18/2 WIRING FROM POWER PACKS, SEE DETAIL C3 THIS SHEET. WIRE
<br />TO COMMON AND NORMALLY CLOSED (NC) TERMINALS. WIRING FROM
<br />POWER PACK TO TERMINAL STRIP BY CONTRACTOR.
<br />NORTHLIGHT RELAY MODULE RLY08M DMX ADDRESS 451
<br />LINE VOLTAGE CONTROL SCHEDULE
<br />ID DMX # DESCRIPTION CIRCUIT
<br />1 451 FANS LEFT WING 2. 452 FANS CENTER WING -
<br />3 453 FANS RIGHT WING -
<br />4 454 EONS-ZONEA -
<br />5 455 EONS - ZONE B
<br />6 456 EONS - ZONE C -
<br />7 457 EONS - ZONED -
<br />LIGHTING CONTROL SCHEDULE
<br />DESCRIPTION MANUFACTURER PART NUMBER LOCATION
<br />TOUCHSCREEN CONTROLLER W/BACK BOX PHAROS HID-PH-TPC ON ENCLOSURE LID
<br />DMX AND INPUT MODULE PHAROS HID-PH-EXT IN ENCLOSURE
<br />LPC PROCESSOR PHAROS HID-PHLPC IN ENCLOSURE
<br />ENCLOSURE 28" LEVITON HID-LE-47605-28N ENCLOSURE
<br />ENCLOSURE LID LEVITON HID-LE-47605-28S ENCLOSURE
<br />DMX TO CONTACT CLOSURE 8 CHANNEL NORTHLIGHT DMX HID-NL-RLY08M IN ENCLOSURE
<br />SURGE PROTECTED OUTLET LEVITON POW-LE-47605-ACS IN ENCLOSURE
<br />DIN RAIL - HID-SE-16-700DIN IN ENCLOSURE
<br />CAT 5 PATCH CABLES - HID-CI-73-7791-1 IN ENCLOSURE
<br />1 INPUT MODULE 0-10V OR CC - 24 RELAYS PATHWAY HID-PA-1006 IN ENCLOSURE
<br />24V POWER SUPPLY MEANWELL POW-MW-DR-4524 IN ENCLOSURE
<br />! PLUG 3' - POW-MW-DR-4524
<br />I POE INJECTOR TP-LINK TL-PoE150S
<br />I TERMINAL STRIP 28 POSITION ALTECH -
<br />i OCCUPANCY WALL SENSOR DOUGLAS LIGHTING CONTROLS HID-DG-WOSSDD2-DPR-VW ITEM SENT DIRECTLY TO SITE
<br />i WATTSTOPPERS WATTSTOPPER HID-WS-BZ-50 ITEM SENT DIRECTLY TO SITE
<br />WALL SWITCHES LEVITON HID-LE-DCRA-ON/OFF ITEM SENT DIRECTLY TO SITE
<br />I WALL DIMMERS LUTRON HID-LU-DVTV ITEM SENT DIRECTLY TO SITE
<br />TO DIMMING TERMINAL
<br />STRIP FOR ANALOG
<br />MODULE - IN CONTROL
<br />CABINET.
<br />TO LIGHT FIXTURES. TO LIGHT FIXTURES..
<br />MAX 2 FIXTURES PER MAX 2 FIXTURES PERCHANNEL. WIRED IN
<br />CHANNEL. WIRED IN SERIES.
<br />SAMPLE CONTROL WIRING FOR
<br />EON POWER SUPPLIES. SEE
<br />SHEET E1.0 FOR ZONE
<br />DESIGNATIONS.
<br />EON POWER SUPPLY DIMMING AND FIXTURE WIRING DETAIL i c-n
<br />Ls—o.a
<br />1814 TO TERMINAL STRIP
<br />FOR INPUT MODULE IN CFO
<br />CONTROL CABINET
<br />OCCUPANCY SENSOR WIRING DETAIL (C-15
<br />Ls-oa
<br />It
<br />DO
<br />CAT5E DMX
<br />CONTROL
<br />CABLE
<br />DAISY
<br />CHAINED
<br />THROUGH
<br />ALL TRINITY
<br />POWER
<br />SUPPLIES.
<br />WIRING BY
<br />CONTRACTOR.
<br />O O
<br />0 O
<br />0
<br />0
<br />O
<br />0 0
<br />O 0
<br />0 0
<br />0 0
<br />0 0
<br />0 0
<br />0
<br />0
<br />0
<br />0
<br />0 0
<br />0 0
<br />000
<br />Q
<br />o a
<br />O O
<br />O 0 0 0
<br />e
<br />oa
<br />O 0
<br />O 0
<br />O O 0
<br />se
<br />0 e®
<br />O 0 0
<br />O 0 0
<br />O O O
<br />O O O
<br />00 O 0 0
<br />O O O
<br />O 0 0
<br />O
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 0 0
<br />O 0 O 0
<br />O 0 O 0
<br />so � +Za a�
<br />Oa -sag o za o®
<br />�O+L06 31tl XWO x+sd O®
<br />6!o zoS � —z-sa o4
<br />�O Z4 i10.--NO � O®
<br />4<a s +za o®
<br />®a z � !� x—Z4 O�
<br />�o r �+sa o®
<br />Q{O b �—s0 O®
<br />�a O�
<br />�a s +
<br />®O L _ hC
<br />�O 8 Z � expo
<br />NPu
<br />®o zs"
<br />0
<br />�a Fs .
