GENERAL NOTES: <br />I. ALL ELECTRICAL WORK ON THIS PROJECT SHALL CONFORM TO THE REQUIREMENTS OF THE <br />NATIONAL ELECTRICAL CODE, LATEST APPLICABLE EDITION (N.F.P.A. - 70), ALL LOCAL <br />APPLICABLE CODES AND THE FOLLOWING CRITERIA; <br />A. TRADE SIZE CONDUIT SMALLER THAN 1/2' SHALL NOT BE USED <br />B. CONDUIT ABOVE GRADE AND NOT EXPOSED TO WEATHER SHALL BE ELECTRICAL <br />METALLIC TUBING (EMT). FITTINGS SHALL BE COMPRESSION TYPE <br />C. CONDUIT BELOW GRADE SHALL BE SCHEDULE 40 PVC EXCEPT TURNS AND PENETRATIONS <br />AT GRADE SHALL BE GALVANIZED RIGID STEEL. <br />D. CONDUIT ABOVE GRADE AND EXPOSED TO WEATHER SHALL BE GALVANIZED RIGID OR <br />INTERMEDIATE METAL CONDUIT. <br />E. WIRE SIZE SMALLER THAN #13 AWG SHALL NOT BE USED FOR POWER AND LIGHTING <br />CIRCUITS. <br />F. ALL WIRING PROVIDED BY THE ELECTRICAL CONTRACTOR SHALL BE COPPER. <br />G. ALL CONDUCTORS SHALL HAVE A MINIMUM TEMPERATURE RATING OF 75 DEGREES (TYPE <br />THW OR TYPE THHN). <br />H. WHERE POSSIBLE, EXCEPT AS SHOWN OTHERWISE ON THE DRAWINGS, ALL CONDUIT SHALL <br />BE RUN CONCEALED BELOW GRADE, WITHIN WALLS OR ABOVE CEILINGS. <br />I. CONDUCTORS #14 AWG AND SMALLER SHALL BE SOLID. CONDUCTORS #10 AWG AND <br />LARGER SHALL BE STRANDED TYPE WIRE. CONDUCTORS #12 AWG MAY BE SOLID OR <br />STRANDED EXCEPT THAT ONLY #12 AWG SOLID OR #12 AWG STRANDED SHALL BE USED. <br />J. THERE SHALL BE NO MORE THAN 270 DEGREES TOTAL TURN OR 150 FEET BETWEEN <br />PULL POINTS IN ALL CONDUIT RUNS. <br />2. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION PERMITS FOR <br />ELECTRICAL WORK AND FOR SCHEDULING ELECTRICAL INSPECTIONS. <br />3. THE ELECTRICAL CONTRACTOR SHALL ARRANGE FOR AND MAKE NECESSARY CONNECTIONS <br />FOR TEMPORARY POWER AS REQUIRED FOR CONSTRUCTION. <br />4. THE ELECTRICAL CONTRACTOR SHALL MAKE ARRANGEMENTS WITH THE ELECTRIC UTILITY <br />COMPANY FOR SERVICE CONNECTIONS <br />5. SOME SAFETY DISCONNECT SWITCHES MAY BE PROVIDED BY THE MECHANICAL CONTRACTOR <br />BUT INSTALLED AND CONNECTED BY THE ELECTRICAL CONTRACTOR. THIS WORK SHALL BE <br />COORDINATED WITH THE MECHANICAL CONTRACTOR <br />6. CONDUIT WHICH PENETRATES THE ROOF OR EXTERIOR WALLS SHALL BE FLASHED AND <br />SEALED WATERTIGHT. <br />7. BURIED CONDUIT NOT UNDER SLABS SHALL HAVE A MINIMUM COVER OF 24 INCHES. <br />8. UNLESS NOTES OTHERWISE: <br />A. LIGHT SWITCHES SHALL BE CENTERED AT 44 INCHES AFF <br />B. RECEPTACLES SHALL BE CENTERED AT 19 INCHES AFF <br />C. CONDUIT SHALL