Laserfiche WebLink
1 2 3 4 5 6 7 8 9 10 11 12 13 14 <br />1"1 <br />K <br />J <br />F <br />i <br />D � <br />1 <br />1 <br />1 <br />1 <br />1 <br />1 <br />1 <br />1 <br />C � <br />1 <br />1 <br />1 <br />1 <br />—A1 <br />Y <br />1 <br />1 <br />1 <br />1 <br />8 � <br />1 <br />1 <br />1 <br />A <br />ABBREVIATIONS <br />A <br />AMPERE <br />AF <br />AMPERE FRAME <br />AFF <br />ABOVE FINISHED FLOOR <br />AFG <br />ABOVE FINISHED GRADE <br />AHU <br />AIR HANDLING UNIT <br />AL <br />ALUMINUM <br />ATS <br />AUTOMATIC TRANSFER SWITCH <br />AWG <br />AMERICAN WIRE GAUGE <br />C <br />CONDUIT <br />CAT <br />CATEGORY <br />CB <br />CIRCUIT BREAKER <br />CH <br />CHILLER <br />CKT <br />CIRCUIT <br />CL <br />CENTER LINE <br />CLG <br />CEILING <br />CU <br />COPPER <br />EC <br />ELECTRICAL CONTRACTOR <br />EF <br />EXHAUST FAN <br />EM <br />EMERGENCY <br />EMT <br />ELECTRICAL METALLIC TUBING <br />ENCL <br />ENCLOSURE <br />EWH <br />ELECTRIC WATER HEATER <br />EXIST, EX <br />EXISTING <br />FA <br />FIRE ALARM <br />FCP <br />FIRE ALARM CONTROL PANEL <br />FACC <br />FIRE ALARM COMMAND CENTER <br />FATC <br />FIRE ALARM TERMINAL CABINET <br />FO <br />FIBER OPTIC <br />GFl <br />GROUND FAULT CIRCUIT INTERRUPTER <br />GND,G <br />GROUND <br />HOA <br />HAND -OFF -AUTO <br />HACR <br />HEATING/AIR CONDITIONING -RATED <br />HID <br />HIGH INTENSITY DISCHARGE <br />HPF <br />HIGH POWER FACTOR <br />HPS <br />HIGH PRESSURE SODIUM <br />HP <br />HORSEPOWER <br />IG <br />ISOLATED GROUND <br />JB <br />JUNCTION BOX <br />KCMIL <br />THOUSAND CIRCULAR MILS <br />KVA <br />KILOVOLT AMPERE <br />KW <br />KILOWATT <br />MCB <br />MAIN CIRCUIT BREAKER <br />MCC <br />MOTOR CONTROL CENTER <br />MDP <br />MAIN DISTRIBUTION PANEL <br />MH <br />METAL HALIDE <br />MLO <br />MAIN LUGS ONLY <br />MTD <br />MOUNTED <br />NC <br />NORMALLY CLOSED <br />NEC <br />NATIONAL ELECTRICAL CODE <br />NEMA <br />NATIONAL ELECTRICAL MANUFACTURERS ASSOC. <br />NF <br />NON -FUSED <br />NFPA <br />NATIONAL FIRE PROTECTION ASSOCIATION <br />NIC <br />NOT IN CONTRACT <br />NL <br />NIGHT LIGHT <br />NO <br />NORMALLY OPEN <br />PNL <br />PANEL <br />0 <br />PHASE <br />PB <br />PUSHBUTTON <br />PVC <br />POLYVINYL CHLORIDE CONDUIT <br />RGC <br />RIGID GALVANIZED STEEL CONDUIT <br />SW <br />SWITCH <br />SWBD <br />SWITCHBOARD <br />TVSS <br />TRANSIENT VOLTAGE SURGE SUPPRESSOR <br />TS <br />TIME SWITCH <br />XFMR <br />TRANSFORMER <br />TYP <br />TYPICAL <br />UG <br />UNDERGROUND <br />UH <br />UNIT HEATER <br />UPS <br />UNINTERRUPTIBLE POWER SUPPLY <br />LION <br />UNLESS OTHERWISE NOTED <br />VAV VARIABLE AIR VOLUME <br />VFD VARIABLE FREQUENCY DRIVE <br />V VOLT <br />WP WEATHER PROOF <br />DRAWING SYMBOLS <br />1 SECTION NUMBER <br />2 3 DRAWING NUMBER WHERE DRAWN <br />DRAWING NUMBER WHERE CUT <br />® NOTES <br />LIGHTING LEGEND <br />1 <br />a <br />CEILING MTD. 2'x4' LIGHT FIXTURE (SEE SCHEDULE) <br />AD° a <br />CEILING MOUNTED 2'x2' LIGHT FIXTURE (SEE SCHEDULE) <br />A 0 a <br />CEILING MOUNTED LIGHT FIXTURE (SEE SCHEDULE) <br />1 a <br />WALL MOUNTED LIGHT FIXTURE (SEE SCHEDULE) <br />AO a <br />CEILING MOUNTED LIGHT FIXTURE (SEE SCHEDULE) <br />A Q ° <br />WALL MOUNTED LIGHT FIXTURE (SEE SCHEDULE) <br />1 ❑ a <br />CEILING MOUNTED LIGHT FIXTURE (SEE SCHEDULE) <br />A g a <br />WALL MOUNTED LIGHT FIXTURE (SEE SCHEDULE) <br />A F--0—I a <br />FLUORESCENT STRIP (SEE SCHEDULE) <br />A 6-0 <br />POLE MOUNTED LUMINAIRE (SEE SCHEDULE) <br />AC-♦0 <br />2 HEAD POLE MOUNTED LIGHT FIXTURE (SEE SCHEDULE) <br />1 _ I _ <br />A <br />3 HEAD POLE MOUNTED LIGHT FIXTURE (SEE SCHEDULE) <br />1 <br />A <br />4 HEAD POLE MOUNTED LIGHT FIXTURE (SEE SCHEDULE) <br />1 ® A <br />EXIT SIGN. SINGLE OR DOUBLE FACE (SEE SCHEDULE) <br />A <br />EMERGENCY LIGHTING FIXTURE WITH BATTERY BACK-UP (SEE SCHEDULE) <br />A v v v a <br />TRACK LIGHT. NUMBER OF HEADS AS SHOWN (SEE SCHEDULE). <br />LIGHTING CONTROLS <br />a SINGLE POLE SWITCH 20A 120/277V LION CENTERUNE MOUNTED 48" AFF <br />M S K K: KEY TYPE M: MOTOR RATED <br />S2 DOUBLE POLE 20A 240V SWITCH - LION CENTERUNE MOUNTED 48" AFF <br />S 3 THREE WAY 20A 120/277V SWITCH - LION CENTERUNE MOUNTED 48' AFF <br />S4 FOUR WAY WALL MOUNTED SWITCH - LION CENTERUNE MOUNTED 48' AFF <br />SOD DIMMER SWITCH - LION CENTERUNE MOUNTED 48' AFF <br />0 TIME SWITCH AS INDICATED. LION MOUNT TOP OF ENCLOSURE 66' AFF <br />® CEILING MOUNTED OCCUPANCY SENSOR. SEE SPECIFICATIONS <br />WALL MOUNTED OCCUPANCY SENSOR. LION CENTERUNE MOUNTED 6' <br />BELOW CEILING. SEE SPECIFICATIONS. <br />COMMUNICATIONS LEGEND <br />q WALL MOUNTED TELEPHONE OUTLET. <br />LION CENTERLINE MOUNTED 18' AFF <br />V WALL MOUNTED DATA COMMUNICATION OUTLET. <br />LION CENTERLINE MOUNTED 18' AFF <br />0 FLOOR MOUNTED COMMUNICATION OUTLET <br />® POWER/DATA COMMUNICATION POLE AS INDICATED. WITH <br />(2) 20A 120V DUPLEX RECEPTACLES. <br />© COMMUNICATION EQUIPMENT RACK, SEE