<br />oa ti� � A
<br />®a Sl � ®®•Q
<br />�O u �
<br />�a
<br />00 8t m c�
<br />!a oz
<br />pa �z
<br />�o zz©� o®
<br />4•o sz _� a®
<br />®o az
<br />�a POD] � +n a®
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 o O o
<br />a a
<br />120Y AC
<br />PARED BY CONTRACTOR. M
<br />CIRCUIT A-1
<br />120V AC
<br />HARED BY CONTRACTOR.
<br />TO CIRCUIT A-1
<br />01
<br />WRING BY
<br />CONTRACTOR.
<br />18 4 TO 351
<br />18 4 TO 352
<br />18 1 TO 353
<br />18 2 TO 354
<br />18 2 TO 355
<br />n
<br />De
<br />GENERAL NOTES;
<br />1) INSTALLATION SHALL BE IN ACCORDANCE W/ LOCAL, STATE,
<br />PROVINCIAL, COUNTY &NEC REGULATIONS.
<br />2) THIS DOCUMENT IS FOR REFERENCE ONLY, USE IN CONJUNCTION WITH COMPONENT
<br />INSTALLATION. INSTRUCTIONS.
<br />3) CONDUIT REQUIRED FOR LIFE SAFETY LIGHTING.
<br />4) CHECK LOCAL JURISDICTION FOR THE REQUIRED USE OF CONDUIT ON SYSTEMS HIGHER
<br />THAN 24 VOLTS.
<br />5) SPECIFICATIONS SUBJECT TO CHANGE W/0 PRIOR NOTICE.
<br />6) UON, ALL WIRING SHOWN. IS TO BE INSTALLED AND CONNECTED BY CONTRACTOR.
<br />PATHWAY 1006 DMX ADDRESS 351
<br />INPUTSCHEDULE
<br />ID DMX # LOCATION
<br />1 351 MENS ROOM OCC
<br />2 352 WOMENS ROOM OCC.
<br />3 353 LEFT WING
<br />4 354 CENTER WING
<br />5 355 RIGHT WING
<br />6 356 NOT USED
<br />7 357 NOT USED
<br />8 358 NOT USED
<br />9 359 NOT USED
<br />10 360 NOT USED
<br />11 361 NOT USED
<br />12 362 NOT USED
<br />13 363 NOT USED
<br />14 364 NOT USED
<br />15 365 NOT USED
<br />16 366 NOT USED
<br />17 367 NOT USED
<br />18 368 NOT USED
<br />19 369 NOT USED
<br />20 370 NOT USED
<br />21 371 NOT USED
<br />22 372 NOT USED
<br />23 373 NOT USED
<br />24 374 NOT USED
<br />IN THIS CONFIGURATION WHEN CONTROLLING MULTIPLE
<br />CIRCUITS WTH A SINGLE RELAY.
<br />SEE DETAIL C15 THIS SHEET FOR OCCUPANCY
<br />SENSOR WIRING.
<br />WIRE 18/2 TO LUMASTREAM PROVIDED SWTCHES.
<br />THE SWITCHES ACTS AS CONTACT CLOSURE INPUTS
<br />FOR THE LIGHTING CONTROL SYSTEM.
<br />18/2 TO TERMINAL STRIP
<br />FOR RELAY MODULE IN
<br />CONTROL CABINET(n
<br />TO LOAD
<br />TO BREAKEI
<br />CHART THIS
<br />SINGLE POWER PACK WIRING —WIRE POWER PACK IN
<br />THIS CONFIGURATION WHEN CONTROLLING A SINGLE
<br />CIRCUITS -WITH A SINGLE RELAY.
<br />SWITCHING POWER PACK (WATTSTOPPER BZ-50) WIRING DETAIL
<br />EMERALD
<br />ENGINEERING INC.
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 1 FLORIDA EB# 0027845
<br />WWW.EMERALDMEP.COM EEI PROJECT* 180822
<br />0.
<br />t+
<br />a
<br />00
<br />T
<br />0
<br />N
<br />ti
<br />T
<br />1
<br />aS c
<br />e e
<br />ADWY WWELL, PE
<br />FL. REG. NO. PE73853
<br />LIGHTING CONTROL SCHEDULE
<br />DESCRIPTION MANUFACTURER PART NUMBER LOCATION
<br />TOUCHSCREEN CONTROLLER W/BACK BOX PHAROS HID-PH-TPC ON ENCLOSURE LID
<br />DMX AND INPUT MODULE PHAROS HID-PH-EXT IN ENCLOSURE
<br />LPC PROCESSOR PHAROS HID-PHLPC IN ENCLOSURE
<br />ENCLOSURE 28" LEVITON HID-LE-47605-28N ENCLOSURE
<br />ENCLOSURE LID LEVITON HID-LE-47605-28S ENCLOSURE
<br />DMX TO CONTACT CLOSURE 8 CHANNEL NORTHLIGHT DMX HID-NL-RLY08M IN ENCLOSURE
<br />SURGE PROTECTED OUTLET LEVITON POW-LE-47605-ACS IN ENCLOSURE
<br />DIN RAIL - HID-SE-16-700DIN IN ENCLOSURE
<br />CAT 5 PATCH CABLES - HID-CI-73-7791-1 IN ENCLOSURE
<br />1 INPUT MODULE 0-10V OR CC - 24 RELAYS PATHWAY HID-PA-1006 IN ENCLOSURE
<br />24V POWER SUPPLY MEANWELL POW-MW-DR-4524 IN ENCLOSURE
<br />! PLUG 3' - POW-MW-DR-4524
<br />I POE INJECTOR TP-LINK TL-PoE150S
<br />I TERMINAL STRIP 28 POSITION ALTECH -
<br />i OCCUPANCY WALL SENSOR DOUGLAS LIGHTING CONTROLS HID-DG-WOSSDD2-DPR-VW ITEM SENT DIRECTLY TO SITE
<br />i WATTSTOPPERS WATTSTOPPER HID-WS-BZ-50 ITEM SENT DIRECTLY TO SITE
<br />WALL SWITCHES LEVITON HID-LE-DCRA-ON/OFF ITEM SENT DIRECTLY TO SITE
<br />I WALL DIMMERS LUTRON HID-LU-DVTV ITEM SENT DIRECTLY TO SITE
<br />TO DIMMING TERMINAL
<br />STRIP FOR ANALOG
<br />MODULE - IN CONTROL
<br />CABINET.
