GENERAL NOTES:
<br />I. ALL ELECTRICAL WORK ON THIS PROJECT SHALL CONFORM TO THE REQUIREMENTS OF THE
<br />NATIONAL ELECTRICAL CODE, LATEST APPLICABLE EDITION (N.F.P.A. - 70), ALL LOCAL
<br />APPLICABLE CODES AND THE FOLLOWING CRITERIA;
<br />A. TRADE SIZE CONDUIT SMALLER THAN 1/2' SHALL NOT BE USED
<br />B. CONDUIT ABOVE GRADE AND NOT EXPOSED TO WEATHER SHALL BE ELECTRICAL
<br />METALLIC TUBING (EMT). FITTINGS SHALL BE COMPRESSION TYPE
<br />C. CONDUIT BELOW GRADE SHALL BE SCHEDULE 40 PVC EXCEPT TURNS AND PENETRATIONS
<br />AT GRADE SHALL BE GALVANIZED RIGID STEEL.
<br />D. CONDUIT ABOVE GRADE AND EXPOSED TO WEATHER SHALL BE GALVANIZED RIGID OR
<br />INTERMEDIATE METAL CONDUIT.
<br />E. WIRE SIZE SMALLER THAN #13 AWG SHALL NOT BE USED FOR POWER AND LIGHTING
<br />CIRCUITS.
<br />F. ALL WIRING PROVIDED BY THE ELECTRICAL CONTRACTOR SHALL BE COPPER.
<br />G. ALL CONDUCTORS SHALL HAVE A MINIMUM TEMPERATURE RATING OF 75 DEGREES (TYPE
<br />THW OR TYPE THHN).
<br />H. WHERE POSSIBLE, EXCEPT AS SHOWN OTHERWISE ON THE DRAWINGS, ALL CONDUIT SHALL
<br />BE RUN CONCEALED BELOW GRADE, WITHIN WALLS OR ABOVE CEILINGS.
<br />I. CONDUCTORS #14 AWG AND SMALLER SHALL BE SOLID. CONDUCTORS #10 AWG AND
<br />LARGER SHALL BE STRANDED TYPE WIRE. CONDUCTORS #12 AWG MAY BE SOLID OR
<br />STRANDED EXCEPT THAT ONLY #12 AWG SOLID OR #12 AWG STRANDED SHALL BE USED.
<br />J. THERE SHALL BE NO MORE THAN 270 DEGREES TOTAL TURN OR 150 FEET BETWEEN
<br />PULL POINTS IN ALL CONDUIT RUNS.
<br />2. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION PERMITS FOR
<br />ELECTRICAL WORK AND FOR SCHEDULING ELECTRICAL INSPECTIONS.
<br />3. THE ELECTRICAL CONTRACTOR SHALL ARRANGE FOR AND MAKE NECESSARY CONNECTIONS
<br />FOR TEMPORARY POWER AS REQUIRED FOR CONSTRUCTION.
<br />4. THE ELECTRICAL CONTRACTOR SHALL MAKE ARRANGEMENTS WITH THE ELECTRIC UTILITY
<br />COMPANY FOR SERVICE CONNECTIONS
<br />5. SOME SAFETY DISCONNECT SWITCHES MAY BE PROVIDED BY THE MECHANICAL CONTRACTOR
<br />BUT INSTALLED AND CONNECTED BY THE ELECTRICAL CONTRACTOR. THIS WORK SHALL BE
<br />COORDINATED WITH THE MECHANICAL CONTRACTOR
<br />6. CONDUIT WHICH PENETRATES THE ROOF OR EXTERIOR WALLS SHALL BE FLASHED AND
<br />SEALED WATERTIGHT.
<br />7. BURIED CONDUIT NOT UNDER SLABS SHALL HAVE A MINIMUM COVER OF 24 INCHES.
