R502.5 Allowable girder spans.
<br />The allowable spans of girders fabricated of dimension lumber shall not
<br />exceed the values set forth in Tables R502. 5( 1) and R502. 5(2).
<br />TABLE R502. 5( 1)
<br />GIRDER SPANSa AND HEADER SPANSO FOR EXTERIOR BEARING WALLS
<br />(Maximum spans for Douglas fir -larch, hem -fir, southern pine
<br />and spruce-pine-firb and required number of jack studs)
<br />GIRDERS AND HEADERS
<br />SUPPORTING
<br />SIZE
<br />Building widthc (feet)
<br />20
<br />28
<br />36
<br />SPAN
<br />Njd
<br />SPAN
<br />Njd
<br />SPAN
<br />NJ
<br />Roof and ceiling
<br />2-2x4
<br />3-6
<br />1
<br />3-2
<br />1
<br />2-10
<br />1
<br />2-2x6
<br />5-5
<br />1
<br />4-8
<br />1
<br />4-2
<br />1
<br />2-2x8
<br />6-10
<br />1
<br />5-11
<br />2
<br />5-4
<br />2
<br />2-2x10
<br />8-5
<br />2
<br />7-3
<br />2
<br />6-6
<br />1 2
<br />2-2x12
<br />9-9
<br />2
<br />8-5
<br />2
<br />7-6
<br />2
<br />3-2x8
<br />8-4
<br />1
<br />7-5
<br />1
<br />6-8
<br />1
<br />3-2x10
<br />10-6
<br />1
<br />9-1
<br />2
<br />8-2
<br />2
<br />3-2x12
<br />12-2
<br />2
<br />10-7
<br />2
<br />9-5
<br />2
<br />4-2x8
<br />9-2
<br />1
<br />8-4
<br />1
<br />7-8
<br />1 2
<br />4-2x10
<br />11-8
<br />1
<br />10-6
<br />1
<br />9-5
<br />2
<br />4-2x12
<br />14-1
<br />1
<br />12-2
<br />2
<br />10-11
<br />2
<br />Roof, cei 1 ing and one
<br />center -bearing floor
<br />2-2x4
<br />3-1
<br />1
<br />2-9
<br />1
<br />2-5
<br />1
<br />2-2x6
<br />4-6
<br />1
<br />4-0
<br />1
<br />3-7
<br />2
<br />2-2x8
<br />5-9
<br />2
<br />5-0
<br />2
<br />4-6
<br />1 2
<br />2-2x10
<br />7-0
<br />2
<br />6-2
<br />2
<br />5-6
<br />2
<br />2-2x12
<br />8-1
<br />2
<br />7-1
<br />2
<br />6-5
<br />2
<br />3-2x8
<br />7-2
<br />1
<br />6-3
<br />2
<br />5-8
<br />2
<br />3-2x10
<br />8-9
<br />2
<br />7-8
<br />2
<br />6-11
<br />2
<br />3-2x12
<br />10-2
<br />2
<br />8-11
<br />2
<br />8-0
<br />1 2
<br />4-2x8
<br />8-1
<br />1
<br />7-3
<br />1
<br />6-7
<br />2
<br />4-2x10
<br />10-1
<br />1
<br />8-10
<br />2
<br />8-0
<br />2
<br />4-2x12
<br />11-9
<br />2
<br />10-3
<br />2
<br />9-3
<br />2
<br />Roof, ceiling and one
<br />clear span floor
<br />2-2x4
<br />2-8
<br />1
<br />2-3
<br />1
<br />2-0
<br />1
<br />2-2x6
<br />3-11
<br />2
<br />3-3
<br />2
<br />2-11
<br />2
<br />2-2x8
<br />5-0
<br />2
<br />4-2
<br />3
<br />3-9
<br />2
<br />2-2x10
<br />6-1
<br />2
<br />5-1
<br />3
<br />4-7
<br />3
<br />2-2x12
<br />7-1
<br />3
<br />5-10
<br />3
<br />5-3
<br />3
<br />3-2x8
<br />6-3
<br />2