<br />TO LIGHT FIXTURES. TO LIGHT FIXTURES..
<br />MAX 2 FIXTURES PER MAX 2 FIXTURES PERCHANNEL. WIRED IN
<br />CHANNEL. WIRED IN SERIES.
<br />SAMPLE CONTROL WIRING FOR
<br />EON POWER SUPPLIES. SEE
<br />SHEET E1.0 FOR ZONE
<br />DESIGNATIONS.
<br />EON POWER SUPPLY DIMMING AND FIXTURE WIRING DETAIL i c-n
<br />Ls—o.a
<br />1814 TO TERMINAL STRIP
<br />FOR INPUT MODULE IN CFO
<br />CONTROL CABINET
<br />OCCUPANCY SENSOR WIRING DETAIL (C-15
<br />Ls-oa
<br />It
<br />DO
<br />CAT5E DMX
<br />CONTROL
<br />CABLE
<br />DAISY
<br />CHAINED
<br />THROUGH
<br />ALL TRINITY
<br />POWER
<br />SUPPLIES.
<br />WIRING BY
<br />CONTRACTOR.
<br />O O
<br />0 O
<br />0
<br />0
<br />O
<br />0 0
<br />O 0
<br />0 0
<br />0 0
<br />0 0
<br />0 0
<br />0
<br />0
<br />0
<br />0
<br />0 0
<br />0 0
<br />000
<br />Q
<br />o a
<br />O O
<br />O 0 0 0
<br />e
<br />oa
<br />O 0
<br />O 0
<br />O O 0
<br />se
<br />0 e®
<br />O 0 0
<br />O 0 0
<br />O O O
<br />O O O
<br />00 O 0 0
<br />O O O
<br />O 0 0
<br />O
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 0 0
<br />O 0 O 0
<br />O 0 O 0
<br />so � +Za a�
<br />Oa -sag o za o®
<br />�O+L06 31tl XWO x+sd O®
<br />6!o zoS � —z-sa o4
<br />�O Z4 i10.--NO � O®
<br />4<a s +za o®
<br />®a z � !� x—Z4 O�
<br />�o r �+sa o®
<br />Q{O b �—s0 O®
<br />�a O�
<br />�a s +
<br />®O L _ hC
<br />�O 8 Z � expo
<br />NPu
<br />®o zs"
<br />0
<br />�a Fs .
<br />oa ti� � A
<br />®a Sl � ®®•Q
<br />�O u �
<br />�a
<br />00 8t m c�
<br />!a oz
<br />pa �z
<br />�o zz©� o®
<br />4•o sz _� a®
<br />®o az
<br />�a POD] � +n a®
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 o O o
<br />a a
<br />120Y AC
<br />PARED BY CONTRACTOR. M
<br />CIRCUIT A-1
<br />120V AC
<br />HARED BY CONTRACTOR.
<br />TO CIRCUIT A-1
<br />01
<br />WRING BY
<br />CONTRACTOR.
<br />18 4 TO 351
<br />18 4 TO 352
<br />18 1 TO 353
<br />18 2 TO 354
<br />18 2 TO 355
<br />n
<br />De
<br />GENERAL NOTES;
<br />1) INSTALLATION SHALL BE IN ACCORDANCE W/ LOCAL, STATE,
<br />PROVINCIAL, COUNTY &NEC REGULATIONS.
<br />2) THIS DOCUMENT IS FOR REFERENCE ONLY, USE IN CONJUNCTION WITH COMPONENT
<br />INSTALLATION. INSTRUCTIONS.
<br />3) CONDUIT REQUIRED FOR LIFE SAFETY LIGHTING.
<br />4) CHECK LOCAL JURISDICTION FOR THE REQUIRED USE OF CONDUIT ON SYSTEMS HIGHER
<br />THAN 24 VOLTS.
<br />5) SPECIFICATIONS SUBJECT TO CHANGE W/0 PRIOR NOTICE.
<br />6) UON, ALL WIRING SHOWN. IS TO BE INSTALLED AND CONNECTED BY CONTRACTOR.
<br />PATHWAY 1006 DMX ADDRESS 351
<br />INPUTSCHEDULE
<br />ID DMX # LOCATION
<br />1 351 MENS ROOM OCC
<br />2 352 WOMENS ROOM OCC.
<br />3 353 LEFT WING
<br />4 354 CENTER WING
<br />5 355 RIGHT WING
<br />6 356 NOT USED
<br />7 357 NOT USED
<br />8 358 NOT USED
<br />9 359 NOT USED
<br />10 360 NOT USED
<br />11 361 NOT USED
<br />12 362 NOT USED
<br />13 363 NOT USED
<br />14 364 NOT USED
<br />15 365 NOT USED
<br />16 366 NOT USED
<br />17 367 NOT USED
<br />18 368 NOT USED
<br />19 369 NOT USED
<br />20 370 NOT USED
<br />21 371 NOT USED
<br />22 372 NOT USED
<br />23 373 NOT USED
<br />24 374 NOT USED
<br />IN THIS CONFIGURATION WHEN CONTROLLING MULTIPLE
<br />CIRCUITS WTH A SINGLE RELAY.