<br />8. UNLESS NOTES OTHERWISE:
<br />A. LIGHT SWITCHES SHALL BE CENTERED AT 44 INCHES AFF
<br />B. RECEPTACLES SHALL BE CENTERED AT 19 INCHES AFF
<br />C. CONDUIT SHALL BE MINIMUM 112'
<br />D. WIRING SHALL BE MINIMUM #12 AWG
<br />E. DISCONNECT SWITCHES SHALL BE HEAVY DUTY, NON -FUSED, NEMA-I, 30 AMP, 3 POLE
<br />9. RECEPTACLES MOUNTED ON OPPOSITE SIDES OF THE WALL SHALL BE SEPARATED BY A
<br />MINIMUM OF 24 INCHES
<br />10. ALL LIGHT FIXTURES SHALL BE PROVIDED WITH LAMPS AND SHALL BE OPERABLE AT THE
<br />TIME OF FINAL INSPECTION.
<br />11. VERIFY DOOR SWINGS PRIOR TO ELECTRICAL ROUGH -IN TO ASSURE PROPER SWITCH LOCATION.
<br />ELECTRICAL LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />-IN CEILING RECESSED LIGHT FIXTURE (OR SURFACE MOUNTED "CLOUD" FIXTURE
<br />QLAY
<br />N
<br />WHERE SCHEDULED) LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE
<br />WALL MOUNTED LIGHT FIXTURE
<br />0 N
<br />LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE
<br />RECESSED CEILING MOUNTED CAN LIGHT FIXTURE
<br />N
<br />LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE
<br />RECESSED CEILING MOUNTED 3" CAN WALL WASHER LIGHT FIXTURE
<br />N
<br />LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE
<br />®P
<br />CEILING MOUNTED JUNCTION BOX SECURED TO SUPPORT PENDANT LIGHT
<br />PENDANT LIGHT SUPPLIED BY OWNER - INSTALLED BY CONTRACTOR
<br />io EX
<br />EXIT LIGHT FIXTURE
<br />LETTER DENOTES MARK IN FIXTURE SCHEDULE
<br />1=�EM
<br />EMERGENCY LIGHT FIXTURE
<br />LETTER DENOTES MARK IN FIXTURE SCHEDULE
<br />FLUSH MOUNTED SINGLE POLE WALL SWITCH, 20 AMP, HUBBELL CAT.
<br />NO, 12211 OR EQUAL
<br />LEVITON OSS10 OR LUTRON LOS-SIR-HD OCCUPANCY SENSOR WALL SWITCH
<br />V
<br />LOW VOLTAGE SWITCH
<br />gg
<br />FLUSH MOUNTED DUPLEX WALL RECEPTACLE, NEMA 5-15R, MOUNTED AT 19" AFF UNLESS
<br />aD
<br />NOTED OTHERWISE
<br />Jl
<br />FLUSH MOUNTED DUPLEX WALL RECEPTACLE, NEMA 5-15R, TOP HALF SWITCHED
<br />®
<br />MOUNTED AT 19" AFF UNLESS NOTED OTHERWISE
<br />1tD
<br />DEDICATED FLUSH MOUNTED DUPLEX WALL RECEPTACLE, NEMA 5-15R, MOUNTED AT 19"
<br />�D
<br />AFF UNLESS NOTED OTHERWISE
<br />FLUSH MOUNTED QUAD WALL RECEPTACLE, NEMA 5-15R, MOUNTED AT
<br />19" AFF UNLESS NOTED OTHERWISE
<br />FLUSH MOUNTED QUAD WALL RECEPTACLE, NEMA 5-15R, TOP HALF SWITCHED
<br />MOUNTED AT 19" AFF UNLESS NOTED OTHERWISE
<br />.
<br />TWO SURFACE MOUNTED DUPLEX RECEPTACLES AND DATA OUTLET
<br />®
<br />FLUSH MOUNTED FLOOR BOX WITH TWO DUPLEX RECEPTACLES AND DATA OUTLET
<br />LO
<br />ELECTRICAL DISCONNECT SWITCH; SEE ELECTRICAL NOTES
<br />©
<br />JUNCTION BOX WITH COVER SIZED FOR THE NUMBER OF CIRCUITS SHOWN TERMINATING
<br />AT THAT LOCATION.
<br />.
<br />VOICE/DATA JACK WITH CAT 5 WIRE TO VOICE DATA PANEL.