<br />5-2
<br />2
<br />4-8
<br />2
<br />3-2x10
<br />7-7
<br />2
<br />6-4
<br />1 2
<br />5-8
<br />2
<br />3-2x12
<br />8-10
<br />2
<br />7-4
<br />3
<br />6-7
<br />2
<br />4-2x8
<br />7-2
<br />1
<br />6-0
<br />2
<br />5-5
<br />2
<br />4-2x10
<br />8-9
<br />2
<br />7-4
<br />2
<br />6-7
<br />2
<br />4-2x12
<br />10-2
<br />2
<br />8-6
<br />2
<br />7-8
<br />2
<br />Roof, ceiling and two
<br />center -bearing floors
<br />2-2x4
<br />2-7
<br />1
<br />2-3
<br />1
<br />2-0
<br />1
<br />2-2x6
<br />3-9
<br />2
<br />3-3
<br />2
<br />2-11
<br />2
<br />2-2x8
<br />4-9
<br />2
<br />4-2
<br />2
<br />3-9
<br />2
<br />2-2x10
<br />5-9
<br />2
<br />5-1
<br />2
<br />4-7 1
<br />3
<br />2-2x12
<br />6-8
<br />2
<br />5-10
<br />3
<br />5-3
<br />3
<br />3-2x8
<br />5-11
<br />2
<br />5-2
<br />1 2
<br />4-8
<br />2
<br />3-2x10
<br />7-3
<br />2
<br />6-4
<br />2
<br />5-8
<br />2
<br />3-2x12
<br />8-5
<br />2
<br />7-4
<br />2
<br />6-7
<br />2
<br />4-2x8
<br />6-10
<br />1
<br />6-0
<br />2
<br />5-5
<br />2
<br />4-2x10
<br />8-4
<br />2
<br />7-4
<br />2
<br />6-7 1
<br />2
<br />4-2x12
<br />9-8
<br />2
<br />8-6
<br />2
<br />7-8
<br />2
<br />Roof, ceiling and two
<br />clear span floor
<br />2-2x4
<br />2-1
<br />1
<br />1-8
<br />1
<br />1-6
<br />2
<br />2-2x6
<br />3-1
<br />2
<br />2-8
<br />2
<br />2-4
<br />2
<br />2-2x8
<br />3-10
<br />2
<br />3-4
<br />2
<br />3-0
<br />3
<br />2-2x10
<br />4-9 1
<br />2
<br />4-1
<br />3
<br />3-8 1
<br />3
<br />2-2x12
<br />5-6
<br />2
<br />4-9
<br />3
<br />4-3
<br />3
<br />3-2x8
<br />4-10
<br />2
<br />4-2
<br />2
<br />3-9
<br />2
<br />3-2x10
<br />5-11
<br />2
<br />5-1
<br />2
<br />4-7
<br />2
<br />3-2x12
<br />6-10
<br />2
<br />5-11
<br />3
<br />5-4
<br />2
<br />4-2x8
<br />5-7
<br />2
<br />4-10
<br />2
<br />4-4
<br />2
<br />4-2x10
<br />6-10
<br />2
<br />5-11
<br />2
<br />5-3
<br />2
<br />4-2x12
<br />7-11
<br />2
<br />6-10
<br />2
<br />6-2
<br />3
<br />For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m2.
<br />a. Spans are given in feet and inches.
<br />b. Tabulated values assume #2 grade lumber.
<br />c. Building width is measured perpendicular to the ridge. For widths between
<br />those shown, spans are permitted to be interpolated.
<br />d. NJ - Number of jack studs required to support each end. Where the number of
<br />required jack studs equals one, the header is permitted to be supported
<br />by an approved framing anchor attached to the full -height wall stud and to the
<br />header.
<br />e. Reserved.