<br />SEE DETAIL C15 THIS SHEET FOR OCCUPANCY
<br />SENSOR WIRING.
<br />WIRE 18/2 TO LUMASTREAM PROVIDED SWTCHES.
<br />THE SWITCHES ACTS AS CONTACT CLOSURE INPUTS
<br />FOR THE LIGHTING CONTROL SYSTEM.
<br />18/2 TO TERMINAL STRIP
<br />FOR RELAY MODULE IN
<br />CONTROL CABINET(n
<br />TO LOAD
<br />TO BREAKEI
<br />CHART THIS
<br />SINGLE POWER PACK WIRING —WIRE POWER PACK IN
<br />THIS CONFIGURATION WHEN CONTROLLING A SINGLE
<br />CIRCUITS -WITH A SINGLE RELAY.
<br />SWITCHING POWER PACK (WATTSTOPPER BZ-50) WIRING DETAIL
<br />EMERALD
<br />ENGINEERING INC.
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 1 FLORIDA EB# 0027845
<br />WWW.EMERALDMEP.COM EEI PROJECT* 180822
<br />0.
<br />t+
<br />a
<br />00
<br />T
<br />0
<br />N
<br />ti
<br />T
<br />1
<br />aS c
<br />e e
<br />ADWY WWELL, PE
<br />FL. REG. NO. PE73853
<br />TO DIMMING TERMINAL
<br />STRIP FOR ANALOG
<br />MODULE - IN CONTROL
<br />CABINET.
<br />TO LIGHT FIXTURES. TO LIGHT FIXTURES..
<br />MAX 2 FIXTURES PER MAX 2 FIXTURES PERCHANNEL. WIRED IN
<br />CHANNEL. WIRED IN SERIES.
<br />SAMPLE CONTROL WIRING FOR
<br />EON POWER SUPPLIES. SEE
<br />SHEET E1.0 FOR ZONE
<br />DESIGNATIONS.
<br />EON POWER SUPPLY DIMMING AND FIXTURE WIRING DETAIL i c-n
<br />Ls—o.a
<br />1814 TO TERMINAL STRIP
<br />FOR INPUT MODULE IN CFO
<br />CONTROL CABINET
<br />OCCUPANCY SENSOR WIRING DETAIL (C-15
<br />Ls-oa
<br />It
<br />DO
<br />CAT5E DMX
<br />CONTROL
<br />CABLE
<br />DAISY
<br />CHAINED
<br />THROUGH
<br />ALL TRINITY
<br />POWER
<br />SUPPLIES.
<br />WIRING BY
<br />CONTRACTOR.
<br />O O
<br />0 O
<br />0
<br />0
<br />O
<br />0 0
<br />O 0
<br />0 0
<br />0 0
<br />0 0
<br />0 0
<br />0
<br />0
<br />0
<br />0
<br />0 0
<br />0 0
<br />000
<br />Q
<br />o a
<br />O O
<br />O 0 0 0
<br />e
<br />oa
<br />O 0
<br />O 0
<br />O O 0
<br />se
<br />0 e®
<br />O 0 0
<br />O 0 0
<br />O O O
<br />O O O
<br />00 O 0 0
<br />O O O
<br />O 0 0
<br />O
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 0 0
<br />O 0 O 0
<br />O 0 O 0
<br />so � +Za a�
<br />Oa -sag o za o®
<br />�O+L06 31tl XWO x+sd O®
<br />6!o zoS � —z-sa o4
<br />�O Z4 i10.--NO � O®
<br />4<a s +za o®
<br />®a z � !� x—Z4 O�
<br />�o r �+sa o®
<br />Q{O b �—s0 O®
<br />�a O�
<br />�a s +
<br />®O L _ hC
<br />�O 8 Z � expo
<br />NPu
<br />®o zs"
<br />0
<br />�a Fs .
<br />oa ti� � A
<br />®a Sl � ®®•Q
<br />�O u �
<br />�a
<br />00 8t m c�
<br />!a oz
<br />pa �z
<br />�o zz©� o®
<br />4•o sz _� a®
<br />®o az
<br />�a POD] � +n a®
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 o O o
<br />a a
<br />120Y AC
<br />PARED BY CONTRACTOR. M
<br />CIRCUIT A-1
<br />120V AC
<br />HARED BY CONTRACTOR.
<br />TO CIRCUIT A-1
<br />01
<br />WRING BY
<br />CONTRACTOR.
<br />18 4 TO 351
<br />18 4 TO 352
<br />18 1 TO 353
<br />18 2 TO 354
<br />18 2 TO 355
<br />n
<br />De
<br />GENERAL NOTES;
<br />1) INSTALLATION SHALL BE IN ACCORDANCE W/ LOCAL, STATE,
<br />PROVINCIAL, COUNTY &NEC REGULATIONS.
<br />2) THIS DOCUMENT IS FOR REFERENCE ONLY, USE IN CONJUNCTION WITH COMPONENT
<br />INSTALLATION. INSTRUCTIONS.
<br />3) CONDUIT REQUIRED FOR LIFE SAFETY LIGHTING.
<br />4) CHECK LOCAL JURISDICTION FOR THE REQUIRED USE OF CONDUIT ON SYSTEMS HIGHER
<br />THAN 24 VOLTS.
<br />5) SPECIFICATIONS SUBJECT TO CHANGE W/0 PRIOR NOTICE.