<br />PANNEEL
<br />ELECTRICAL PANEL; LETTERING IDENTIFIES PANEL
<br />®
<br />WATERPROOF EXTERIOR MOUNTED PUSH BUTTON WIRED TO BUZZER SIGNAL DEVICE
<br />- EDWARDS 852 OR 1786-8
<br />BUZZ
<br />DISENGAGE SWITCH FOR ELECTRIC DOOR LOCK
<br />TV
<br />TELEVISION JACK WITH HDMI AND DATA JACK. PROVIDE HDMI CABLE TO LES BOARD
<br />SD
<br />SMOKE DETECTOR HARD WIRED AND INTERCONNECTED
<br />EF
<br />ELECTRICAL FAN - SEE MECHANICAL PLAN
<br />BRANCH CIRCUIT WIRING SCHEDULE GUIDE
<br />SINGLE POLE (1P)
<br />THREE POLE (312)
<br />CIB
<br />SIZE
<br />WIRE
<br />CONDUIT
<br />REMARKS
<br />S�
<br />WIRE
<br />CONDUIT
<br />REMARKS
<br />20o.
<br />2-#12, 1-#12G.
<br />3/4"
<br />10,2W
<br />20a.
<br />3-#12, 1-#12G.
<br />3/4"
<br />30, 3W
<br />25a.
<br />2-#10, 1-#12G.
<br />3/4"
<br />10,2W
<br />25a.
<br />3-#10, 1-#10G.
<br />3/4"
<br />30, 3W
<br />300.
<br />2-#10, 1-#10G.
<br />3/4"
<br />10,2W
<br />30a.
<br />3-#10, 1-#10G.
<br />3/4"
<br />30, 3W
<br />35a.
<br />2-#8, 1-#10G.
<br />3/4"
<br />10,2W
<br />30a,
<br />3-#10, 1-#10N, 1-#100.
<br />3/4"
<br />30, 4W
<br />40a.
<br />2-#8, 1-#10G.
<br />3/4"
<br />10,2W
<br />35a.
<br />3-#8, 1-#10G.
<br />1"
<br />30, 3W
<br />45a.
<br />2-#8, 1-#10G.
<br />3/4"
<br />10,2W
<br />35a.
<br />3-#8, 1-#8, 1-#10G.
<br />1"
<br />30, 4W
<br />50a.
<br />2-#8, 1-#10G.
<br />3/4"
<br />10,2W
<br />40a.
<br />3-#8, 1-#IOG.
<br />1"
<br />30, 3W
<br />600.
<br />2-#6, 1-#10G.
<br />3/4"
<br />10,2W
<br />40o.
<br />3-#8, 1-#8N, 1-#10G.
<br />1"
<br />30, 4W
<br />45a.
<br />3-#8, 1-#10G.
<br />1"
<br />30, 3W
<br />TWO POLE
<br />(2P)
<br />45a,
<br />3-#8, 1-#8N, 1-10G,
<br />1"
<br />30, 4W
<br />20a.
<br />2-#12, 1-#12G.
<br />3/4"
<br />10,2W
<br />50a.
<br />3-#8, 1-#10G.
<br />1"
<br />30, 3W
<br />25a.
<br />2-#10, 1-#10G.
<br />3/4"
<br />10,2W
<br />50a.
<br />3-#8, 1-#8N, 1-10G.
<br />1"
<br />30, 4W
<br />300.
<br />2-#10, 1-#10G.
<br />3/4"
<br />10,2W
<br />60a.
<br />3-#6, 1-#10G.
<br />1"
<br />30, 3W
<br />40a.
<br />2-#8, 1-#10G.
<br />1"
<br />10,2W
<br />60a.
<br />3-#6, 1-#6N, 1-#100.
<br />1 1/4"
<br />30, 4W
<br />45a.
<br />2-#8, 1-#10G.
<br />1"
<br />10,2W
<br />1000.
<br />3-#3, 1-#3N, 1-#3G.
<br />1 1/2"
<br />30, 4W
<br />50a.
<br />2-#8, 1-#10G.
<br />1"
<br />10,2W
<br />125a.
<br />3-#1, 1-#1N, 1-#6G.
<br />2"
<br />30, 4W
<br />60a.
<br />2-#6, 1-#10G.
<br />1"
<br />10,2W
<br />1500.