SPECIFICATIONS. <br />GENERAL NOTES <br />1. TEXT SHOWN ON PLANS ADJACENT TO UGHTING FIXTURES SHALL DENOTE THE FOLLOWING: <br />LOWERCASE LETTER (BY FIXTURE OR SWITCH) INDICATES LIGHT SWITCH CONTROL UPPERCASE <br />LETTER INDICATES FIXTURE TYPE NUMERAL INDICATES BRANCH CIRCUIT NUMBER. <br />2. SHADED LIGHTING FIXTURE SYMBOLS THAT APPEAR ON PLANS INDICATE EMERGENCY LIGHTING <br />FIXTURES AND SHALL BE INTERPRETED AS FOLLOWS: <br />LIFE SAFETY BRANCH CIRCUIT: <br />CRITICAL BRANCH CIRCUIT: <br />EMERGENCY LIGHT FIXTURE <br />WITH BATTERY BACK UP: <br />(THE ABOVE SHAD. APPLY TO ALL UGHTTNG FIXTURE SYMBOLS SHOWN ON LEGEND). <br />3• NUMERALS SHOWN ON PLANS ADJACENT TO WIRING DEVICES INDICATE BRANCH CIRCUIT NUMBER(S). <br />4. STANDARD SYMBOLS SHOWN ON LEGEND MAY NOT ALL APPEAR ON PLANS. WHERE SYMBOL <br />APPEARS ON PLANS FURNISH AND INSTALL AS SPECIFIED. <br />5. ALL STANDARD SYMBOLS ON LEGEND THAT APPEAR ON PLANS WITH HIDDEN LINES SHALL BE EXISTING <br />TO REMAIN (FOR REFERENCE ONLY). EXISTING SYMBOLS (AS DESCRIBED ABOVE) THAT APPEAR ON <br />PLANS WITH AN ADJACENT ABBREVIATION SHAD_ BE INTERPRETED AS FOLLOWS: <br />RL = EXISTING TO BE RELOCATED (SHOWN AT EXISTING LOCATION ON DEMOLITION PLAN). <br />REFER TO INSTALLATION PLAN FOR NEW LOCATION. CONTRACTOR SHALL EXTEND WIRING TO NEW <br />LOCATION AND RECONNECT. <br />R = EXISTING TO BE REMOVED. CONTRACTOR SHALL REMOVE DEVICE AND/OR EQUIPMENT AND <br />UNLESS OTHERWISE NOTED REMOVE ALL UNUSED CONDUIT AND WIRING. <br />POWER LEGEND <br />HOMERUN TO PANEL INDICATED (CONCEALED). MINIMUM 3/4'C. UNLESS <br />OTHERWISE NOTED PROVIDE #12 CONDUCTORS AS REQUIRED BY <br />NUMBER OF CIRCUITS SHOWN. INCLUDE J12 GROUND AND #12 NEUTRAL <br />LP t ► CONDUCTORS. FOR HOMERUNS EXCEEDING 100' IN LENGTH PROVIDE #10 <br />CONDUCTORS IN LIEU OF #12 AS INDICATED ABOVE. THERE SHALL BE A <br />MAXIMUM OF 3 BRANCH CIRCUITS PER HOMERUN (AS INDICATED ON <br />PLANS). TEXT SHOWN BY HOMERUN INDICATES PANELBOARD DESIGNATION <br />AND CIRCUIT NUMBER(S). <br />CONDUIT CONCEALED IN WALL OR ABOVE CEILING SPACE. UNLESS OTHERWISE <br />NOTED PROVIDE #12 CONDUCTORS AS REQUIRED BY NUMBER OF CIRCUITS <br />SHOWN. INCLUDE #12 GROUND AND #12 NEUTRAL MINIMUM 1/2'C. <br />UNDERGROUND CONDUIT OR BELOW SLAB. UNLESS OTHERWISE NOTED <br />PROVIDE #12 CONDUCTORS AS REQUIRED BY NUMBER OF CIRCUITS <br />SHOWN. INCLUDE #12 GROUND AND #12 NEUTRAL. MINIMUM 3/4"C. <br />- - - - - EXISTING CONDUIT. AS INDICATED. <br />Q CEILING