<br />6) UON, ALL WIRING SHOWN. IS TO BE INSTALLED AND CONNECTED BY CONTRACTOR.
<br />PATHWAY 1006 DMX ADDRESS 351
<br />INPUTSCHEDULE
<br />ID DMX # LOCATION
<br />1 351 MENS ROOM OCC
<br />2 352 WOMENS ROOM OCC.
<br />3 353 LEFT WING
<br />4 354 CENTER WING
<br />5 355 RIGHT WING
<br />6 356 NOT USED
<br />7 357 NOT USED
<br />8 358 NOT USED
<br />9 359 NOT USED
<br />10 360 NOT USED
<br />11 361 NOT USED
<br />12 362 NOT USED
<br />13 363 NOT USED
<br />14 364 NOT USED
<br />15 365 NOT USED
<br />16 366 NOT USED
<br />17 367 NOT USED
<br />18 368 NOT USED
<br />19 369 NOT USED
<br />20 370 NOT USED
<br />21 371 NOT USED
<br />22 372 NOT USED
<br />23 373 NOT USED
<br />24 374 NOT USED
<br />IN THIS CONFIGURATION WHEN CONTROLLING MULTIPLE
<br />CIRCUITS WTH A SINGLE RELAY.
<br />SEE DETAIL C15 THIS SHEET FOR OCCUPANCY
<br />SENSOR WIRING.
<br />WIRE 18/2 TO LUMASTREAM PROVIDED SWTCHES.
<br />THE SWITCHES ACTS AS CONTACT CLOSURE INPUTS
<br />FOR THE LIGHTING CONTROL SYSTEM.
<br />18/2 TO TERMINAL STRIP
<br />FOR RELAY MODULE IN
<br />CONTROL CABINET(n
<br />TO LOAD
<br />TO BREAKEI
<br />CHART THIS
<br />SINGLE POWER PACK WIRING —WIRE POWER PACK IN
<br />THIS CONFIGURATION WHEN CONTROLLING A SINGLE
<br />CIRCUITS -WITH A SINGLE RELAY.
<br />SWITCHING POWER PACK (WATTSTOPPER BZ-50) WIRING DETAIL
<br />EMERALD
<br />ENGINEERING INC.
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 1 FLORIDA EB# 0027845
<br />WWW.EMERALDMEP.COM EEI PROJECT* 180822
<br />0.
<br />t+
<br />a
<br />00
<br />T
<br />0
<br />N
<br />ti
<br />T
<br />1
<br />aS c
<br />e e
<br />ADWY WWELL, PE
<br />FL. REG. NO. PE73853
<br />0
<br />0
<br />O
<br />0 0
<br />O 0
<br />0 0
<br />0 0
<br />0 0
<br />0 0
<br />0
<br />0
<br />0
<br />0
<br />0 0
<br />0 0
<br />000
<br />Q
<br />o a
<br />O O
<br />O 0 0 0
<br />e
<br />oa
<br />O 0
<br />O 0
<br />O O 0
<br />se
<br />0 e®
<br />O 0 0
<br />O 0 0
<br />O O O
<br />O O O
<br />00 O 0 0
<br />O O O
<br />O 0 0
<br />O
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 0 0
<br />O 0 O 0
<br />O 0 O 0
<br />so � +Za a�
<br />Oa -sag o za o®
<br />�O+L06 31tl XWO x+sd O®
<br />6!o zoS � —z-sa o4
<br />�O Z4 i10.--NO � O®
<br />4<a s +za o®
<br />®a z � !� x—Z4 O�
<br />�o r �+sa o®
<br />Q{O b �—s0 O®
<br />�a O�
<br />�a s +
<br />®O L _ hC
<br />�O 8 Z � expo
<br />NPu
<br />®o zs"
<br />0
<br />�a Fs .
<br />oa ti� � A
<br />®a Sl � ®®•Q
<br />�O u �
<br />�a
<br />00 8t m c�
<br />!a oz
<br />pa �z
<br />�o zz©� o®
<br />4•o sz _� a®
<br />®o az
<br />�a POD] � +n a®
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 o O o
<br />a a
<br />120Y AC
<br />PARED BY CONTRACTOR. M
<br />CIRCUIT A-1
<br />120V AC
<br />HARED BY CONTRACTOR.
<br />TO CIRCUIT A-1
<br />01
<br />WRING BY
<br />CONTRACTOR.
<br />18 4 TO 351
<br />18 4 TO 352
<br />18 1 TO 353
<br />18 2 TO 354
<br />18 2 TO 355
<br />n
<br />De
<br />GENERAL NOTES;
<br />1) INSTALLATION SHALL BE IN ACCORDANCE W/ LOCAL, STATE,
<br />PROVINCIAL, COUNTY &NEC REGULATIONS.
<br />2) THIS DOCUMENT IS FOR REFERENCE ONLY, USE IN CONJUNCTION WITH COMPONENT
<br />INSTALLATION. INSTRUCTIONS.
<br />3) CONDUIT REQUIRED FOR LIFE SAFETY LIGHTING.
<br />4) CHECK LOCAL JURISDICTION FOR THE REQUIRED USE OF CONDUIT ON SYSTEMS HIGHER
<br />THAN 24 VOLTS.
<br />5) SPECIFICATIONS SUBJECT TO CHANGE W/0 PRIOR NOTICE.
<br />6) UON, ALL WIRING SHOWN. IS TO BE INSTALLED AND CONNECTED BY CONTRACTOR.