<br />3-#1/0, 1-#1/ON, 1-#6G.
<br />2"
<br />30, 4W
<br />70o.
<br />2-#4, 1-#8G.
<br />1"
<br />10,2W
<br />175a.
<br />3-#2/0, 1-#2/ON, 1-#6G.
<br />2'
<br />30, 4W
<br />800.
<br />2-#3, 1-#8G.
<br />1 1/4"
<br />10,2W
<br />2000.
<br />3-#3/0, 1-#3/ON, 1-#6G.
<br />2 1/2"
<br />30, 4W
<br />900,
<br />2-#2, 1-#8G.
<br />1 1/4"
<br />10,2W
<br />1000,
<br />2-#2, 1-#8G.
<br />1 1/4"
<br />10,2W
<br />CIRCUITING EXAMPLE KEY
<br />CKT: a
<br />DENOTES LIGHTING SWITCH LEG
<br />DENOTES PANEL NAME (BY ROOM). LIGHTING PLAN ONLY
<br />DENOTES CIRCUIT NUMBER
<br />DISCONNECT EXAMPLE KEY
<br />3P6050WR
<br />NUMBER OF POLES NEMA WEATHER RATING
<br />DISCONNECT RATING FUSE SIZE
<br />("NF" DENOTES NON -FUSED)
<br />FLORIDA ENERGY CODE
<br />BRANCH CIRCUIT WIRE SIZES SHALL COMPLY WITH FLORIDA
<br />ENERGY CODE, 6TH EDITION (2017) C405.7.3.1 AND C405.7.3.2
<br />FOR VOLTAGE DROP.
<br />GENERAL RULE:
<br />-USE #10 FOR 20A, 277V BRANCH CIRCUITS LONGER THAN 200'
<br />-USE #10 FOR 20A, 120V BRANCH CIRCUITS LONGER THAN 75'
<br />-USE #8 FOR 20A, 277V BRANCH CIRCUITS LONGER THAN 250'
<br />-USE #8 FOR 20A, 120V BRANCH CIRCUITS LONGER THAN 150'
<br />ARC FLASH NOTE
<br />THE ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL
<br />SIGNAGE/LABELS FOR ARC FLASH/SHOCK HAZARD FOR ALL
<br />SERVICE EQUIPMENT AS PER N.E.C. ART. 110.24 AND NFPA
<br />70E. SIGNAGE/LABELS MUST SUITABLE TO WITHSTAND THE
<br />ENVIRONMENT AND SHALL INCLUDE THE MAXIMUM AVAILABLE
<br />FAULT CURRENT, LEVEL OF PPE REQUIRED, APPROACH
<br />BOUNDARIES AND DATE OF CALCULATION.
<br />34
<br />M
<br />° PNL-A
<br />4wE
<br />208Y/120V 30 4W
<br />FED FROM MDP
<br />° 119179 AFC
<br />_�—W6°0 PRE -DRILLED HOLES. SECURE TO PANEL
<br />WITH �'O SS RIVETS (TYP. 4)
<br />---EQUIPMENT NAME AS SPECIFIED ON PLANS
<br />SYSTEM VOLTAGE
<br />—UPSTREAM EQUIPMENT SUPPLYING POWER
<br />AVAILABLE FAULT CURRENT AT EQUIPMENT
<br />INSTALL LABEL AT TOP OF
<br />ENCLOSURE
<br />e
<br />NOTES:
<br />I. ALL DISTRIBUTION EQUIPMENT SUCH AS PANELBOARDS, SWITCHBOARDS, DISCONNECTS, TRANSFORMERS, ETC.
<br />SHALL BE PROVIDED WITH AN EQUIPMENT LABEL PER THE REQUIREMENTS OF THIS DETAIL.
<br />2. LABELS SHALL BE 2-PLY ENGRAVED PLASTIC LAMINATE WITH BLACK TYPEFACE LETTERS., LABEL BACKGROUND
<br />SHALL FOLLOW THE BELOW COLOR SCHEME:
<br />a. NORMAL POWER - WHITE
<br />b. UPS POWER - BLUE
<br />c. LIFE SAFETY POWER - YELLOW
<br />3. LABEL MATERIAL SHALL BE DURABLE, UV STABLE, RATED FOR OUTDOOR USE, AND ABRASION RESISTANT. WHERE
<br />ATTACHED TO NEMA 4X EQUIPMENT, LABELS SHALL IN ADDITION BE CHEMICAL RESISTANT.