BE MINIMUM 112' <br />D. WIRING SHALL BE MINIMUM #12 AWG <br />E. DISCONNECT SWITCHES SHALL BE HEAVY DUTY, NON -FUSED, NEMA-I, 30 AMP, 3 POLE <br />9. RECEPTACLES MOUNTED ON OPPOSITE SIDES OF THE WALL SHALL BE SEPARATED BY A <br />MINIMUM OF 24 INCHES <br />10. ALL LIGHT FIXTURES SHALL BE PROVIDED WITH LAMPS AND SHALL BE OPERABLE AT THE <br />TIME OF FINAL INSPECTION. <br />11. VERIFY DOOR SWINGS PRIOR TO ELECTRICAL ROUGH -IN TO ASSURE PROPER SWITCH LOCATION. <br />ELECTRICAL LEGEND <br />SYMBOL <br />DESCRIPTION <br />-IN CEILING RECESSED LIGHT FIXTURE (OR SURFACE MOUNTED "CLOUD" FIXTURE <br />QLAY <br />N <br />WHERE SCHEDULED) LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE <br />WALL MOUNTED LIGHT FIXTURE <br />0 N <br />LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE <br />RECESSED CEILING MOUNTED CAN LIGHT FIXTURE <br />N <br />LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE <br />RECESSED CEILING MOUNTED 3" CAN WALL WASHER LIGHT FIXTURE <br />N <br />LETTER DENOTES MARK IN LIGHTING FIXTURE SCHEDULE <br />®P <br />CEILING MOUNTED JUNCTION BOX SECURED TO SUPPORT PENDANT LIGHT <br />PENDANT LIGHT SUPPLIED BY OWNER - INSTALLED BY CONTRACTOR <br />io EX <br />EXIT LIGHT FIXTURE <br />LETTER DENOTES MARK IN FIXTURE SCHEDULE <br />1=�EM <br />EMERGENCY LIGHT FIXTURE <br />LETTER DENOTES MARK IN FIXTURE SCHEDULE <br />FLUSH MOUNTED SINGLE POLE WALL SWITCH, 20 AMP, HUBBELL CAT. <br />NO, 12211 OR EQUAL <br />LEVITON OSS10 OR LUTRON LOS-SIR-HD OCCUPANCY SENSOR WALL SWITCH <br />V <br />LOW VOLTAGE SWITCH <br />gg <br />FLUSH MOUNTED DUPLEX WALL RECEPTACLE, NEMA 5-15R, MOUNTED AT 19" AFF UNLESS <br />aD <br />NOTED OTHERWISE <br />Jl <br />FLUSH MOUNTED DUPLEX WALL RECEPTACLE, NEMA 5-15R, TOP HALF SWITCHED <br />® <br />MOUNTED AT 19" AFF UNLESS NOTED OTHERWISE <br />1tD <br />DEDICATED FLUSH MOUNTED DUPLEX WALL RECEPTACLE, NEMA 5-15R, MOUNTED AT 19" <br />�D <br />AFF UNLESS NOTED OTHERWISE <br />FLUSH MOUNTED QUAD WALL RECEPTACLE, NEMA 5-15R, MOUNTED AT <br />19" AFF UNLESS NOTED OTHERWISE <br />FLUSH MOUNTED QUAD WALL RECEPTACLE, NEMA 5-15R, TOP HALF SWITCHED <br />MOUNTED AT 19" AFF UNLESS NOTED OTHERWISE <br />. <br />TWO SURFACE MOUNTED DUPLEX RECEPTACLES AND DATA OUTLET <br />® <br />FLUSH MOUNTED FLOOR BOX WITH TWO DUPLEX RECEPTACLES AND DATA OUTLET <br />LO <br />ELECTRICAL DISCONNECT SWITCH; SEE ELECTRICAL NOTES <br />© <br />JUNCTION BOX WITH COVER SIZED FOR THE NUMBER OF CIRCUITS SHOWN