<br />PATHWAY 1006 DMX ADDRESS 351
<br />INPUTSCHEDULE
<br />ID DMX # LOCATION
<br />1 351 MENS ROOM OCC
<br />2 352 WOMENS ROOM OCC.
<br />3 353 LEFT WING
<br />4 354 CENTER WING
<br />5 355 RIGHT WING
<br />6 356 NOT USED
<br />7 357 NOT USED
<br />8 358 NOT USED
<br />9 359 NOT USED
<br />10 360 NOT USED
<br />11 361 NOT USED
<br />12 362 NOT USED
<br />13 363 NOT USED
<br />14 364 NOT USED
<br />15 365 NOT USED
<br />16 366 NOT USED
<br />17 367 NOT USED
<br />18 368 NOT USED
<br />19 369 NOT USED
<br />20 370 NOT USED
<br />21 371 NOT USED
<br />22 372 NOT USED
<br />23 373 NOT USED
<br />24 374 NOT USED
<br />IN THIS CONFIGURATION WHEN CONTROLLING MULTIPLE
<br />CIRCUITS WTH A SINGLE RELAY.
<br />SEE DETAIL C15 THIS SHEET FOR OCCUPANCY
<br />SENSOR WIRING.
<br />WIRE 18/2 TO LUMASTREAM PROVIDED SWTCHES.
<br />THE SWITCHES ACTS AS CONTACT CLOSURE INPUTS
<br />FOR THE LIGHTING CONTROL SYSTEM.
<br />18/2 TO TERMINAL STRIP
<br />FOR RELAY MODULE IN
<br />CONTROL CABINET(n
<br />TO LOAD
<br />TO BREAKEI
<br />CHART THIS
<br />SINGLE POWER PACK WIRING —WIRE POWER PACK IN
<br />THIS CONFIGURATION WHEN CONTROLLING A SINGLE
<br />CIRCUITS -WITH A SINGLE RELAY.
<br />SWITCHING POWER PACK (WATTSTOPPER BZ-50) WIRING DETAIL
<br />EMERALD
<br />ENGINEERING INC.
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 1 FLORIDA EB# 0027845
<br />WWW.EMERALDMEP.COM EEI PROJECT* 180822
<br />0.
<br />t+
<br />a
<br />00
<br />T
<br />0
<br />N
<br />ti
<br />T
<br />1
<br />aS c
<br />e e
<br />ADWY WWELL, PE
<br />FL. REG. NO. PE73853
<br />0
<br />0
<br />0
<br />0
<br />0 0
<br />0 0
<br />000
<br />Q
<br />o a
<br />O O
<br />O 0 0 0
<br />e
<br />oa
<br />O 0
<br />O 0
<br />O O 0
<br />se
<br />0 e®
<br />O 0 0
<br />O 0 0
<br />O O O
<br />O O O
<br />00 O 0 0
<br />O O O
<br />O 0 0
<br />O
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 0 0
<br />O 0 O 0
<br />O 0 O 0
<br />so � +Za a�
<br />Oa -sag o za o®
<br />�O+L06 31tl XWO x+sd O®
<br />6!o zoS � —z-sa o4
<br />�O Z4 i10.--NO � O®
<br />4<a s +za o®
<br />®a z � !� x—Z4 O�
<br />�o r �+sa o®
<br />Q{O b �—s0 O®
<br />�a O�
<br />�a s +
<br />®O L _ hC
<br />�O 8 Z � expo
<br />NPu
<br />®o zs"
<br />0
<br />�a Fs .
<br />oa ti� � A
<br />®a Sl � ®®•Q
<br />�O u �
<br />�a
<br />00 8t m c�
<br />!a oz
<br />pa �z
<br />�o zz©� o®
<br />4•o sz _� a®
<br />®o az
<br />�a POD] � +n a®
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 o O o
<br />a a
<br />120Y AC
<br />PARED BY CONTRACTOR. M
<br />CIRCUIT A-1
<br />120V AC
<br />HARED BY CONTRACTOR.
<br />TO CIRCUIT A-1
<br />01
<br />WRING BY
<br />CONTRACTOR.
<br />18 4 TO 351
<br />18 4 TO 352
<br />18 1 TO 353
<br />18 2 TO 354
<br />18 2 TO 355
<br />n
<br />De
<br />GENERAL NOTES;
<br />1) INSTALLATION SHALL BE IN ACCORDANCE W/ LOCAL, STATE,
<br />PROVINCIAL, COUNTY &NEC REGULATIONS.
<br />2) THIS DOCUMENT IS FOR REFERENCE ONLY, USE IN CONJUNCTION WITH COMPONENT
<br />INSTALLATION. INSTRUCTIONS.
<br />3) CONDUIT REQUIRED FOR LIFE SAFETY LIGHTING.
<br />4) CHECK LOCAL JURISDICTION FOR THE REQUIRED USE OF CONDUIT ON SYSTEMS HIGHER
<br />THAN 24 VOLTS.
<br />5) SPECIFICATIONS SUBJECT TO CHANGE W/0 PRIOR NOTICE.
<br />6) UON, ALL WIRING SHOWN. IS TO BE INSTALLED AND CONNECTED BY CONTRACTOR.
<br />PATHWAY 1006 DMX ADDRESS 351
<br />INPUTSCHEDULE
<br />ID DMX # LOCATION
<br />1 351 MENS ROOM OCC
<br />2 352 WOMENS ROOM OCC.
