if discrepancies are found. <br />4. Mechanical, Plumbing and Electrical drawings are diagrammatical. <br />Contractor to furnish and install all items necessary for a complete, <br />first-class installation or that are essential for proper operation of work <br />indicated. <br />5. All work on this project shall conform to the requirements of the <br />"General Conditions of the Contract for Construction", AIA Document <br />A201 and are hereby made a part of these specifications as if bound <br />herein and shall apply to all divisions as though copies in each. <br />6. All materials to be incorporated into the project shall be new. If <br />required, the contractor shall furnish satisfactory evidence as to kind <br />and quality and meet all specification standard and requirements. <br />7. The contractor shall store all materials for construction and protect <br />from rain, pilferage and damage. Contractor shall obtain insurance <br />covering same. <br />SECTION 01340 - SHOP DRAWINGS AND SAMPLES <br />1. Contractor to provide Architect shop drawings for approval prior to <br />ordering and fabrication of the following: <br />a. Pre Engineered wood trusses <br />2. Verification of field measurements or conditions shall remain the <br />responsibility of the Contractor. <br />SECTION 01720 - PROJECT RECORD DOCUMENTS <br />1. Maintain at the job site one copy of all Contract Drawings and Project <br />Manual. Clearly mark the Drawings as "Project Record Copy"; maintain <br />in good condition, available at all times for inspection by the Architect. Do <br />not use for construction. <br />2. Mark up the most appropriate Document to show: <br />a. Significant changes made during the construction process. <br />b. Significant detail not shown in the original Contract <br />Documents. <br />3. Keep Project -Record Documents current. Do not permanently conceal <br />any work until the required information has been recorded. <br />4. Use red line on all documents. In marking the Drawings use the same <br />symbols, legends, etc. as used on the Drawings to identify like material, <br />piping, etc. <br />5. Submit Project Record Documents to the Architect upon completion <br />of the Project and prior to final payment. <br />DIVISION TWO - SITEWORK <br />SECTION 02210 - BUILDING SITE EARTHWORK <br />1. Perform work in compliance with applicable requirements of <br />governing authorities having jurisdiction. <br />2. Employ, at Contractor's expense, a testing laboratory acceptable to <br />Architect to perform soil testing and inspection service for testing <br />suitability of footing subgrades and density of building slab subgrade. <br />3. Submit 1 copy of all test reports directly to the Architect from the Testing <br />and Inspection Service, with copy to the Contractor. <br />a. Test reports on borrow material. <br />b. Field density test reports. <br />C. One optimum moisture -maximum density curve for each <br />type of soil encountered. <br />d. Verification of suitability of footing subgrades. <br />4. Provide acceptable soil materials for backfill and fill. Provide <br />relatively clean sand free of clay, rock or gravel larger than 2" in any <br />dimension, debris, waste, vegetable and other deleterious matter, <br />and with no more than 10% of the total material passing the #200 <br />mesh sieve. Soil materials must be approved by the Testing and <br />Inspection Service. <br />5. Maintain the sides and slopes of excavations in a safe condition until <br />completion of backfilling. <br />6. Prevent surface water and subsurface or ground water from flowing <br />into the excavations. <br />7. Do not allow water to accumulate in excavations. Provide and maintain <br />pumps, sumps, suction and discharge lines, and other <br />dewatering system components necessary to convey the water away <br />from excavations. <br />8. Convey water removed from excavations and rain water to collecting or <br />run-off areas. Do not use trench excavations for site utilities as <br />temporary drainage ditches. <br />9. Conform to the elevations and dimensions shown on the Drawings, <br />within a tolerance of plus or minus 0.10 feet. <br />10. In excavating for footings and foundations, take care not to disturb <br />the bottom of the excavation. Excavate by hand to final grade just <br />before concrete reinforcement is placed. Trim bottoms to the required <br />lines and grades to leave a solid base to receive concrete. <br />11. Control soil compaction during fill and backfill for compliance with the <br />percentage of density specified for