HANGER STRAPS: 1 "x 22 GAUGE, <br />FLEXIBLE DUCT: <br />SUPPORTED FROM STRUCTURE ABOVE, INSULATED, MAXIMUM <br />(3) SHEET METAL SCREWS BELOW <br />8'-0" DO NOT SAG OR <br />KINK <br />WRAP INSULATION: OVER- <br />ROUND SELF-SEALING <br />WIRE SUPPORTS <br />LAP 4" MINIMUM, STAPLE & <br />DUCT EQUAL TO <br />TO PREVENT SAGS <br />TAPE FOR VAPOR SEAL <br />SPIROSAFE; WRAP w/ <br />AND KINKS IN FLEX <br />2" DUCT INSULATION; <br />SEAL INSULATION w/ <br />GLASS FABRIC/MASTIC <br />ARE <br />TAPE AND <br />BAND CLAMP AND <br />IDE <br />:FREE <br />I MASTIC OUTER <br />THREE SHEET <br />EA <br />JACKET, TYP <br />METAL SCREWS <br />ONS — <br />— — — — — — — — <br />THROUGH HELIX OF <br />FLEXIBLE DUCT <br />MINIMUM RADIUS EQUAL <br />LINER, TYP <br />SECURE INSULATION w/ <br />TO THE FLEX DUCT <br />STICK -PINS AT 18" OC <br />DIAMETER <br />AND ADHESIVE ON <br />BOTTOM, FOR DUCTS 24" <br />AND LARGER <br />MAXIMUM <br />VERTICAL DUCT <br />—mil <br />l� <br />CONICAL SPIN -IN FITTING <br />;RUN <br />w/ VOLUME DAMPER <br />EQUAL TO CROWN <br />PRODUCTS MODEL 3200-DS <br />(SEE SPECS FOR OTHER DESIGNER: <br />OPTIONS) BE AWARE OF DIFFUSER TYPE AND <br />SHEETMETAL CONSTRUCTION. <br />DUCT FABRICATION NOTES: <br />1. DUCTS SHALL BE FABRICATED & INSTALLED PER THE LATEST EDITION OF SMACNA DUCT <br />CONSTRUCTION STANDARDS. <br />2. ALTERNATE INTERPRETATIONS OF SMACNA DUCT MATERIAL, HANGERS AND REINFORCEMENTS <br />ARE SUBJECT TO ENGINEER APPROVAL, AND REQUIRE SEPARATE SUBMITTAL OF THE <br />ALTERNATES. <br />3. FLEXIBLE DUCT CONNECTORS SHALL BE PROVIDED WHERE SHOWN ON THE PLAN. <br />4. SUPPLY AIR DROPS FROM ROOF TOP UNITS SHALL TRANSITION FROM THE UNIT OPENING SIZE TO <br />SQUARE NECK ELBOWS, w/ SIZES AS SHOWN ON THE PLAN. IF TWO SUPPLY AIR DUCT RUNS ARE <br />AT THE UNIT, THEN TWO SEPARATE DROPS & ELBOWS SHALL BE PROVIDED. <br />5. RETURN AIR DROPS FROM THE ROOF TOP UNITS SHALL BE FULL SIZE OF THE UNIT OPENING. <br />6. ELBOWS SHALL BE SQUARE NECK (SAME IN OUT DIMENSION) w/ 2" DOUBLE THICKNESS TURNING <br />VANES. <br />7. OFFSETS SHALL NOT REDUCE THE FREE AREA, AND SHALL NOT EXCEED 30 A RADIUS HEEL <br />SHALL BE PROVIDED ON 300 OFFSETS. SMALLER OFFSETS SHALL BE MITERED AT BOTH THE HEEL <br />& THROAT. <br />8. TRANSITIONS SHALL NOT EXCEED 1:3 RATIO (4" TRANSITION PER FOOT SINGLE SIDED TRANSITION, <br />AND 8" PER FOOT DOUBLE SIDED TRANSITION). <br />9. INSULATION SHALL BE NFPA 90 APPROVED, w/ MINIMUM R-VALUE OF 4.2. WRAP INSULATION SHALL <br />BE 2" THICK w/ ALUMINUM FOIL FACING. LINER SHALL BE 1" THICK, 1-1/2 PCF DENSITY. <br />10. RECTANGULAR BRANCH CONNECTIONS SHALL BE 450 ENTRY TYPE PER SMACNA FIGURE 2-6. <br />11. ROUND DUCT CONNECTIONS SHALL BE w/ "CROWN PRODUCTS COMPANY" 3200-DS FITTINGS, <br />DAMPER AND HANDLE. SPRAY PAINT LOCATIONS OF HANDLES. <br />12. FLEXIBLE DUCT SHALL INCLUDE