<br />3 353 LEFT WING
<br />4 354 CENTER WING
<br />5 355 RIGHT WING
<br />6 356 NOT USED
<br />7 357 NOT USED
<br />8 358 NOT USED
<br />9 359 NOT USED
<br />10 360 NOT USED
<br />11 361 NOT USED
<br />12 362 NOT USED
<br />13 363 NOT USED
<br />14 364 NOT USED
<br />15 365 NOT USED
<br />16 366 NOT USED
<br />17 367 NOT USED
<br />18 368 NOT USED
<br />19 369 NOT USED
<br />20 370 NOT USED
<br />21 371 NOT USED
<br />22 372 NOT USED
<br />23 373 NOT USED
<br />24 374 NOT USED
<br />IN THIS CONFIGURATION WHEN CONTROLLING MULTIPLE
<br />CIRCUITS WTH A SINGLE RELAY.
<br />SEE DETAIL C15 THIS SHEET FOR OCCUPANCY
<br />SENSOR WIRING.
<br />WIRE 18/2 TO LUMASTREAM PROVIDED SWTCHES.
<br />THE SWITCHES ACTS AS CONTACT CLOSURE INPUTS
<br />FOR THE LIGHTING CONTROL SYSTEM.
<br />18/2 TO TERMINAL STRIP
<br />FOR RELAY MODULE IN
<br />CONTROL CABINET(n
<br />TO LOAD
<br />TO BREAKEI
<br />CHART THIS
<br />SINGLE POWER PACK WIRING —WIRE POWER PACK IN
<br />THIS CONFIGURATION WHEN CONTROLLING A SINGLE
<br />CIRCUITS -WITH A SINGLE RELAY.
<br />SWITCHING POWER PACK (WATTSTOPPER BZ-50) WIRING DETAIL
<br />EMERALD
<br />ENGINEERING INC.
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 1 FLORIDA EB# 0027845
<br />WWW.EMERALDMEP.COM EEI PROJECT* 180822
<br />0.
<br />t+
<br />a
<br />00
<br />T
<br />0
<br />N
<br />ti
<br />T
<br />1
<br />aS c
<br />e e
<br />ADWY WWELL, PE
<br />FL. REG. NO. PE73853
<br />0 0 0 0
<br />0 0 0 0
<br />0 0 o O o
<br />a a
<br />120Y AC
<br />PARED BY CONTRACTOR. M
<br />CIRCUIT A-1
<br />120V AC
<br />HARED BY CONTRACTOR.
<br />TO CIRCUIT A-1
<br />01
<br />WRING BY
<br />CONTRACTOR.
<br />18 4 TO 351
<br />18 4 TO 352
<br />18 1 TO 353
<br />18 2 TO 354
<br />18 2 TO 355
<br />n
<br />De
<br />GENERAL NOTES;
<br />1) INSTALLATION SHALL BE IN ACCORDANCE W/ LOCAL, STATE,
<br />PROVINCIAL, COUNTY &NEC REGULATIONS.
<br />2) THIS DOCUMENT IS FOR REFERENCE ONLY, USE IN CONJUNCTION WITH COMPONENT
<br />INSTALLATION. INSTRUCTIONS.
<br />3) CONDUIT REQUIRED FOR LIFE SAFETY LIGHTING.
<br />4) CHECK LOCAL JURISDICTION FOR THE REQUIRED USE OF CONDUIT ON SYSTEMS HIGHER
<br />THAN 24 VOLTS.
<br />5) SPECIFICATIONS SUBJECT TO CHANGE W/0 PRIOR NOTICE.
<br />6) UON, ALL WIRING SHOWN. IS TO BE INSTALLED AND CONNECTED BY CONTRACTOR.
<br />PATHWAY 1006 DMX ADDRESS 351
<br />INPUTSCHEDULE
<br />ID DMX # LOCATION
<br />1 351 MENS ROOM OCC
<br />2 352 WOMENS ROOM OCC.
<br />3 353 LEFT WING
<br />4 354 CENTER WING
<br />5 355 RIGHT WING
<br />6 356 NOT USED
<br />7 357 NOT USED
<br />8 358 NOT USED
<br />9 359 NOT USED
<br />10 360 NOT USED
<br />11 361 NOT USED
<br />12 362 NOT USED
<br />13 363 NOT USED
<br />14 364 NOT USED
<br />15 365 NOT USED
<br />16 366 NOT USED
<br />17 367 NOT USED
<br />18 368 NOT USED
<br />19 369 NOT USED
<br />20 370 NOT USED
<br />21 371 NOT USED
<br />22 372 NOT USED
<br />23 373 NOT USED
<br />24 374 NOT USED
<br />IN THIS CONFIGURATION WHEN CONTROLLING MULTIPLE
<br />CIRCUITS WTH A SINGLE RELAY.
<br />SEE DETAIL C15 THIS SHEET FOR OCCUPANCY
<br />SENSOR WIRING.
<br />WIRE 18/2 TO LUMASTREAM PROVIDED SWTCHES.
<br />THE SWITCHES ACTS AS CONTACT CLOSURE INPUTS
<br />FOR THE LIGHTING CONTROL SYSTEM.
<br />18/2 TO TERMINAL STRIP
<br />FOR RELAY MODULE IN
<br />CONTROL CABINET(n
<br />TO LOAD
<br />TO BREAKEI
<br />CHART THIS
<br />SINGLE POWER PACK WIRING —WIRE POWER PACK IN
<br />THIS CONFIGURATION WHEN CONTROLLING A SINGLE
<br />CIRCUITS -WITH A SINGLE RELAY.
<br />SWITCHING POWER PACK (WATTSTOPPER BZ-50) WIRING DETAIL
<br />EMERALD
<br />ENGINEERING INC.
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 1 FLORIDA EB# 0027845
<br />WWW.EMERALDMEP.COM EEI PROJECT* 180822
<br />0.
