Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan Is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />PEPP <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />L.Ph <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />�94 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />® <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH 1 <br />CHIMES (OPTIONAL) <br />i9 <br />PUSH BUTTON SWITCH (OPTIONAL) <br />FD <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />® 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />tL <br />ELECTRIC PANEL <br />_A*J <br />DISCONNECT SWITCH <br />L J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />GD <br />(1) PHONE LINE, (1) DATA PORT <br />150AI200A INDOOR <br />NEMA1 <br />150 AMP/ <br />200 AMP <br />#14 to lights & outlets <br />812 to appliances and GFI <br />#10 to WH <br />#8 to Range <br />#6 to HVAC <br />so=2�o <br />200=4I0 in 2" Conduit <br />200 amp <br />150 amp <br />UNDERGROUND IDis <br />SERVICE BY POWER CO.---_ <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER 51 <br />Bare Cu Ground <br />NEC 17. 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />BEDROOM 5� <br />`` �7\ \ <br />C 6/ v \ I 1= <br />ROUGH -IN FOR \ <br />OPT. CLG. FAN/ I <br />LIGHT PRE -WIRE I <br />IB <br />S.D C.M <br />VP <br />BEDROOM 4 <br />ROUGH -IN FOR <br />I jh OPT. CLG. FAN/ -- <br />G LIGHT PRE -WIRE <br />-gig T -- <br />� II <br />VP I I <br />MQ <br />I I <br />W.I.C. <br />I <br />RECEPT. <br />FOR ALARM <br />r i SYSTEM <br />S. <br />7L- <br />p," U <br />i <br />OWNER'S SUITE <br />ROUGH -IN FOR I <br />OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />0 <br />BEDROOM 2 <br />/ '/ <br />ROUGH -IN FOR <br />OPT. CLG. FAN/ <br />/ LIGHT PRE -WIRE <br />S.D <br />� <br />I <br />�„- 3 <br />/ II <br />(I <br />LOFT <br />I � \ <br />II <br />\ ROUGH -IN FOR <br />I \ OPT. CLG. FAN/ <br />--I I LIGHT PRE -WIRE <br />II � <br />II � <br />II � <br />II \ <br />II � <br />BEDROOM 3 <br />_"� /2ROUGH-IN FOR <br />OPT. CLG. FAN/ <br />G LIGHT PRE -WIRE <br />SECOND FLOOR ELECTRICAL PLAN - ELEV-Al. <br />SCALE: 14"= V-0" <br />s.+ <br />N <br />t� <br />N <br />C0 <br />C14 <br />r <br />V <br />> w <br />O <br />c o <br />SIC U c14 <br />y cc c >— <br />Gam. <br />y Na <br />Q w N <br />to <br />co <br />e/ -a <br />y ti <br />c E <br />ro 0 <br />1 f..1 <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition. Engineers signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />9) <br />Q <br />p E <br />$ 8p� <br />N 6 C <br />0 <br />of <br />0 <br />1-1 co y <br />to <br />c�i o0 <br />di <br />coNV <br />W LL <br />a <br />cc <br />w a <br />Z <br />JLL� <br />c° <br />`°Y= _ <br />o <br />i <br />W <br />d CV <br />o <br />mWz <br />°°' <br />co_jILw <br />O U <br />W <br />❑❑ <br />z <br />z <br />$ <br />z <br />J <br />o <br />— <br />d. <br />� <br />� <br />z <br />� <br />o <br />+-J <br />U <br />w <br />� <br />A <br />t <br />0 <br />W <br />toUl <br />c <br />QCID <br />�� <br />� e <br />s <br />o <br />c') <br />M <br />y <br />a <br />w <br />L <br />Mp <br />Q2j <br />u <br />.S <br />Z <br />� <br />t� <br />Q <br />U <br />E <br />to <br />�� <br />X <br />Q Y <br />wpac <br />� U <br />Z <br />N <br />L <br />o <br />O <br />K <br />5 <br />Z <br />.W <br />= <br />_ <br />-- <br />U3 <br />to <br />C <br />C <br />Cu <br />Y <br />H� <br />m <br />'0 <br />u. <br />Z <br />>z <br />i <br />W <br />Q <br />W0.LL <br />o <br />U <br />NZ <br />CCD� <br />woa <br />�_u¢ <br />�r <br />a c <br />P4 <br />Uzi <br />O <br />L0 <br />O <br />rn <br />all <br />(a <br />Q <br />M <br />W <br />c� <br />C O <br />:3T" <br />0 <br />O <br />J <br />ca <br />T <br />m <br />O <br />�° <br />N <br />rn <br />Lo <br />00 <br />co <br />o <br />CD <br />CD <br />LO <br />M <br />Q <br />LO <br />oo <br />ui <br />m <br />E O <br />C7 <br />N <br />0 <br />Z <br />c <br />a0 <br />E <br />_j <br />a <br />�? <br />0 <br />c <br />JOB <br />NO: <br />22-09413 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4.1 <br />