each area classification. <br />12. Percentage of maximum density requirements: Compact soil to not less <br />than the following percentages of maximum density for soils which <br />exhibit a well-defined moisture density relationship determined in <br />accordance with ASTM D 1557 (Modified Proctor Density). <br />a. Building Slabs: 95% maximum density. <br />b. Trenches: 95% maximum density. <br />13. Place backfill and fill materials in layers not more than 12" in loose <br />depth for material compacted by heavy compaction equipment, and <br />not more than 4" in loose depth for material compacted by hand - <br />operated tampers. <br />14. Before compaction, moisten each layer as necessary to provide the <br />optimum moisture content. Compact each layer to the required <br />percentage of maximum dry density for each area classification. <br />15. Care shall be taken to insure that all backfill around foundation <br />excavations and in service line trenches beneath slabs -on -grade is <br />properly placed and compacted. <br />SECTION 02280 - SOIL TREATMENT <br />1. Provide soil treatment for termite control as herein specified. <br />2. Use an emulsible concentrate insecticide for dilution with water, specially <br />formulated to prevent infestation by termites. Fuel oil will not be <br />permitted as a diluent. Provide a working solution of one of the following <br />chemical elements and concentrations: <br />a. Chloropyrifos ("Dursban-TC"); 1.0% in water emulsion. <br />b. Permathrin ("Dragnet", "Torpedo"); 0.5% in water <br />emulsion. <br />3. Other solutions may be used as recommended by Applicator and if <br />acceptable to local governing authorities. Use only soil treatment <br />solutions which are not injurious to planting. <br />4. Remove foreign matter which could decrease effectiveness of <br />treatment on areas to be treated. Loosen, rake and level soil to be <br />treated, except previously compacted areas under slabs and <br />foundations. <br />5. Apply soil treatment solution at following minimum rate: <br />a. Within building area, with or without slabs -on -grade, at rate <br />of one gallon per 10 square feet. <br />b. Outside building perimeter, under aprons, pads, or paved <br />extensions, at rate of one gallon per 5 square feet. <br />C. At hollow masonry foundations treat voids at rate of one <br />gallon per 5 lineal feet, poured directly into hollow spaces. <br />d. At control joints, along both sides of foundation walls and <br />areas where slab will be penetrated, at rate of 2 gallons <br />per 5 lineal feet of penetration. <br />6. Allow drying time after application of not less than 12 hours before <br />beginning concrete placement or other construction activities. <br />7. Post signs in areas of application warning workers that soil poisoning <br />has been applied. Remove signs when areas are covered by other <br />construction. <br />8. Reapply soil treatment solution to areas disturbed by subsequent <br />excavation or other construction activities following application. <br />DIVISION THREE - CONCRETE <br />SECTION 03310 - CONCRETE WORK <br />1. All concrete work shall be performed in accordance with the <br />"Specifications for Structural Concrete for Building" (ACI 301) <br />2. Reinforcing steel shall be domestic steel conforming to ASTM A615 <br />grade 60. Welded wire fabric shall conform to ASTM A185. <br />3. All concrete shall be ready -mixed concrete in accordance with ASTM C94 <br />4. Portland cement to be ASTM C 150, Type 1 <br />5. Non -shrink grout to be CRD-C 621 factory premixed, Type D, <br />nonmetallic grout. <br />6. Proportion and design mixes to result in concrete slump at point of <br />placement of 4" (plus or minus 1 inch). Design mix to be 3000 psi <br />minimum 28-day compressive strength, 470 Ibs cement per cubic <br />yard minimum. <br />7. No admixtures shall be provided without prior approval of the <br />Architect. <br />8. Provide curing in accordance with ACI 301 procedures <br />DIVISION FOUR - MASONRY <br />(No work in this division) <br />DIVISION FIVE - METALS <br />SECTION 05120 - STRUCTURAL STEEL <br />1. Comply with AISC "Code of Standard Practice for Steel Buildings <br />and Bridges", AISC "Specifications for the Design, Fabrication, and <br />Erection of Structural Steel for Buildings", AISC "Specifications for <br />Structural Joints using ASTM A-325 or A-490 Bolts" and the AWS <br />D1.1 "Structural Welding Code". <br />2. Qualify welding processes and Welding operators in accordance with <br />the AWS "Standard Qualifications Procedure" <br />3. Submit shop drawings showing complete details and schedules for <br />fabrication and assembly of members. <br />4. Steel product specifications are as follows: <br />a. Structural steel shapes, plates and bars to be ASTM A-36. <br />b. Cold formed steel tubing to be ASTM A-500 Grade B <br />C. Hot formed steel tubing to be ASTM A-501 <br />d. Anchor bolts to be ASTM A-307 non -threaded type (unless <br />otherwise indicated) <br />e. High strength fasteners to be hexagonal structural bolts <br />(medium carbon steel) as per ASTM A-325. <br />5. Provide welding electrodes as per AWS code. <br />6. Shrink -resistant grout to be nonmetallic as manufactured by Burke <br />Company, US Grout Corp. or equal. <br />7. Splices in structural members shall not be permitted without prior <br />approval. <br />8. Shop paint structural steel work except for portions of members to be <br />embedded in concrete or which are to be welded or bolted with friction <br />type connectors. <br />SECTION 05400 - METAL STUDS <br />1. Provide "C" shaped cold -formed metal studs as manufactured by <br />U.S. Gypsum or equal. Provide manufacturer's recommended size, <br />gage and type for height and spacing, condition and application shown <br />on the drawings. <br />2. 16 gage and heavier units to be fabricated of ASTM A 446 sheet steel. <br />3. 18 gage and lighter units to be fabricated of ASTM A 446, A 570, or <br />611 sheet steel. <br />4. Provide runner tracks secured at a maximum of 16" on center. Provide <br />fasteners at ends and corners of tracks. <br />5. Frame openings larger than 2'-0" square with double stud at each <br />jamb of frame. Install runner tracks and jack studs above and below <br />openings. Install horizontal stiffeners in stud system at not more than <br />4'-6" on center. Weld at each intersection. <br />DIVISION SIX - WOOD AND PLASTICS <br />SECTION 06192 - PREFABRICATED WOOD TRUSSES <br />1. Prefabricated wood trusses include planar structural units consisting of <br />metal plate connected members which are fabricated from dimension <br />lumber and which have been cut and assembled prior to delivery to the <br />job site. <br />2. Comply with application requirements and recommendations of the <br />following Truss Plate Institute (TPI) publications. <br />a. "Design Specification for Metal Plate Connected Wood <br />Trusses". <br />b. "Commentary and Recommendations for Handling and <br />Erecting Wood Trusses". <br />C. "Commentary and Recommendations for Bracing Wood <br />Trusses". <br />d. "Quality Control Manual". <br />3. Comply with applicable requirements of "National Design Specification for <br />Wood Construction" published by N.F.P.A. <br />4. Comply with PS 20 and with applicable rules of the respective grading <br />inspecting agencies for species and grade of lumber indicated. <br />5. Provide truss connector plates manufactured by a firm which is a member <br />of TPI and which complies with TPI quality control procedures for <br />manufacture of connector plates published in TPI "Quality Control <br />Manual". <br />6. Submit shop drawings showing species, sizes and stress grades of <br />lumber to be used; pitch, span, camber, configuration and spacing for <br />each type of truss required; type, size, material, finish, design value, and <br />location of metal connector plates; and bearing and anchorage details. <br />a. Provide shop drawings which have been signed and stamped <br />by structural engineer licensed to practice in the State the <br />project is located. <br />7. Handle and store trusses with care, and in accordance with <br />manufacturer's Instructions and TPI recommendations to avoid damage <br />from bending, overturning or other cause for which truss is not designed <br />to resist or endure. <br />8. Products: <br />a. Factory mark each piece of lumber with type, grade, mill and <br />grading agency. <br />b. Nominal sizes are indicated, except as shown by detail <br />dimensions. Provide actual sizes as required by PS 20, for <br />dressed lumber, S4S, unless otherwise indicated. <br />C. Provide seasoned lumber with maximum moisture content at <br />time of dressing of 15%. <br />d. Lumber species: Southern Pine, graded by SPIB. <br />e. Lumber Grade: For species indicated, provide the following <br />stress -rated grade: "Selected Structural". <br />9. Metal Connector Plates, Fasteners and Anchorage's: <br />a. Connector plate material: Metal complying with following <br />requirements, unless otherwise indicated; not less than "0.036" <br />thick, coated thickness. <br />b. Galvanized