<br />ROOF SHEATHING FASTENING SCHEDULE a b,c,d,e
<br />kid Common (0.13I x 2-1/2 Inches) or Ring -Shank (0.135, X 2-1/2 Inches)
<br />(Except Uklere Noted) for Exposure B, Enclosed l5ulldinge, Roof Framing Spaced 24 inches
<br />o.c. or Lee&
<br />Roof Fastening Zone
<br />Overhang
<br />Wind
<br />Main
<br />Sheathing -to -Gable
<br />(eaves)
<br />Velocfty
<br />Roof
<br />End -Wall Framingg
<br />(3-9econd
<br />Panel
<br />1
<br />2
<br />3
<br />2 3
<br />2
<br />3
<br />Gust)
<br />Location
<br />Fastening schedule (inches on center)
<br />Supported Panel
<br />6
<br />6
<br />6
<br />6
<br />6
<br />150 mph f,g
<br />and and edges
<br />3h
<br />Panel field
<br />6
<br />4
<br />3
<br />4
<br />3
<br />Supported Panel
<br />6
<br />6
<br />6
<br />6
<br />fo
<br />120 mph F9
<br />and and edges
<br />3
<br />Panel field
<br />12
<br />6
<br />4
<br />6
<br />4
<br />Supported Panel
<br />6
<br />6
<br />6
<br />6
<br />6
<br />90 mph
<br />and and edges
<br />6
<br />Panel field
<br />12
<br />12
<br />6
<br />6
<br />fo
<br />a. Specific gravltg (G) of lumber and panels shall be 0.42 or greater.
<br />b. For Exposure B and a 2-foot overhang.
<br />C. For median roof height 35 feet or less.
<br />.I- Caabla all halgk,�t of 8 feat or lees from top floor callincr] to roof peak
<br />e. Provide adequate uplift hardware at trues -to -wail connections. Such
<br />connections are beyond the scope of this publication.
<br />f. When wind speed la 110 mph or greater and when median roof height is between
<br />25 and 35 feet, use &d ring shank nails (0.135 x 2-1/2 InchasAuithfn 48 Inches of
<br />gable and walla. (IRC Table W23, footnote f)
<br />g. When wind speed is 100 mph or greater, block panel edges perpendicular to
<br />gable -end -well framing members In the first two bays of framing. Blocking shall be
<br />spaced a maximum of 4 feet o.c. (Wood Frame Construction Manual, section 3b.5)
<br />h. 10d ring -shank nails (0.145x 3 Inches).
<br />i. Blocking not required.
<br />TABLE R301. 5
<br />MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS
<br />(in pounds per square foot)
<br />USE
<br />LIVE LOAD
<br />Uninhabitable attics without storage b,g
<br />10
<br />Uninhabitable attics with limited storage b,g
<br />20
<br />Habitable attics and attics served with fixed stairs
<br />30
<br />Balconies (exterior) and decks e
<br />40
<br />Fire escapes
<br />40
<br />Guardrails and handrails d
<br />200h
<br />Guardrail in -fill components f
<br />50h
<br />Passenger vehicle garages a
<br />50a
<br />Rooms other than sleeping room
<br />40
<br />Sleeping rooms
<br />30
<br />Stairs
<br />40c
<br />For SI: 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2,
<br />1 pound = 4.45 N.
<br />a. Elevated garage floors shall be capable of supporting a 2,000-pound load applied over a 20-square-inch area.
<br />b. Uninhabitable attics without storage are those where the maximum clear height between joists and rafters is less than 42
<br />inches, or where there are not two or more adjacent trusses with web configurations capable of accommodating an assumed
<br />rectangle 42 inches high by 24 inches in width, or greater, within the plane of the trusses. This live load need not be
<br />assumed to act concurrently with any other live load requirements.
<br />c. Individual stair treads shall be designed for the uniformly distributed live load or a 300-pound concentrated load
<br />acting over an area of 4 square inches, whichever produces the greater stresses,
<br />d. A single concentrated load applied in any direction at any point along the top.
<br />e. See Section R502.2 for decks attached to exterior walls,
<br />f. Guard in -fill components (all those except the handrail), balusters and panel fillers shall be designed to withstand a
<br />horizontally applied normal load of 50 pounds on an area equal to 1 square foot. This load need not be assumed to act
<br />concurrently with any other live load requirement.