TERMINATING <br />AT THAT LOCATION. <br />. <br />VOICE/DATA JACK WITH CAT 5 WIRE TO VOICE DATA PANEL. <br />PANNEEL <br />ELECTRICAL PANEL; LETTERING IDENTIFIES PANEL <br />® <br />WATERPROOF EXTERIOR MOUNTED PUSH BUTTON WIRED TO BUZZER SIGNAL DEVICE <br />- EDWARDS 852 OR 1786-8 <br />BUZZ <br />DISENGAGE SWITCH FOR ELECTRIC DOOR LOCK <br />TV <br />TELEVISION JACK WITH HDMI AND DATA JACK. PROVIDE HDMI CABLE TO LES BOARD <br />SD <br />SMOKE DETECTOR HARD WIRED AND INTERCONNECTED <br />EF <br />ELECTRICAL FAN - SEE MECHANICAL PLAN <br />BRANCH CIRCUIT WIRING SCHEDULE GUIDE <br />SINGLE POLE (1P) <br />THREE POLE (312) <br />CIB <br />SIZE <br />WIRE <br />CONDUIT <br />REMARKS <br />S� <br />WIRE <br />CONDUIT <br />REMARKS <br />20o. <br />2-#12, 1-#12G. <br />3/4" <br />10,2W <br />20a. <br />3-#12, 1-#12G. <br />3/4" <br />30, 3W <br />25a. <br />2-#10, 1-#12G. <br />3/4" <br />10,2W <br />25a. <br />3-#10, 1-#10G. <br />3/4" <br />30, 3W <br />300. <br />2-#10, 1-#10G. <br />3/4" <br />10,2W <br />30a. <br />3-#10, 1-#10G. <br />3/4" <br />30, 3W <br />35a. <br />2-#8, 1-#10G. <br />3/4" <br />10,2W <br />30a, <br />3-#10, 1-#10N, 1-#100. <br />3/4" <br />30, 4W <br />40a. <br />2-#8, 1-#10G. <br />3/4" <br />10,2W <br />35a. <br />3-#8, 1-#10G. <br />1" <br />30, 3W <br />45a. <br />2-#8, 1-#10G. <br />3/4" <br />10,2W <br />35a. <br />3-#8, 1-#8, 1-#10G. <br />1" <br />30, 4W <br />50a. <br />2-#8, 1-#10G. <br />3/4" <br />10,2W <br />40a. <br />3-#8, 1-#IOG. <br />1" <br />30, 3W <br />600. <br />2-#6, 1-#10G. <br />3/4" <br />10,2W <br />40o. <br />3-#8, 1-#8N, 1-#10G. <br />1" <br />30, 4W <br />45a. <br />3-#8, 1-#10G. <br />1" <br />30, 3W <br />TWO POLE <br />(2P) <br />45a, <br />3-#8, 1-#8N, 1-10G, <br />1" <br />30, 4W <br />20a. <br />2-#12, 1-#12G. <br />3/4" <br />10,2W <br />50a. <br />3-#8, 1-#10G. <br />1" <br />30, 3W <br />25a. <br />2-#10, 1-#10G. <br />3/4" <br />10,2W <br />50a. <br />3-#8, 1-#8N, 1-10G. <br />1" <br />30, 4W <br />300. <br />2-#10, 1-#10G. <br />3/4" <br />10,2W <br />60a. <br />3-#6, 1-#10G. <br />1" <br />30, 3W <br />40a. <br />2-#8, 1-#10G. <br />1" <br />10,2W <br />60a. <br />3-#6, 1-#6N, 1-#100. <br />1 1/4" <br />30, 4W <br />45a. <br />2-#8, 1-#10G. <br />1" <br />10,2W <br />1000. <br />3-#3, 1-#3N, 1-#3G. <br />1 1/2" <br />30, 4W <br />50a. <br />2-#8, 1-#10G. <br />1" <br />10,2W <br />125a. <br />3-#1, 1-#1N, 1-#6G. <br />2" <br />30, 4W <br />60a. <br />2-#6, 