OR WALL MOUNTED JUNCTION BOX. LION SIZE AS REQUIRED <br />BY NEC. <br />MOTOR. AS INDICATED. <br />6 120/240V 10 3W PANELBOARD. AS INDICATED. <br />HEAVY DUTY DISCONNECT SWITCH, NON FUSIBLE. SEE SPECIFICATIONS. <br />LION MOUNT TOP OF ENCLOSURE 66' AFF <br />HEAVY DUTY FUSIBLE DISCONNECT SWITCH. FUSED AS INDICATED ON <br />PLANS. SEE SPECIFICATIONS. LION MOUNT TOP OF ENCLOSURE 66' AFF. <br />Q� DUPLEX RECEPTACLE. 20A 120V LION CENTERLINE MOUNTED 18' AFF <br />DUPLEX RECEPTACLE. 20A 120V LION CENTERUNE MOUNTED 42" AFF <br />DOUBLE DUPLEX RECEPTACLE OUTLET. 20A 120V LION CENTERUNE <br />MOUNTED 18' AFF. <br />DOUBLE DUPLEX RECEPTACLE OUTLET. 20A 120V LION CENTERUNE <br />MOUNTED 42' AFF. <br />FIRE ALARM LEGEND <br />© PULL STATION. LION CENTERUNE MOUNTED 48" AFF. <br />❑a HORN CENTERUNE MOUNTED 80" AFF OR <br />6' BELOW CEILING, WHICHEVER IS LOWER. <br />® STROBE. MOUNTED 80' AFF OR 6' BELOW CEILING <br />WHICHEVER IS LOWER <br />HORN/STROBE. MOUNTED 80' AFF OR 6' BELOW CEILING <br />WHICHEVER IS LOWER <br />CHIME/STROBE. MOUNTED 80" AFF OR 6" BELOW CEILING <br />WHICHEVER IS LOWER <br />Q HEAT DETECTOR CEILING MOUNTED <br />20 SMOKE DETECTOR CEILING MOUNTED <br />W. DUCT MOUNTED SMOKE DETECTOR <br />FIRE ALARM CONTROL PANEL <br />FCP LION MOUNT TOP OF ENCLOSURE 72' AFF. <br />FIRE ALARM SYSTEM REMOTE ANNUNCIATOR. <br />® LION MOUNT TOP OF ENCLOSURE 66" AFF. <br />8 FLOW SWITCH <br />TAMPER SWITCH <br />Q SHUT -DOWN RELAY <br />® MAGNETIC DOOR HOLDER <br />REMOTE ALARM INDICATOR WITH TEST SWITCH. FLUSH <br />® COUNG MOUNTED. (WALL MOUNTED, CENTER LINE 48' <br />AFF IN MECHANICAL ROOMS). <br />HALON CONTROL PANEL <br />HCP LION MOUNT TOP OF ENCLOSURE 66" AFF <br />Q FIRE ALARM TRANSPONDER <br />LION MOUNT TOP OF ENCLOSURE 66' AFF <br />FIRE SERVICE JACK <br />mi LION CENTERLINE MOUNTED 48" AFF <br />FIRE SERVICE HANDSET <br />MH LION CENTERUNE MOUNTED 48" AFF <br />1 FIRE DAMPER (FURNISHED UNDER DIV. 15.) <br />TSMOKE DAMPER (FURNISHED UNDER DIV. 15) <br />Q: <br />T FIRE SMOKE DAMPER. (FURNISHED UNDER DIV. 15.) <br />ELECTRICAL SPECIFICATIONS <br />1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACC, E W <br />NFPA 70, 2005 EDITION 1 )°'���.._t 15 jl i- TI (sj�� x `wu% Ti� j <br />NFPA 72, 2002 EDITION. 