<br />g. Uninhabitable attics with limited storage are those where the maximum clear height between joists and rafters is 42
<br />inches or greater, or where there are two or more adjacent trusses with web configurations capable of accommodating an
<br />assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses.
<br />The live load need only be applied to those portions of the joists or truss bottom chords where all of the following
<br />conditions are met:
<br />1. The attic area is accessible from an opening not less than 20 inches in width by 30 inches in length that is located
<br />where the clear height in the attic is a minimum of 30 inches.
<br />2. The slopes of the joists or truss bottom chords are no greater than 2 inches vertical to 12 units horizontal.
<br />3. Required insulation depth is less than the joist or truss bottom chord member depth.
<br />The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live
<br />load of not less than 10 lb/ft2.
<br />h. Glazing used in handrail assemblies and guards shall be designed with a safety factor of 4. The safety factor shall be
<br />applied to each of the concentrated loads applied to the top of the rail, and to the load on the in -fill components. These
<br />loads shall be determined independent of one another, and loads are assumed not to occur with any other live load.
<br />ROOF FASTENING ZONES FOR WIND UPLIFT
<br />Zones 1,2 and 3 shown below Indicate areas of the roof that may have different Fastening
<br />requirements.
<br />GABLE END WALL WALL LINE
<br />OVERHANG 3 OVERHANG .3 OVERHANG
<br />3 G
<br />WALL LINE
<br />2 OVERHANG .. - . .. : '.:.
<br />VE - YERI 1
<br />2:.. .`. 3 2 3F 3 ' 2 3.
<br />-7 }�..... I{ I I I I.
<br />2 2 I I I{
<br />II 2..2�i } }} #I
<br />a I I ..
<br />II I I I} k} .. . {{
<br />II I }} }} }l
<br />II I I }} I} }I
<br />� : I I-IP OCiF d . I CxA�L R�OF I.
<br />III { 1 {}�:
<br />112:} 1 }2 2 1 1 I?)} �I}21 1 }2 2:I 1 12}1
<br />o a s o o
<br />V 2
<br />2
<br />{} } I I 1 I }{
<br />II 2. 1 �2 11 I} 11
<br />�-
<br />2-� I I. i
<br />1.--. .
<br />2} , .... 2 k....
<br />1. i _:' ..... „k'.'^
<br />_ _ yet v� _ _
<br />2 F ::. :::1 2 :.
<br />20 VERHANG
<br />vERH VERH
<br />YWALL LINE 3 OVERHANG 3 OVERHANG
<br />3 OVERHANG WALL LINE GABLE END WALL
<br />Distance a•4 ft. In most cases (10q of least building width or 0.4 times building height,
<br />whichever Is smaller, but not less than either 4% of least building width or 3 ft.)
<br />ROOF D 114f5HR14r111 N141 L INCH SCHEDULE (G148LES)
<br />COLLAR TIE 1X(o (MIN.) EVERY
<br />il
<br />OTHER RAFTER T-mOR LONGER
<br />2511 MIN. LAP 25" MIN. LAP
<br />rf
<br />I I
<br />I
<br />I
<br />I(1) "5 DOWEL
<br />I IN CORNER
<br />I I
<br />I
<br />I • I
<br />I
<br />II (1) 05 DOWEL
<br />II IN CORNER
<br />FOOTING 4 STEi IWALL RE INFORCE" iENT
<br />2X6 VERTICAL SCAB OR KNEEWALL MID -POINT
<br />IN RAFTER W1 RAFTER SPAN LENGTH GREATER
<br />THAN 14 FT OR LONGER.
<br />CONN W1 4-10d NAILS AT TOP 4 HURRICANE
<br />CL iP s BOTTOM.
<br />2X6 (MIN.) NO. 2 YP
<br />SIMPSON L5TA12
<br />(OR EQUAL)
<br />PLYWOOD SHEATHING
<br />(4) lmd 'a RIDGE
<br />BOARD END
<br />TRU55ES BELOW 5HEATHED PRIOR
<br />TO VALLEY FRAMING INSTALLATION
<br />OR &'-0" O.C. TOP CHORD
<br />51MP5ON L6TA12 5TRAP OR 51MP5ON A22 TIE
<br />EA. RAFTER W/ 10-10ol NAILS
<br />(TYP.)