1-#10G. <br />1" <br />10,2W <br />1500. <br />3-#1/0, 1-#1/ON, 1-#6G. <br />2" <br />30, 4W <br />70o. <br />2-#4, 1-#8G. <br />1" <br />10,2W <br />175a. <br />3-#2/0, 1-#2/ON, 1-#6G. <br />2' <br />30, 4W <br />800. <br />2-#3, 1-#8G. <br />1 1/4" <br />10,2W <br />2000. <br />3-#3/0, 1-#3/ON, 1-#6G. <br />2 1/2" <br />30, 4W <br />900, <br />2-#2, 1-#8G. <br />1 1/4" <br />10,2W <br />1000, <br />2-#2, 1-#8G. <br />1 1/4" <br />10,2W <br />CIRCUITING EXAMPLE KEY <br />CKT: a <br />DENOTES LIGHTING SWITCH LEG <br />DENOTES PANEL NAME (BY ROOM). LIGHTING PLAN ONLY <br />DENOTES CIRCUIT NUMBER <br />DISCONNECT EXAMPLE KEY <br />3P6050WR <br />NUMBER OF POLES NEMA WEATHER RATING <br />DISCONNECT RATING FUSE SIZE <br />("NF" DENOTES NON -FUSED) <br />FLORIDA ENERGY CODE <br />BRANCH CIRCUIT WIRE SIZES SHALL COMPLY WITH FLORIDA <br />ENERGY CODE, 6TH EDITION (2017) C405.7.3.1 AND C405.7.3.2 <br />FOR VOLTAGE DROP. <br />GENERAL RULE: <br />-USE #10 FOR 20A, 277V BRANCH CIRCUITS LONGER THAN 200' <br />-USE #10 FOR 20A, 120V BRANCH CIRCUITS LONGER THAN 75' <br />-USE #8 FOR 20A, 277V BRANCH CIRCUITS LONGER THAN 250' <br />-USE #8 FOR 20A, 120V BRANCH CIRCUITS LONGER THAN 150' <br />ARC FLASH NOTE <br />THE ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL <br />SIGNAGE/LABELS FOR ARC FLASH/SHOCK HAZARD FOR ALL <br />SERVICE EQUIPMENT AS PER N.E.C. ART. 110.24 AND NFPA <br />70E. SIGNAGE/LABELS MUST SUITABLE TO WITHSTAND THE <br />ENVIRONMENT AND SHALL INCLUDE THE MAXIMUM AVAILABLE <br />FAULT CURRENT, LEVEL OF PPE REQUIRED, APPROACH <br />BOUNDARIES AND DATE OF CALCULATION. <br />34 <br />M <br />° PNL-A <br />4wE <br />208Y/120V 30 4W <br />FED FROM MDP <br />° 119179 AFC <br />_�—W6°0 PRE -DRILLED HOLES. SECURE TO PANEL <br />WITH �'O SS RIVETS (TYP. 4) <br />---EQUIPMENT NAME AS SPECIFIED ON PLANS <br />SYSTEM VOLTAGE <br />—UPSTREAM EQUIPMENT SUPPLYING POWER <br />AVAILABLE FAULT CURRENT AT EQUIPMENT <br />INSTALL LABEL AT TOP OF <br />ENCLOSURE <br />e <br />NOTES: <br />I. ALL DISTRIBUTION EQUIPMENT SUCH AS PANELBOARDS, SWITCHBOARDS, DISCONNECTS, TRANSFORMERS, ETC. <br />SHALL BE PROVIDED WITH AN EQUIPMENT LABEL PER THE REQUIREMENTS OF THIS DETAIL. <br />2. LABELS SHALL BE 2-PLY ENGRAVED PLASTIC LAMINATE WITH BLACK TYPEFACE LETTERS., LABEL BACKGROUND <br />SHALL FOLLOW THE BELOW COLOR SCHEME: <br />a. NORMAL POWER - WHITE <br />b. UPS POWER - BLUE <br />c. LIFE SAFETY POWER - YELLOW <br />3. LABEL MATERIAL SHALL