1 <br />NFPA 101, LIFE SAFETY CODE 2003 EDITION. <br />FLORIDA BUILDING CODE 2004 EDITION. INCLUDING THE 2005 AND 2006 <br />AMENDMENTS. <br />FLORIDA ARE PREVENTION CODE 2004. <br />ALL APPLICABLE RULES AND REGULATIONS OF LOCAL CODES. <br />2. ALL WIRING SHALL BE COPPER TYPE THHN/THWN. SOLID FOR 110 AND <br />SMALLER, STRANDED FOR ALL CONDUCTORS J8 AND LARGER. <br />3. UNLESS OTHERWISE NOTED ALL CABLES AND CONDUCTORS SHALT. BE INSTALLED <br />(CONCEALED WHERE POSSIBLE) IN AN APPROVED RACEWAY, AS FOLLOWS: <br />INTERIOR (CONCEALED OR EXPOSED): <br />a) EMT, SET SCREW TYPE FITTINGS OR COMPRESSION TYPE FITTINGS IN DAMP <br />LOCATIONS. <br />b) FLEXIBLE CONNECTION WHIPS (MAXIMUM 6'-0' LENGTH). <br />FLEXIBLE METAL CONDUIT SHALL BE USED FOR ALL FINAL CONNECTIONS TO <br />MOTORS, LIGHTING FIXTURES AND OTHER VIBRATING EQUIPMENT. <br />ALL INTERIOR CONDUITS SHALL BE CONCEALED EXCEPT IN ELECTRICAL AND <br />MECHANICAL ROOMS. <br />EXTERIOR (CONCEALED OR EXPOSED): <br />a)CONDUIT OR RIGID (THREADED <br />FITTINGS AS MANUFACTURED BY CONDUIT MANUFACTURR <br />b) FLEXIBLE LIQUIDTIGHT CONNEC11ON WHIPS (MAXIMUM 6'-0' LENGTH). <br />FLEXIBLE UQUIDTIGHT CONDUIT SHALL BE USED FOR ALL FINAL CONNECTIONS <br />TO MOTORS AND OTHER VIBRATING EQUIPMENT. <br />ALL RACEWAYS SHALL BE INSTALLED PERPENDICULAR AND PARALLEL <br />TO MAJOR STRUCTURAL ELEMENTS AND IN A NEAT AND WORKMAN LIKE <br />MANNER. <br />EXTERIOR (UNDERGROUND): <br />a) SCHEDULE 40 PVC. <br />4. DISCONNECTING MEANS SHALL BE OF THE HEAVY-DUTY TYPE. UNLESS <br />OTHERWISE INDICATED PROVIDE NEMA 1 ENCLOSURE. <br />5. CONTRACTOR SHALL REMOVE AND DISPOSE OF ALL MATERIALS INDICATED <br />TO BE REMOVED AS PART OF DEMOLITION WORK OF THIS PROJECT. <br />CONTRACTOR SHALL CLEAN EACH AREA WHERE WORK IS PERFORMED ON A <br />DAILY BASIS. <br />6. ALL CUTTING AND PATCHING SHALL BE RESTORED TO MATCH EXISTING <br />SURFACE AND FINISH. WHERE NECESSARY TO DRILL THROUGH EXISTING FIRE <br />RATED PARTITIONS OR FLOORS CONTRACTOR SHALL PATCH USING MATERIALS <br />OF AN EQUIVALENT FIRE RATING. <br />7. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO <br />NEW OR EXISTING WALLS, FLOOR, FURNITURE ETC. AND SHALL REPLACE ANY <br />DAMAGED ITEMS WITHOUT ADDITIONAL COST TO OWNER. USE TEMPORARY <br />COVERS TO AVOID SPREAD OF DUST AND CONSTRUCTION DEBRIS. <br />8. UPON COMPLETION OF THE WORK THE ELECTRICAL CONTRACTOR SHALL <br />TEST ALL NEW EQUIPMENT, DEVICES, ETC. FOR PROPER OPERATION. <br />REPLACE MALFUNCTIONING UNITS AND RE -TEST TO FULFILL REQUIREMENTS. <br />9. PANELBOARDS SHALL BE ACCURATELY LABELED TO IDENTIFY FINAL CIRCUIT <br />NUMBERS UTILIZED, THEIR LOAD AND LOCATION. <br />10. ELECTRICAL INSTALLATION SHALL BE CLOSELY COORDINATED WITH ALL OTHER <br />WORK. CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH <br />ILL-TIMED INSTALLATION INCLUDING ANY ASSOCIATED REPAIRS OR <br />REPLACEMENTS. <br />11. 