sheet steel: ASTM A 446, Grade A, Coating <br />G60. <br />C. Fasteners and anchorages: Provide size, type, material and <br />finish indicated, complying with applicable Federal <br />Specifications for nails, screws, bolts, nuts and washers and <br />anchoring devices. <br />10. Erect and brace trusses to comply with recommendations of <br />manufacturer and the Truss Plate Institute. <br />11. Erect trusses with plane of truss webs vertical (plumb) and parallel to <br />each other, located accurately at design spacing indicated. <br />12. Hoist units in place by means of lifting equipment suited to sizes and <br />types of trusses required, applied at designated lift points as <br />recommended by fabricator, exercising care not to damage truss <br />members or joints by out -of -plane bending or other causes. <br />13. Provide temporary bracing as required to maintain trusses plumb, parallel <br />and in location indicated, until permanent bracing is installed. <br />14. Anchor trusses securely at all bearing points to comply with methods and <br />details indicated. <br />15. Install permanent bracing and related components to enable trusses to <br />maintain design spacing, withstand live and dead loads including lateral <br />loads, and to comply with other indicated requirements. <br />16. Do not cut or remove truss members. <br />SECTION 06200 - ROUGH CARPENTRY <br />1. Provide labor and materials for all wood grounds, nailers, blocking, <br />framing, wood furring, etc. <br />2. Comply with the following wood product quality standards: <br />a. Lumber standards - PS 20 <br />b. Plywood standards - PS 1 / ANSI - A199.1 and APA <br />3. Nominal sizes of lumber are indicated, except as shown by detail <br />dimensions. <br />4. Provide dressed lumber, S4S unless otherwise indicated, seasoned <br />lumber with 19% maximum moisture content at time of dressing. <br />5. Provide exterior or interior grade plywood as required by field <br />application. Provide 18 gage hurricane clips (Heckman or equal) <br />6. All wood exposed to weather or in contact with masonry shall be <br />pressure treated in accordance with AWPB LP-2. <br />7. Furring for gypsum drywall, unless otherwise indicated, provide 1" x 2" <br />furring at 16" on center vertically. <br />DIVISION SEVEN - THERMAL AND MOISTURE PROTECTION <br />SECTION 7200 - INSULATION <br />1. Extent of insulation work is shown on drawings, by generic name or by <br />abbreviation. <br />2. Insulation to be as follows: <br />A. Wall insulation to be FiFoil VR Plus Shield (or equal) R-7.1 <br />insulation. <br />B. Roof insulation to be 3" spray polyurethane foam insulation <br />(SPF) closed cell type, minimum R-6.0/per inch. <br />3. Comply with manufacturer's instructions for particular conditions of <br />installation in each case. If printed instructions are not available or <br />do not apply to project conditions, consult manufacturer's technical <br />representative for specific recommendations before proceeding with <br />work. <br />4. Extend insulation full thickness as shown over entire area to be <br />insulated. Cut and fit tightly around obstructions, and fill voids with <br />insulation. Remove projections which interfere with placement. <br />SECTION 07540 - TPO ROOFING <br />1. Provide a smooth type, polyester scrim reinforced thermoplastic <br />polyolefin membrane, for use as a single ply roofing membrane. <br />2. Product shall meet or exceed the minimum requirements of ASTM D- <br />6878. UL Listed, FM Approved, Dade County Product Approval, Florida <br />Building Code Approved. <br />3. Provide an EverGuard® Extreme TPO; EverGuard® Extreme TPO Fleece - <br />Back Membrane with a thickness of 60mil. <br />4. Use manufacturer's recommended mechanical fasteners and flashing <br />materials. <br />5. Install system per manufacturer's printed instructions. <br />SECTION 07600 - FLASHING AND SHEET METAL <br />1. Provide aluminum ASTM B 209, alloy 3003, 20 gage flashing as shown <br />and as required by conventional practice. <br />2. Shop fabricate work to the greatest extent possible. Shop fabricate <br />ALL corners, T's, ends and interfaces. Fabricate non-moving seams <br />in sheet metal with flat lock seams. <br />3. For steel flashing, tin edges to be seamed, form seams, rivet and <br />solder. Form aluminum seams with epoxy seam sealer, rivet joints <br />for additional strength as required. <br />4. Where aluminum is to be installed directly on cementatious or wood <br />substrates, install a course of paper slip sheet and a course of <br />polyethylene underlayment. <br />SECTION 07900 - JOINT SEALERS <br />1. Provide elastomeric sealants to seal and make watertight all exterior <br />joints as required. <br />2. Provide caulking compound to fill or close interior joints where <br />expansion and contraction are of no consideration and where <br />appearance is of primary importance. <br />3. Caulking compound shall be architectural grade non -shrink elastic <br />caulking compound conforming to federal specifications TT-C-598. <br />4. Sealants shall be one of the following types: <br />Manufacturer Masonry and Concrete All other areas <br />G.E. Silprup 1200 <br />Dow Corning 790 786 <br />PRC - 500 <br />5. Color of caulking compound and sealants shall match adjacent surfaces <br />where not painted. <br />DIVISION EIGHT - DOORS AND WINDOWS <br />SECTION 08100 - DOORS AND WINDOWS <br />1. Provide doors and windows as indicated on the drawings and as <br />scheduled. Conform to all manufs installation requirements. <br />DIVISION NINE - FINISHES <br />SECTION 09250 - GYPSUM DRYWALL <br />1. Gypsum wallboard products: <br />a. Standard gypsum wallboard shall be 48" wide with tapered <br />edges, 5/8" thick and shall conform to ASTM C-36 <br />b. Water resistant gypsum wallboard shall be self furring 48" <br />wide sheets, 5/8" thick and conform to ASTM C-36. <br />2. Products and metal accessories: <br />a. Corner beads and casing beads shall be standard <br />galvanized steel section and manufactured for use with <br />drywall construction. <br />b. Nails shall be annular ring nails conforming to ASTM C- <br />380. <br />C. Screws shall be self -drilling, corrosion resistant screws <br />with Phillip heads. <br />3. The gypsum wallboard shall be installed by an approved, <br />experienced drywall applicator normally engaged in this trade. <br />4. Water resistant gypsum wallboard shall be applied to walls in toilets <br />5. Gypsum wallboard of maximum practical length shall be used so that <br />an absolute minimum number of end joints occur. Boards shall be <br />brought into contact with each other but shall not be forced into place. <br />gypsum board joints at openings shall be located so that no end joint will <br />align with edges of openings. All end joints shall be staggered. <br />6. Apply gypsum board with the length at right angles to the supporting <br />members. Center abutting ends or edges over supports. <br />7. Fasteners shall be spaced not less than 1/8" from ends and edges of <br />wallboard. Wallboard shall be held in firm contact with support slightly <br />below the surface of the wallboard with care being taken while fasteners <br />are being placed. Heads shall be dimpled to break the paper face. <br />8. Apply gypsum board with fasteners spaced 12" on center in the field <br />and 8" on center along vertical edges. <br />9. All joints, internal angles, dimpled corners and edges shall be <br />reinforced and finished using the 3-coat system. Allow 24 hours for <br />drying time between applications of cement. Sand the cement after <br />each coat is dry to a smooth surface effectively concealing the joints <br />or fasteners. <br />10. Joint treatment products shall be fiber reinforced tape and ready mixed <br />joint compound and toppings compound as recommended by the gypsum <br />board manufacturer. <br />11. Comer beads shall be applied to all external corners. Casing beads <br />shall be applied around all wall or ceiling openings. <br />12. All materials shall be delivered to the job site in unbroken manufs <br />containers and shall be properly stored and protected from the <br />elements until use. <br />SECTION 09900 - PAINTING <br />1. Paint all exposed surfaces unless otherwise indicated. All paints shall be <br />first -line, premium quality as manufactured by Sherwin Williams. <br />2. Refer to drawings for painting schedule. <br />SECTION 10800 - TOILET ACCESSORIES <br />1. The extent of each type of toilet accessory is shown on the drawings <br />and schedules, and as described in these specifications. <br />2. Deliver accessories to the job in protective cartons; store in a safe <br />place protected against damage. <br />3. Coordinate with Section 06100 Rough Carpentry for the accurate <br />location of all wood blocking required for the anchoring of toilet room <br />accessories. <br />4 Installer must examine the areas and conditions under which <br />accessories are to be installed and notify the Contractor in writing of <br />conditions detrimental to the proper and timely completion of the work. <br />Do not proceed with the work until unsatisfactory