BE DURABLE, UV STABLE, RATED FOR OUTDOOR USE, AND ABRASION RESISTANT. WHERE <br />ATTACHED TO NEMA 4X EQUIPMENT, LABELS SHALL IN ADDITION BE CHEMICAL RESISTANT. <br />4. LABELS SHALL BE PERMANENTLY ATTACHED TO ENCLOSURE COVER WITH RIVETS UNLESS DOING SO COMPROMISES ITS <br />NEMA / IP RATING. LABELS FOR ENCLOSURES WITH WELDED SEAMS AND GASKETED DOORS SUCH AS THOSE RATED <br />NEMA 12 OR NEMA 4 SHALL BE INSTALLED USING PERMANENT WEATHER-, UV-, AND TEMPERATURE -RESISTANT <br />DOUBLE -SIDED MOUNTING TAPE ONLY. <br />S. A SUBMITTAL WITH A COMPLETE LIST OF EQUIPMENT LABELS SHALL BE PROVIDED FOR ENGINEER APPROVAL PRIOR <br />TO ORDERING. <br />6. LABELS SHALL INDICATE NO LESS THAN THE FOLLOWING: <br />a. EQUIPMENT NAME. <br />b. THE NOMINAL SYSTEM VOLTAGE WHICH SAID EQUIPMENT IS CONNECTED TO. <br />c. THE EQUIPMENT NAME SUPPLYING POWER TO SAID EQUIPMENT. <br />d. THE AVAILABLE FAULT CURRENT AT SAID EQUIPMENT. <br />11 EQUIPMENT LABEL DETAIL <br />0.0/ NOT TO SCALE <br />nPODM (WH) 3X <br />nPODM(WH)3X <br />• <br />ADD ADDITIONAL DEVICES <br />PER ZONE LAYOUT. <br />OFF <br />• <br />R <br />C <br />nCM PDT 10 RJB nCM PDT 10 RJB <br />OR OR <br />nCM PDT 9 RJB nCM PDT 9 RJB <br />BLK- 120V/ ORN- 277V <br />ADD ADDITIONAL DEVICES <br />PER ZONE LAYOUT. <br />TYPICAL WIRING DIAGRAM <br />LOW VOLTAGE CEILING <br />SENSOR AND SWITCH <br />TO ADDITIONAL <br />LUMINAIRES ON <br />SAME ZONE <br />WIRE LEGEND <br />0-- CAT 5-E (CLASS 2) <br />- Bf LINE VOLTAGE <br />NOTE: <br />REFER TO CONTROLS SCHEDULE <br />FOR EXACT MODEL NUMBERS. <br />0.0j NOT TO SCALE <br />5 <br />0.0. <br />OCCUPANCY SENSOR <br />POWER PAC" <br />RETAINING NUT <br />RETAINING WASHER <br />CEILING STRUCTURE <br />OCCUPANCY SENSOR <br />JLTAGE CONNECTION MADE <br />JUNCTION BOX <br />CEILING OCCUPANCY SENSOR <br />INSTALLATION DETAIL <br />NOTES: <br />PROVIDE ARC FLASH HAZARD LABELING AND FIELD MARK ALL ELECTRICAL EQUIPMENT AS PART OF <br />ARC FLASH RISK ASSESSMENT PER 2015 EDITION OF NFPA 70E 130.50. THE LABEL MUST CONTAIN <br />THE FOLLOWING INFORMATION: <br />I. NONE SYSTEM VOLTAGE. <br />2. ARC FLASH BOUNDARY. <br />3. AT LEAST ONE OF THE FOLLOWING: <br />a. AVAILABLE INCIDENT ENERGY AND THE CORRESPONDING DISTANCE, <br />OR THE ARC FLASH PPE CATEGORY IN TABLE 130.7(C)(15)(A)(b) <br />OR 130.7(C)(15)(B) FOR THE EQUIPMENT, BUT NOT BOTH. <br />b. MINIMUM ARC RATING OF CLOTHING. <br />c. SITE -SPECIFIC LEVEL OF PPE. <br />ARC FLASH WARNING LABEL <br />2 