<br />2X6 CONT. W/SLEEPER, CLIPPED
<br />OR STRAPPED TO TRU55 BELOW
<br />�, I 1 I CONY VALLEY FRAMING DETAI
<br />DESCRIPTION OF BUILDING ELEMENTS
<br />NUMBER AND TYPE OF FASTENER
<br />SPACING
<br />AND LOCATION
<br />Roof
<br />3-8d common 2 x 0. 131, ; or
<br />3_10d box (3 x 0. 128. ); or
<br />1.
<br />Blocking between ceiling joists, rafters or trusses to top
<br />3-3" x 0.131" no11a: or
<br />Each and. toenail
<br />plate or other framing below
<br />3-3" 14 gage staples," crown
<br />2-8d common (2}" X 0. 131")
<br />2-3" x 0.131" nails
<br />Each and, toenail
<br />Blocking between rafters or truss not at the wall top plate,
<br />2-3" 14 gage staples
<br />to
<br />rafter or truss
<br />2-15 d common 3 " x 0.162
<br />3-3' x 0.131" nails
<br />End nail
<br />3-3" 14 gage staples
<br />16d common (3j" X 0. 162") 0 6" o. c.
<br />3"x 0.131" nails 0 6" o.c.
<br />Face nail
<br />Flat blocking to truss and web filler
<br />3" 14 gage staples 0 6"o.c.
<br />3-8d common S 2}' X 0. 131") or
<br />3-I0d box (3 x 0.128')or
<br />Each joist,
<br />toenail
<br />2.
<br />Ceiling joists to top plate
<br />3-3" 0.131* nails; or
<br />3-3' 14 gage staples, " crown
<br />3.
<br />Ceiling joist not attached to parallel rafter,
<br />3-16d common (2}" X 0.131")or
<br />4-I0d box (3" x 0.128")or
<br />lope
<br />over partitions (no thrust)
<br />4-3"x 0.131" nails; or
<br />Face Nail
<br />(see Section 2301.2)
<br />4-3' 14 gage staples, ?e" crown
<br />4.
<br />Calling joist attached to parallel rafter (heel joint) (see
<br />Per Section 2301.2
<br />Face nail
<br />Section 2301.2
<br />3-I0d common 3 X 0.148" ;or
<br />5.
<br />Colter tie to rafter
<br />4-I0d box ( 3' x 0. 128" ) ; or
<br />4-3' 0.131" nails; or
<br />Face nail
<br />4-3" 14 gage staples, t'e" crown
<br />3-10d common 3 X 0. 148"); or
<br />8.
<br />Rafter or roof truss to top plate
<br />4-10d box (3' x 0.128");or
<br />(See Section 2301.2)
<br />4-3' 0.131" nails; or
<br />Toenallc
<br />4-3" 14 gage staples, ?S" crown
<br />2-16d common 3 1/2 X 0. 162 ; or
<br />3-I0d box ( 3" x 0. 128" ); or
<br />3-3" 0.131' nails; or
<br />End nail
<br />7.
<br />Roof rafters to ridge valley or hip rafters; or roof
<br />3-3' 14 gage staples, J" crown;or
<br />rafter
<br />to 2-inch ridge beam
<br />3-IOD Common (3'-0. 148"); or
<br />4-16D BOX (3 1/2" xO. 135"); or
<br />4-100 BOX (3" x0. 128"); or
<br />Toenail
<br />4-3" x0. 131" Nails; or
<br />4-3" 14 gage at op les " crown
<br />16d common 3 ] 2 X 0.162
<br />24"o.c. face
<br />nail
<br />8.
<br />Stud to stud (not at braced wall panels)
<br />1 Od common .I ;or
<br />3"x 0.131" nails; or
<br />16"o.c. face
<br />nail
<br />3-3" 14 gage staples, ?," crown
<br />9.