conditions have been <br />corrected in a manner acceptable to the Installer. <br />5 Provide anchors, bolts, and other necessary anchorages, and attach <br />accessories securely to walls and partitions in locations as shown. <br />6 Install concealed mounting devices and fasteners where possible, <br />fabricated of the same material as the accessories, or of galvanized <br />steel, as recommended by manufacturer. <br />7 Secure accessories to adjacent walls and partitions complying with the <br />manufs instructions for each item and each type of substrate. <br />8 Mount all accessories in handicap accessible toilet rooms as required <br />by all applicable codes. <br />DIVISION TEN - SPECIALTIES <br />(No work in this division) <br />DIVISION ELEVEN -EQUIPMENT <br />(No work in this division) <br />DIVISION TWELVE - FURNISHINGS <br />(No work in this division) <br />DIVISION THIRTEEN - SPECIAL CONSTRUCTION <br />(No work in this division) <br />DIVISION FOURTEEN - CONVEYING SYSTEMS <br />((No work in this division) <br />DIVISION FIFTEEN - MECHANICAL <br />SECTION 16400 - PLUMBING <br />1. All plumbing materials, fixtures and installation shall comply with all <br />requirements of the Florida State Board of Health's Sanitary Code, <br />the Florida Building Code and the Florida Plumbing Code. <br />2. The work consists of cold water supply piping, soil waste and vent <br />piping, plumbing fixtures and trim, flashings for roof penetrations, <br />and connections of equipment supplied by others. <br />3. All materials shall be new and shall bear underwriters' label, where <br />applicable. <br />4. All work shall be performed by a licensed plumbing contractor, in a <br />first-class workmanlike manner. The completed system shall be fully <br />operative and acceptance by engineer or architect must be a <br />condition of the subcontract. <br />5. All work shall be coordinated with other trades, to avoid interference <br />with the progress of construction. <br />6. Verify locations, size, elevations and materials and present state of <br />all existing utilities, prior to beginning construction. Advise Owner of <br />any discrepancies. <br />7. Water piping to be Type 'L' copper, with wrought solder fittings, except <br />where noted otherwise. <br />8. Soil, waste and vent piping to be schedule 40 PVC, together with <br />schedule 40 PVC fittings. Fittings on waste lines to be drainage pattern. <br />All joints to be made with approved cement applied in strict accordance <br />with the manufacturers' published instructions. <br />9. Install readily accessible gate valves in all branch water lines serving <br />any room having plumbing fixtures. All fixtures must be provided <br />with readily accessible stops. <br />10. Where dissimilar metals are to be joined, approved insulating unions <br />shall be used. <br />11. Contractor shall guarantee all materials and workmanship free from <br />defects, for a period of not less than one (1) year, from date of <br />acceptance. <br />SECTION 15500 - HEATING, VENTILATION AND AIR CONDITIONING <br />1. HVAC Contractor shall install HVAC units, diffusers and ductwork for <br />a complete and operable Air Conditioning system to provide Heating, <br />Cooling and ventilation comfort in accordance with Ashrae <br />Standards. Contractor to provide all ductwork, thermostat wiring, <br />electrical hookup etc. to provide a fully operational system. <br />2. Drawings are diagrammatic. Do not scale the drawings for the exact <br />location of equipment, piping, ductwork, etc. <br />3. These drawings are not intended to show every minor detail. The <br />Contractor shall furnish and install all items required for a complete, <br />acceptable working installation. <br />4. All work shall be performed by a licensed Contractor, in a First -Class <br />workmanlike manner. The completed system shall be fully operative <br />and acceptance by Owner is a condition of the Sub -contract. <br />5. All work shall be coordinated with other trades, to avoid interference <br />with the progress of construction. <br />6. All workmanship and materials shall be in strict accordance with <br />applicable National, State and Local Codes, Rules and Ordinances. <br />7. All materials shall be new and shall bear underwriters' label, where <br />applicable. <br />8. Ductwork below roof to be spiral metal type as indicated on the <br />drawings. Fabricate and install in strict accordance with the <br />manufacturers' instructions. <br />9. Air distribution accessories shall be of aluminum with volume controls as <br />manufactured