AN INNER POLYETHYLENE LINER, A SPRING HELIX, 1-1/4" BLANKET <br />INSULATION (R-6.0), A FOIL OUTER VAPOR BARRIER, AND BE UL LISTED CLASS I AIR DUCT. <br />13. SEAL ALL SUPPLY, RETURN & OUTSIDE AIR DUCT JOINTS w/ DUCT SEALER; SEAL ALL INSULATION <br />JOISTS w/ GLASS FABRIC AND MASTIC. <br />CONCEALED DUCTWORK INSTALLATION DETAIL (SHEET <br />METAL) <br />SCALE: NTS <br />PROVIDE COLLAR WHERE <br />DUCTS PASS THRU WALL <br />BLADE AND LINK CINCH <br />17- <br />1 <br />i I <br />� I <br />L---J <br />ACCESS <br />PANEL <br />FIRE —RATED <br />STRUCTURE <br />20 GA STEEL BLADES w/ <br />INTERLOCKING JOINTS <br />PROVIDE CLOSURE SPRING <br />AND LATCHES FOR <br />HORIZONTAL INSTALLATION <br />ROUND OR <br />RECTANGULAR <br />i DUCT <br />FUSIBLE LINK (165°F) <br />22 GA STEEL MOUNTING COLLAR <br />BREAK -AWAY CONNECTION <br />1 1/2"xl 1/2"xl/8" STEEL ANGLE <br />FASTENED TO COLLAR ONLY <br />w/ #10 SCREWS, TYP <br />DYNAMIC FIRE DAMPER DETAIL <br />SCALE: NTS <br />FANP_� <br />-- \ <br />HANGER SUPPORTS: 1"x 22 GA, <br />DO NOT SUPPORT FROM CEILING <br />INTEGRAL BACKDRAFT DAMPER <br />�— VARIABLE SPEED CONTROLLER <br />MARK w/ THE "AS BALANCED <br />POSITION" (DIRECT DRIVE UNITS) <br />DISCONNECT SWITCH: FURNISHED <br />BY MECHANICAL CONTRACTOR OR <br />FAN MANUFACTURER <br />CEILING <br />CEILING MOUNTED FAN DETAIL <br />SCALE: NTS <br />T/MIr+AI Ol1llC -r^M I Mrr <br />1" COND w/ 2" P-TRAP <br />FLEX CONN, TYP <br />GASKET CONN <br />ROOF DECK <br />FUL <br />DUCT, <br />AND BEAM <br />TYPICAL ROOF MOUNTED UNIT <br />SCALE: NTS <br />INTAKE FILTER <br />OA INTAKE <br />RY CURB <br />SMOKE DETECTOR <br />CEILING <br />JED DUCT, SEE PLAN <br />STRAP HANGARS <br />FiANGEK — <br />STRAPS <br />60" MAX <br />SCREWS MAY <br />BE OMITTED IF 1" MIN <br />HANGAR <br />LOOPS UNDER <br />DUCT <br />HANGAR <br />FLOAD RA" <br />FASTENE <br />FASTENEI <br />36" 0 MAX <br />BAND OF SAME SIZE <br />AS HANGER STRAP <br />UNLESS FOOT OF <br />STRAP IS PLACED <br />UNDER A BOTTOM <br />DUCT REINFORCEMENT <br />24" 0 MAX <br />CURE <br />WIRE <br />SEE <br />10" 0 MAX <br />— HANGER RODS, — <br />WIRES OR STRAPS <br />TRAPEZE HANGARS <br />SIZE BOLT(S) FOR LOAD <br />ROD <br />NUTS `—ANGLES <br />ALTERNATE <br />LOCATION - <br />GENERAL NOTES: <br />1. DETAILS BASED ON SMACNA 1995, FIG. 4-4. <br />2. DUCT REINFORCEMENT MAY BE USED FOR ATTACHMENT IF IT <br />QUALIFIES FOR BOTH DUTIES. <br />3. DO NOT EXCEED SMACNA, CH. 4, ALLOWABLE LOAD LIMITS. <br />4. HANGERS MUST NOT DEFORM DUCT SHAPE. <br />BAND, ONE—HALF ROUND, <br />MAY BE USED IF DUCT <br />SHAPE IS MAINTAINED <br />DUCT SUPPORT DETAIL <br />SCALE: NTS <br />MECHANICAL SUBCONTRACTOR <br />SHALL PROVIDE ITEMS <br />NOTED BELOW <br />ROOFTOP UNIT <br />GASKET AND <br />SILICONE SEALING <br />PRESSURE —TREATED <br />WOOD NAILER STRIP <br />FACTORY CURB: NRCA <br />APPROVED, 18 GAGE, SQUARE <br />WIN 1/8" ON DIAGONAL <br />MEASUREMENT, w/ A MINIMUM <br />OF 8" ABOVE TOP OF ROOF <br />CURB SET DIRECTLY ON STEEL - <br />MECH UNIT BASE <br />GASKET & SEALANT <br />2410 TEK SCREWS @ 24" <br />PT 2x WOOD NAILER <br />STRUCTURAL STEEL ANGLE <br />CURB <br />HEIGHT <br />= 14" <br />GENERAL CONTRACTOR <br />SHALL PROVIDE ITEMS <br />NOTED BELOW <br />SEE DETAIL A -A <br />COUNTER FLASHING STRIP <br />1" RIGID INSULATION <br />3" CANT STRIP <br />ROOFING <br />ROOF INSULATION <br />— METAL DECKING <br />STRUCTURAL SUPPORT FRAME <br />FOR UNIT & DECKING AT FULL <br />PERIMETER OF FACTORY CURB <br />12 GA ANGLE w/ 1-8" LEGS <br />0'-6" LG @ 24" (2 MIN PER SIDE) <br />w/ 2410 TEK SCREWS EACH LEG <br />ROOFING & <br />FLASHING, SEE ARCH <br />�—#10 TEK SCREWS @ 12" OC <br />OR 1-8" FILLET WELD @ 12" <br />DETAIL A -A <br />NOTES: <br />1. MECHANICAL SUBCONTRACTOR SHALL FURNISH ROOF OPENING SIZES & <br />LOCATIONS, FOR STRUCTURAL SUPPORT FRAMING BY GENERAL <br />CONTRACTOR. <br />2. THIS CURB DETAIL WILL ALLOW THE UNIT TO SLOPE w/ THE SLOPE OF THE <br />ROOF PITCH. THIS DETAIL CAN ONLY BE USED: <br />A. IF THE CONDENSATE DRAIN PAN OUTLET IS ON THE LOW SIDE OFTHE UNIT, <br />OR <br />B. IF THE CONDENSATE DRAIN PAN IS NOT AFFECTED BY SLOPE. THIS DETAIL <br />CAN NOT BE USED IF THE CONDENSATE DRAIN CONNECTION IS ON THE <br />HIGH SIDE OF THE UNIT. <br />3. COORDINATE THIS DETAIL w/ ARCHITECTURAL APPLICATIONS FOR THE ROOF. <br />r6 <br />ROOFTOP UNIT CURB DETAIL <br />SCALE: NTS <br />15 ' <br />i®�� <br />` STATE OF <br />170NAL E���� <br />4*. <br />MOVE IGH &MANGUM <br />ENGINEERING INC <br />Atlanta • Charlotte • Jacksonville Raleigh <br />www.McVeighMangum.com <br />1955 Lake Park Drive SE, Suite 325 <br />Smyrna, Georgia 30080 <br />Ph: (678) 213-1616 <br />email: mail@,McVeigWangum.com <br />PEF005182 <br />Eng. of Record: KENNETHGONZALEZ LicenseNo.:61015 <br />VON <br />J <br />Roswell Mill <br />85-A Mill Street, Suite 200 <br />Roswell, Georgia 30015 <br />t 110.�i50.1558 f 710.fi50.1559 <br />e-mail architects@randallpaulson.com <br />These plans and specifications are the property of Randall -Paulson Architects, <br />Incorporated. These documents may not he copied, reproduced, used or <br />implemented in any way, in part Orin whole, without the written consent of <br />Randall -Paulson Architects, Incorporated. All common law rights of copyright are <br />hereby specifically reserved. <br />TENANT <br />BUILD -OUT <br />at <br />ZEPHYRHILLS <br />for <br />U.S. HIGHWAY 301 & PRETTY <br />POND ROAD, <br />ZEPHYRHILLS, FLORIDA 33541 <br />Print Record <br />Revisions <br />Date Project No. <br />14 JUNE 2021 2021217.00 <br />Sheet Title <br />DETAILS <br />Sheet No. <br />M=400 <br />Released for Construction <br />❑Not Released for Construction <br />