RE UIREMENT DETAIL <br />0.0 NOT TO SCALE <br />e H N <br />:1 w <br />BLACK <br />ON/OFF BLACK LIGHT <br />FIXTURE <br />GREEN e <br />NOTE: <br />REFER TO CONTROLS SCHEDULE <br />FOR EXACT MODEL NUMBERS. <br />TYPICAL WIRING DIAGRAM <br />LOW VOLTAGE WALL <br />4 MOUNT SENSOR DETAIL <br />� NOT TO SCALE <br />I CONTACTOR CONTROLLED RECEPTACLES <br />CONTROLLED RECEPTACLES SHALL BE CONTROLLED BY <br />LIGHTING CONTROL PANEL OR LOCAL CONTROL DEVICE. <br />REFER TO LIGHTING CONTROL PANEL CONTACTOR SCHEDULE <br />FOR BRANCH CIRCUITS ROUTED VIA CONTACTOR. PROGRAM <br />CONTROLLED CONTROLLED RECEPTACLE CONTACTOR(S) TO BE ON SAME <br />RECEPTACLE SYMBOL TIME SCHEDULE AS INTERIOR LIGHTING. <br />PER NEC 406.3 <br />POWER PACK <br />LIGHTING CONTROL <br />CKT #1 PANEL CONTACT <br />CONTROLLED <br />H <br />r <br />v <br />O <br />O <br />NON -CONTROLLED <br />NOTES: <br />I. ALL CONTROLLED RECEPTACLES AND/OR COVER PLATES SHALL BE <br />PROVIDED WITH FACTORY ENGRAVED LABELS INDICATING TOP OUTLET AS <br />'CONTROLLED' AND BOTTOM OUTLET AS 'NON -CONTROLLED'. <br />2. CIRCUIT NUMBER SHALL BE INDICATED WITH A TYPED SELF-ADHESIVE BACKED <br />LABEL WITH CLEAR BACKGROUND AND CHARACTERS OF CONTRASTING COLOR <br />TO COVER PLATE (BLACK OR WHITE CHARACTERS). <br />3. FOR CLARITY, NOT ALL EQUIPMENT GROUNDS ARE SHOWN. <br />4. PROVIDE ISOLATED GROUND RECEPTACLE AND IG CONDUCTOR WHEN SPECIFIED <br />ON PLAN DRAWINGS AND PANEL SCHEDULES. <br />5. CONTROLLED RECEPTACLES SHALL BE FACTORY MARKED WITH THE <br />CONTROLLED RECEPTACLE SYMBOL [NEC 406.31. <br />HALF SWITCHED PLUG <br />6 LOAD WIRING DIAGRAM <br />v <br />D <br />- XX <br />Revisions Date By <br />Mark A. Jonnatti <br />Florida AR 0010778 <br />JONNATTI <br />ARCHITECTURE <br />INCORPORATED <br />21021 US Highway 19 N <br />Clearwater, Florida 33765 <br />(727) 725-ARCH <br />(727) 725-2603 fx <br />www.jarch.com <br />info@jarch.com <br />© jonnatti Architecture <br />Incorporated 2021 <br />OF•FLO <br />�o/V • .y <br />SIR 1107PI III <br />•an.. <br />S/6/21 <br />"i `"- • M <br />r , •• •• a <br />• •,.. <br />:. ,. <br />Tru lit VqU <br />INTERIOR <br />REMODEL <br />US H" 301 <br />GALL BLVD <br />ZEPHYRHILLS <br />FLORIDA <br />33542 <br />ELECTRICAL <br />DETAILS <br />OTES AND <br />AILS <br />(Draw7nMAI <br />Check <br />MAI <br />Date <br />AUG 31, 2021 <br />EScaleAS <br />NOTED <br />TRULIEVE-ZH <br />Sheet: <br />EOOO <br />NOT TO SCALE <br />0.0/ NOT TO SCALE <br />