<br />4. LABELS SHALL BE PERMANENTLY ATTACHED TO ENCLOSURE COVER WITH RIVETS UNLESS DOING SO COMPROMISES ITS
<br />NEMA / IP RATING. LABELS FOR ENCLOSURES WITH WELDED SEAMS AND GASKETED DOORS SUCH AS THOSE RATED
<br />NEMA 12 OR NEMA 4 SHALL BE INSTALLED USING PERMANENT WEATHER-, UV-, AND TEMPERATURE -RESISTANT
<br />DOUBLE -SIDED MOUNTING TAPE ONLY.
<br />S. A SUBMITTAL WITH A COMPLETE LIST OF EQUIPMENT LABELS SHALL BE PROVIDED FOR ENGINEER APPROVAL PRIOR
<br />TO ORDERING.
<br />6. LABELS SHALL INDICATE NO LESS THAN THE FOLLOWING:
<br />a. EQUIPMENT NAME.
<br />b. THE NOMINAL SYSTEM VOLTAGE WHICH SAID EQUIPMENT IS CONNECTED TO.
<br />c. THE EQUIPMENT NAME SUPPLYING POWER TO SAID EQUIPMENT.
<br />d. THE AVAILABLE FAULT CURRENT AT SAID EQUIPMENT.
<br />11 EQUIPMENT LABEL DETAIL
<br />0.0/ NOT TO SCALE
<br />nPODM (WH) 3X
<br />nPODM(WH)3X
<br />•
<br />ADD ADDITIONAL DEVICES
<br />PER ZONE LAYOUT.
<br />OFF
<br />•
<br />R
<br />C
<br />nCM PDT 10 RJB nCM PDT 10 RJB
<br />OR OR
<br />nCM PDT 9 RJB nCM PDT 9 RJB
<br />BLK- 120V/ ORN- 277V
<br />ADD ADDITIONAL DEVICES
<br />PER ZONE LAYOUT.
<br />TYPICAL WIRING DIAGRAM
<br />LOW VOLTAGE CEILING
<br />SENSOR AND SWITCH
<br />TO ADDITIONAL
<br />LUMINAIRES ON
<br />SAME ZONE
<br />WIRE LEGEND
<br />0-- CAT 5-E (CLASS 2)
<br />- Bf LINE VOLTAGE
<br />NOTE:
<br />REFER TO CONTROLS SCHEDULE
<br />FOR EXACT MODEL NUMBERS.
<br />0.0j NOT TO SCALE
<br />5
<br />0.0.
<br />OCCUPANCY SENSOR
<br />POWER PAC"
<br />RETAINING NUT
<br />RETAINING WASHER
<br />CEILING STRUCTURE
<br />OCCUPANCY SENSOR
<br />JLTAGE CONNECTION MADE
<br />JUNCTION BOX
<br />CEILING OCCUPANCY SENSOR
<br />INSTALLATION DETAIL
<br />NOTES:
<br />PROVIDE ARC FLASH HAZARD LABELING AND FIELD MARK ALL ELECTRICAL EQUIPMENT AS PART OF
<br />ARC FLASH RISK ASSESSMENT PER 2015 EDITION OF NFPA 70E 130.50. THE LABEL MUST CONTAIN
<br />THE FOLLOWING INFORMATION:
<br />I. NONE SYSTEM VOLTAGE.
<br />2. ARC FLASH BOUNDARY.
<br />3. AT LEAST ONE OF THE FOLLOWING:
<br />a. AVAILABLE INCIDENT ENERGY AND THE CORRESPONDING DISTANCE,
<br />OR THE ARC FLASH PPE CATEGORY IN TABLE 130.7(C)(15)(A)(b)
<br />OR 130.7(C)(15)(B) FOR THE EQUIPMENT, BUT NOT BOTH.
<br />b. MINIMUM ARC RATING OF CLOTHING.
<br />c. SITE -SPECIFIC LEVEL OF PPE.