<br />Stud to stud and abutting studs at Intersecting wall
<br />I6d common 3 1/2* X 0.162"
<br />16"o.c. face
<br />nail
<br />16d box 3 1/2- X 0.135" ;or
<br />12"o.c. face
<br />nail
<br />corners
<br />(at braced wall panels)
<br />3 x 0.131 nails; or
<br />3-3' 14 gage staples, ?g" crown
<br />12"o.c. face
<br />nail
<br />10.
<br />Built-up header (2" to 2" header))
<br />i6d common 3 1 2 X 0.162
<br />16"o.c. face
<br />nai)
<br />I6d box 3 1 2 X 0. 135 ; or
<br />I2 o. c. face
<br />nail
<br />11.
<br />Continuous header to atud 4-8d common (21/2. X 0. 131,);
<br />4-8d comm2 1/2' X 0. 131-),-or
<br />Toenail
<br />4-IOd boxon 3 X 0. 128
<br />16d common 3 1 2 X 0. 162 ; or
<br />16 o. c. face
<br />nail
<br />iod common ;or
<br />12.
<br />Top plate to top plate
<br />3"x 0.131" nails; or
<br />12"o.c. face
<br />nail
<br />3" 14 gage staples, ?9" crown
<br />8-16d common 3 1/2" X 0. 162 ; or
<br />Each side of
<br />end joint, face
<br />12-10d box (3" x 0.128");or
<br />nail
<br />13.
<br />Top plate to top plate, at and joints
<br />12-3" 0.131' nails; or
<br />(minimum 24"
<br />lap splice length
<br />12-3' 14 gage staples, ?g" crown
<br />each side of
<br />end joint)
<br />Ifid common 3 ] 2 X 0. 162' or
<br />16 0. c. face
<br />nail
<br />14.
<br />Bottom plate to joist, rim joist, band joist or blocking
<br />15d box 0. 135 ; or
<br />(not at braced wall panels)
<br />3"x 0.131" nails; or
<br />12"o.c. face
<br />nail
<br />3" 14 gage staples, ?6" crown
<br />2-16d common 3 ] 2 X 0. 162 ; or
<br />15.
<br />Bottom plate to joist, rim joist, band joist or blocking
<br />3-I6d box (3 1/2' x 0.135');or
<br />at
<br />braced wall panels
<br />4-3" 0.131" nails; or
<br />Toenail
<br />4-3" 14 gage staples, j6" crown
<br />4-8d common 2 1/2 X 0. 131 ; or
<br />4-10d box (3" x 0.128");or
<br />Toenail
<br />4-3" 0.131* nails; or
<br />4-3" 14 gage staples, ?S" crown
<br />16.
<br />Stud to top or bottom plate
<br />2-16d common 3 1/2* X 0. 162 ; or
<br />3-10d box (3' x 0. 128" ); or
<br />3-3" 0.131" nails; or
<br />End nail
<br />3-3' 14 gage staples, j- crown
<br />17.
<br />Reserved
<br />2-16d common 3 ] 2 X ;or
<br />18.
<br />Top plates, laps at corners and intersections
<br />3-70d box (3' x 0. 128");;or or
<br />3-3' 0.131" nails; or
<br />Face nail
<br />3-3" 14 gage staples,?S" crown
<br />2-8d common 2 1/2" X 0. 131" ; or
<br />19.
<br />]" brace to each stud and plot
<br />2-10d box (3" x 0.128");or
<br />2-3" 0. 131" nails; or
<br />Face nail
<br />3-3" 14 gage staples, &" crown
<br />20.
<br />I"x6"sheathing to each bearing
<br />2-8d common (2 12 X 0. 131);or
<br />Face moll
<br />3-10d box (3" x 0. 128") ; or
<br />1.
<br />1 x8 and wider sheathing to each bearing
<br />3-8d common 2 1 2 X 0.131 ;or
<br />3-I0d box (3' x 0.128");or
<br />Face nail
<br />Floor
<br />3-8d common 2 1 2 X 0. 131 ; or
<br />22.