by 'Metalaire', or approved equal, unless shown or <br />scheduled otherwise. All grille finishes to be white. <br />10. All elbows must be furnished with approved turning vanes. <br />11. Branch takeoffs must be provided with approved, adjustable, <br />accessible air extractors. <br />13. Filters to be throw -away type, unless noted otherwise. Locate in air <br />handler and/or at return grille. <br />14. Furnish and install all temperature controls under this contract, <br />including humidity controls, where applicable. <br />15. Mount thermostats 5'-6' above floor, unless otherwise noted. <br />16. Install firestats in units over 2000 CFM <br />17. Provide all required roof openings, additional steel reinforcing, roof <br />curbs and flashing at new rooftop unit locations as required. <br />18. Contractor shall guarantee all materials and workmanship free from <br />defects, for a period of not less than one (1) year from date of <br />acceptance, unless noted otherwise. <br />DIVISION SIXTEEN - ELECTRICAL <br />1. Comply with the requirements of the latest edition of the National <br />Electrical Code, and applicable rules and regulations of Local and <br />State Laws and Ordinances. <br />2. Do not scale the drawings. Refer to Architectural Plans and <br />Elevations for locations of equipment. Confirm exact location from <br />approved shop drawings with Owner. It is not the intent of these plans to <br />show every minor detail of construction. Any discrepancies shall be <br />called to Architect's attention. The Contractor is expected to furnish and <br />install all items for a complete electrical system and provide all <br />requirements necessary for equipment to be placed in acceptable, proper <br />working order. <br />3. The electrical installation shall meet all standard requirements of local <br />Utility Company. Verify service requirements, current characteristics and <br />transformer data, prior to commencing any work. <br />4. All cutting and patching, excavation, compacting, backfill, etc., required <br />for the electrical work shall be done by the electrical contractor. <br />5. All materials shall be new and shall bear Underwriters' and Union <br />Labels, where applicable. <br />6. All work shall be coordinated with other trades to avoid interference <br />with the progress of construction. The final locations of all <br />equipment shall be verified with the Owner or his appointed Agent. <br />7. All work shall be performed by a licensed Electrical Contractor, in a <br />First -Class workmanlike manner. The completed system shall be <br />fully operative and acceptance by Architect must be a condition of <br />the Sub- Contract. <br />8. Load data is based on information given Engineer at the time of design. <br />Verify all equipment, panel sizes, protective devices and feeders before <br />ordering. Obtain necessary data from the approved shop drawings of <br />the various Subcontractors. <br />9 The Electrical system shall be completely and effectively grounded, <br />as required by the latest edition of the N.E.C. <br />10. Install facilities for temporary power for construction, as required. <br />Furnish and install all wiring for power and controls of all A/C systems <br />and mechanical equipment. Wire starters and control devices furnished <br />by others. Furnish and install all special systems as called for on the <br />plans or specifications. <br />11. Conductors shall be copper with 600 volt insulation, unless otherwise <br />noted. #6 AWG and smaller may have 60 degree C or higher <br />insulation rating; #4 and larger shall have 75 degree C or higher <br />insulation rating. All conductors #10 and smaller may be solid. #8 <br />and larger shall be stranded. Non-metallic cables and service cords <br />installed where permitted shall have an equipment grounding <br />conductor within the cable assembly sized per N.E.C. No aluminum <br />wire will be permitted <br />END OF SPECIFICATIONS <br />Revisions Date By <br />Mark A. lonnatti <br />Florida AR 0010778 <br />JONNATTI <br />ARCHITECTURE <br />INCORPORATED <br />21021 US Highway 19 N <br />Clearwater, Florida 33765 <br />(727) 725-ARCH <br />(727) 725-2603 fx <br />www.jarch.com <br />info@jarch.com <br />© lonnatti Architecture <br />Incorporated 2021 <br />ZEPHR <br />RETAIL <br />DEVELOPMENT <br />US HWY 301 <br />GALL BLVD <br />ZEPHYRHILLS <br />FLORIDA <br />33542 <br />I SPECIFI CATIONS <br />Drawn <br />MAJ <br />Check <br />MAJ <br />Date <br />AUG 18, 2021 <br />AS NOTED <br />LScale <br />No <br />ZEPHR RB <br />Sheet: Oil <br />