<br />t+
<br />a
<br />00
<br />T
<br />0
<br />N
<br />ti
<br />T
<br />1
<br />aS c
<br />e e
<br />ADWY WWELL, PE
<br />FL. REG. NO. PE73853
<br />n
<br />De
<br />GENERAL NOTES;
<br />1) INSTALLATION SHALL BE IN ACCORDANCE W/ LOCAL, STATE,
<br />PROVINCIAL, COUNTY &NEC REGULATIONS.
<br />2) THIS DOCUMENT IS FOR REFERENCE ONLY, USE IN CONJUNCTION WITH COMPONENT
<br />INSTALLATION. INSTRUCTIONS.
<br />3) CONDUIT REQUIRED FOR LIFE SAFETY LIGHTING.
<br />4) CHECK LOCAL JURISDICTION FOR THE REQUIRED USE OF CONDUIT ON SYSTEMS HIGHER
<br />THAN 24 VOLTS.
<br />5) SPECIFICATIONS SUBJECT TO CHANGE W/0 PRIOR NOTICE.
<br />6) UON, ALL WIRING SHOWN. IS TO BE INSTALLED AND CONNECTED BY CONTRACTOR.
<br />PATHWAY 1006 DMX ADDRESS 351
<br />INPUTSCHEDULE
<br />ID DMX # LOCATION
<br />1 351 MENS ROOM OCC
<br />2 352 WOMENS ROOM OCC.
<br />3 353 LEFT WING
<br />4 354 CENTER WING
<br />5 355 RIGHT WING
<br />6 356 NOT USED
<br />7 357 NOT USED
<br />8 358 NOT USED
<br />9 359 NOT USED
<br />10 360 NOT USED
<br />11 361 NOT USED
<br />12 362 NOT USED
<br />13 363 NOT USED
<br />14 364 NOT USED
<br />15 365 NOT USED
<br />16 366 NOT USED
<br />17 367 NOT USED
<br />18 368 NOT USED
<br />19 369 NOT USED
<br />20 370 NOT USED
<br />21 371 NOT USED
<br />22 372 NOT USED
<br />23 373 NOT USED
<br />24 374 NOT USED
<br />IN THIS CONFIGURATION WHEN CONTROLLING MULTIPLE
<br />CIRCUITS WTH A SINGLE RELAY.
<br />SEE DETAIL C15 THIS SHEET FOR OCCUPANCY
<br />SENSOR WIRING.
<br />WIRE 18/2 TO LUMASTREAM PROVIDED SWTCHES.
<br />THE SWITCHES ACTS AS CONTACT CLOSURE INPUTS
<br />FOR THE LIGHTING CONTROL SYSTEM.
<br />18/2 TO TERMINAL STRIP
<br />FOR RELAY MODULE IN
<br />CONTROL CABINET(n
<br />TO LOAD
<br />TO BREAKEI
<br />CHART THIS
<br />SINGLE POWER PACK WIRING —WIRE POWER PACK IN
<br />THIS CONFIGURATION WHEN CONTROLLING A SINGLE
<br />CIRCUITS -WITH A SINGLE RELAY.
<br />SWITCHING POWER PACK (WATTSTOPPER BZ-50) WIRING DETAIL
<br />EMERALD
<br />ENGINEERING INC.
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 1 FLORIDA EB# 0027845
<br />WWW.EMERALDMEP.COM EEI PROJECT* 180822
<br />0.
<br />t+
<br />a
<br />00
<br />T
<br />0
<br />N
<br />ti
<br />T
<br />1
<br />aS c
<br />e e
<br />ADWY WWELL, PE
<br />FL. REG. NO. PE73853
<br />IN THIS CONFIGURATION WHEN CONTROLLING MULTIPLE
<br />CIRCUITS WTH A SINGLE RELAY.
<br />SEE DETAIL C15 THIS SHEET FOR OCCUPANCY
<br />SENSOR WIRING.
<br />WIRE 18/2 TO LUMASTREAM PROVIDED SWTCHES.
<br />THE SWITCHES ACTS AS CONTACT CLOSURE INPUTS
<br />FOR THE LIGHTING CONTROL SYSTEM.
<br />18/2 TO TERMINAL STRIP
<br />FOR RELAY MODULE IN
<br />CONTROL CABINET(n
<br />TO LOAD
<br />TO BREAKEI
<br />CHART THIS
<br />SINGLE POWER PACK WIRING —WIRE POWER PACK IN
<br />THIS CONFIGURATION WHEN CONTROLLING A SINGLE
<br />CIRCUITS -WITH A SINGLE RELAY.
<br />SWITCHING POWER PACK (WATTSTOPPER BZ-50) WIRING DETAIL
<br />EMERALD
<br />ENGINEERING INC.
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 1 FLORIDA EB# 0027845
<br />WWW.EMERALDMEP.COM EEI PROJECT* 180822
<br />0.
<br />t+
<br />a
<br />00
<br />T
<br />0
<br />N
<br />ti
<br />T
<br />1
<br />aS c
<br />e e
<br />ADWY WWELL, PE
<br />FL. REG. NO. PE73853
<br />0
<br />m
<br />N
<br />s
<br />J
<br />Q
<br />Q
<br />N
<br />N
<br />N
<br />■
<br />BSB
<br />DESIGN
<br />www.bsbdesign.comL S
<br />100 Main St. Suite 209
<br />Safety Harbor, Florida 34695
<br />8132654808
<br />JOB NO: AM180320.00 PROJ MGR:
<br />DRAWN: DS CHECKED:
<br />CONTROL
<br />
|