<br />Joist to sill, top plate, or girder
<br />3-IOd box (3" x 0.128');or
<br />3-3' 0. 131' nails; or
<br />Toenail
<br />3-3" 14 gage staples, ?S" crown
<br />8d common 2 1/2' X 0. 131'); or
<br />23.
<br />Rim joist, band joist, or blocking to top plate, all) or
<br />10d box (3" x 0.128");or
<br />other
<br />framing below
<br />3" 0.131" nails; or
<br />6"o.c., toenail
<br />3. 14 gage staples, ?S' crown
<br />2-8d common 2 1/2- X 0. 131"); or
<br />24.
<br />1"x 6"subfloor or less to each foist
<br />2-10d box (3 " x 0.128" ;or
<br />)
<br />Face Hall
<br />25.
<br />2 subfloor to lolst or girder
<br />2-16d common 3 1 2 X 0.162
<br />Face nail
<br />28.
<br />2" planks lank & beam -floor a roof
<br />2-16d common 3 1/2- X 0.162
<br />Each bearing,
<br />face nail
<br />32" o.c., face
<br />nail at top and
<br />20d common (4"x 0. 192")
<br />bottom
<br />staggered on
<br />opposite sides)
<br />16-d-common ; or
<br />24" o. c. , face no l at top and
<br />27.
<br />Built-up girders and beams, 2. lumber layers
<br />3"x 0. 131" nails; or
<br />bottom
<br />3" 14 gage staples, ?g" crown
<br />staggered on
<br />opposite sides)
<br />2-20d common 4 X 0. 192 -.or
<br />3-1Od box (3' x 0.128");or
<br />Ends and at
<br />each splice, face
<br />3-3" 0.131" nails; or
<br />nail
<br />3-3' 14 gage staples,?" crown
<br />3-16d common ( 3 1/2' X 0. 162); or
<br />4-10d box (3" x 0.128");or
<br />Each joist or
<br />rafter,face nail
<br />28.
<br />Ledger strip supporting joists or rafters
<br />4-3" 0.131" nails; or
<br />4-3" 14 gage stoples, ?S" crown
<br />3-15d common 3 12 X 0. 162 ; or
<br />4-10d box (3" x 0.128");or
<br />End nail
<br />29.
<br />Joist to band Joist or rim joist
<br />4-3" 0.131" nails; or
<br />4-3" 14 gage staples, Ile" crown
<br />3-16d common 3 1/2* X 0. 162 ; or
<br />4-10d box (3' x 0.128');or
<br />End nail
<br />30.
<br />Bridging or blocking to foist, rafter or truss
<br />4-3" 0.131" nulls; or
<br />4-3. 14 gage staples, ?g" crown
<br />Wood structural panels (WSP), subfloor, roof and interior wall
<br />sheathing to framing and particleboard wall sheathing
<br />to framing a
<br />Edges
<br />Intermediate
<br />(inches)
<br />supports
<br />(inches)
<br />6d common or deformed (2" x 0.113")
<br />6
<br />12
<br />subfloor and wall
<br />ad coon or d•farerd 20' •0. 131
<br />(roo/) or ror• 01 (23/•' "0. 1131 nail
<br />6
<br />12
<br />(roof)•
<br />31.
<br />3/8 '- 1/2"
<br />2J'xO.113" nail (subfloor and wall)
<br />6
<br />12
<br />1J" 16 gage staple, ?s" crown
<br />4
<br />8
<br />subfloor and wall
<br />2r x 0.113. nail (roof)
<br />4
<br />8
<br />1 3/4"16 gage staple,"crown(roof)
<br />3
<br />6
<br />80 COMMON (21/2 " x0. 1311; OR
<br />6
<br />12
<br />6D DEFORMED (2' xo.113') (SUBFLOOR AND
<br />32.
<br />19/32 " - 3/4"
<br />WALL)
<br />8d common or deformed (21/2 ' x0. 131 ')
<br />(roof)or RSRS-01 (23/8' xO. 1131 nail
<br />6
<br />12
<br />(roof)d
<br />2(J"xO.113"nail; or
<br />4
<br />8
<br />2" 16 gage staple, ?g"crown
<br />33.