<br />ARC FLASH WARNING LABEL
<br />2 RE UIREMENT DETAIL
<br />0.0 NOT TO SCALE
<br />e H N
<br />:1 w
<br />BLACK
<br />ON/OFF BLACK LIGHT
<br />FIXTURE
<br />GREEN e
<br />NOTE:
<br />REFER TO CONTROLS SCHEDULE
<br />FOR EXACT MODEL NUMBERS.
<br />TYPICAL WIRING DIAGRAM
<br />LOW VOLTAGE WALL
<br />4 MOUNT SENSOR DETAIL
<br />� NOT TO SCALE
<br />I CONTACTOR CONTROLLED RECEPTACLES
<br />CONTROLLED RECEPTACLES SHALL BE CONTROLLED BY
<br />LIGHTING CONTROL PANEL OR LOCAL CONTROL DEVICE.
<br />REFER TO LIGHTING CONTROL PANEL CONTACTOR SCHEDULE
<br />FOR BRANCH CIRCUITS ROUTED VIA CONTACTOR. PROGRAM
<br />CONTROLLED CONTROLLED RECEPTACLE CONTACTOR(S) TO BE ON SAME
<br />RECEPTACLE SYMBOL TIME SCHEDULE AS INTERIOR LIGHTING.
<br />PER NEC 406.3
<br />POWER PACK
<br />LIGHTING CONTROL
<br />CKT #1 PANEL CONTACT
<br />CONTROLLED
<br />H
<br />r
<br />v
<br />O
<br />O
<br />NON -CONTROLLED
<br />NOTES:
<br />I. ALL CONTROLLED RECEPTACLES AND/OR COVER PLATES SHALL BE
<br />PROVIDED WITH FACTORY ENGRAVED LABELS INDICATING TOP OUTLET AS
<br />'CONTROLLED' AND BOTTOM OUTLET AS 'NON -CONTROLLED'.
<br />2. CIRCUIT NUMBER SHALL BE INDICATED WITH A TYPED SELF-ADHESIVE BACKED
<br />LABEL WITH CLEAR BACKGROUND AND CHARACTERS OF CONTRASTING COLOR
<br />TO COVER PLATE (BLACK OR WHITE CHARACTERS).
<br />3. FOR CLARITY, NOT ALL EQUIPMENT GROUNDS ARE SHOWN.
<br />4. PROVIDE ISOLATED GROUND RECEPTACLE AND IG CONDUCTOR WHEN SPECIFIED
<br />ON PLAN DRAWINGS AND PANEL SCHEDULES.
<br />5. CONTROLLED RECEPTACLES SHALL BE FACTORY MARKED WITH THE
<br />CONTROLLED RECEPTACLE SYMBOL [NEC 406.31.
<br />HALF SWITCHED PLUG
<br />6 LOAD WIRING DIAGRAM
<br />v
<br />D
<br />- XX
<br />Revisions Date By
<br />Mark A. Jonnatti
<br />Florida AR 0010778
<br />JONNATTI
<br />ARCHITECTURE
<br />INCORPORATED
<br />21021 US Highway 19 N
<br />Clearwater, Florida 33765
<br />(727) 725-ARCH
<br />(727) 725-2603 fx
<br />www.jarch.com
<br />info@jarch.com
<br />© jonnatti Architecture
<br />Incorporated 2021
<br />OF•FLO
<br />�o/V • .y
<br />SIR 1107PI III
<br />•an..
<br />S/6/21
<br />"i `"- • M
<br />r , •• •• a
<br />• •,..
<br />:. ,.
<br />Tru lit VqU
<br />INTERIOR
<br />REMODEL
<br />US H" 301
<br />GALL BLVD
<br />ZEPHYRHILLS
<br />FLORIDA
<br />33542
<br />ELECTRICAL
<br />DETAILS
<br />OTES AND
<br />AILS
<br />(Draw7nMAI
<br />Check
<br />MAI
<br />Date
<br />AUG 31, 2021
<br />EScaleAS
<br />NOTED
<br />TRULIEVE-ZH
<br />Sheet:
<br />EOOO
<br />NOT TO SCALE
<br />0.0/ NOT TO SCALE
<br />
|