<br />7/8 - 11
<br />10d common (3" x 0. 148"); or
<br />6
<br />12
<br />Other exterior wall sheathing
<br />li" galvanized roofing nail
<br />(&" head dlameter);or
<br />34.
<br />1/2 "fiberboard sheathing b
<br />I}', 16 gage staple with t6"or 1"
<br />3
<br />6
<br />crown
<br />2-20d common 4 X 0. 192 ; or
<br />"
<br />3-10d box (3x 0. 128") ; or
<br />35.
<br />25/32, fiberboard sheathing b
<br />3-3" 0.131" nails; or
<br />3
<br />B
<br />3-3. 14 gage staples. ?6" crown
<br />Wood structural panels, combination subfloor underloyment to framing
<br />36.
<br />3/4 " and less
<br />8d common (2 1/2"x 0. 131"); or
<br />6
<br />12
<br />6d deformed 2"xO. 113"
<br />8d common (2 1/2"x 0.131"); or
<br />6
<br />12
<br />37.
<br />7 8 "- 1"
<br />6d deformed 2"xO.113"
<br />10d common (3" x 0. 148") • or
<br />6
<br />12
<br />38.
<br />1�"- i
<br />8d deformed 2 1 2"xO. 131"
<br />Panel aiding to framing
<br />6d corrosion -resistant siding
<br />( 1j" X 0. 106"); or
<br />6d corrosion -resistant casing (2"X
<br />6
<br />12
<br />39.
<br />1/2, or less
<br />0.099")
<br />8d corrosion -resistant siding
<br />40.
<br />5/8 "
<br />(2 3/8" X 0. 128") ; or
<br />8d corrosion -resistant casing
<br />6
<br />12
<br />( 2 1/2- X 0. 113" )
<br />Interior paneling
<br />4d common (1 1/2"x 0.080"); or
<br />6
<br />12
<br />41.
<br />4d finish 1 1 2" x 0. 072"
<br />_
<br />6d casing (2"x 0.099"); or
<br />6
<br />12
<br />42
<br />a
<br />6d finish(Panel supports at 24"
<br />For S1; 1 inch - 25. 4 mm.
<br />a. Nails spaced at 6 inches at intermediate supports where spans are 48 Inches or more. For nailing of wood structural panel and
<br />particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing.
<br />b. Spacing shall be 8 inches on center on the edges and 12 Inches on center at intermediate supports for nonstructural applications.
<br />Panel supports at 16 inches (20 Inches if strength axis In the long direction of the panel, unless otherwise marked).
<br />c. Where a rafter is fastened to an adjacent parallel ceiling joist in accordance with this schedule and the ceiling joist is
<br />fastened to the top plate in accordance with this schedule, the number of toenails in the rafter shall be permitted to be reduced by
<br />0
<br />C
<br />a.
<br />O
<br />0
<br />C
<br />a�
<br />f�
<br />a�
<br />0
<br />4+
<br />L
<br />a�
<br />C:
<br />L
<br />O
<br />C)
<br />N
<br />O
<br />N
<br />0
<br />(-
<br />Thomas L Digitally signed by T_
<br />Thomas L
<br />Hanson:AO1410 Hanson:A01410D00000
<br />D000001 77EF31 177EF31 B4E000015ADA
<br />Date:2021.05.24 O
<br />B4E000015ADA 08:45:11-04'00' v
<br />U
<br />^I
<br />►mod
<br />N
<br />TWA
<br />PROJECT NO.
<br />2021-115
<br />Signed and sealed by T.L. Hanson YE \\ O 1111111//p//i
<br />using a Digital Signature and date. gf?so N FM1.S,Q`
<br />Printed copies of this document S
<br />are not considered signed and - ~ :
<br />sealed and the signature must be -_ : w -
<br />Iv =
<br />verified on any electronic w to • 2 -;
<br />P '(j
<br />DWG N0.
<br />625
<br />
|