'PROVIDE' SHALL MEAN 'FURNISH AND INSTALL'. <br />12. LIGHTING TOGGLE SWITCHES SHALL BE 20 AMP, SPECIFICATION GRADE <br />TOGGLE TYPE SWITCHES. ALL SWITCHES AND COVERPLATES SHALL BE IVORY. <br />ALL ADJACENT SWITCHES SHALL BE GANGED IN ONE COMMON COVERPLATE/BOX. <br />LOCA11ONS AND HEIGHTS SHALL BE COORDINATED WITH DOOR SWINGS AND <br />COUNTER HEIGHTS. <br />13. DUPLEX AND DOUBLE DUPLEX RECEPTACLES SHALL BE 20 AMP, 125 VOLT <br />RATED, SPECIFICATION GRADE. RECEPTACLES SHALL HAVE A GREEN <br />GROUNDING SCREW TERMINAL AND A SELF GROUNDING CUP. ALL <br />RECEPTACLES SHALL BE YORY. <br />EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL BE COORDINATED <br />WITH THE COUNTER HEIGHTS AND ALL LOCATIONS SHALL BE VERIFIED WITH <br />THE OWNER PRIOR TO ROUGH -IN. <br />GFCI TYPE RECEPTACLES SHALL BE 20 AMP 125V, NON FEED-THRU TYPE. <br />14. PANELBOARDS SHALL BE EQUIPPED WITH COPPER BUS, 98% CONDUCTIVITY. <br />CIRCUIT BREAKERS SHALL BE OF THE BOLT -ON TYPE, SERIES CONNECTED <br />A.IC. RATINGS SHALL. BE ACCEPTABLE AS PER MANUFACTURER'S UL SERIES <br />CONNECTED RATINGS DATA. AVAILABLE MANUFACTURERS SHALL BE: <br />SQUARE D, CUTLER HAMMER AND GE. <br />15. SUPPORTING DEVICES <br />DAMP LOCATIONS AND OUTDOORS: HOT DIP GALVANIZED MATERIALS, U CHANNEL <br />SYSTEM COMPONENTS. <br />DRY LOCATION: STEEL MATERIALS. <br />STRENGTH OF SUPPORTS: ADEQUATE TO CARRY THE LOAD TIMES A SAFETY <br />FACTOR OF FOUR; MINIMUM 200-LB DESIGN LOAD. <br />16. ELECTRICAL IDENTIFICATION <br />ENGRAVED PLASTIC LAMINATE. INSTALL ON EACH UNIT OF EQUIPMENT. THIS <br />INCLUDES POWER, LIGHTING AND ALL SYSTEMS. <br />USE THE FOLLOWING COLORS FOR SERVICE, FEEDERS AND BRANCH CIRCUITS: <br />1. 120/208V: PHASE A. BLACK. PHASE B: RED. PHASE C: BLUE. <br />2. 277/48OV: PHASE A. YELLOW. PHASE B: BROWN. PHASE C: ORANGE <br />17. TEMPORARY ELECTRICAL. SERVICE <br />COST OR USE CHARGES FOR TEMPORARY FACILITIES ARE NOT CHARGEABLE TO <br />THE OWNER, ARCHITECT OR ENGINEER. <br />PROVIDE RECEPTACLE OUTLETS ADEQUATE FOR CONNECTION OF POWER TOOLS <br />AND EQUIPMENT. <br />PROVIDE TEMPORARY LIGHTING WITH LOCAL SWITCHING THAT PROVIDES ADEQUATE <br />ILLUMINATION FOR CONSTRUCTION OPERATION AND TRAFFIC CONDITIONS. <br />DRAWING INDEX <br />ELECTRICAL <br />E-001 LEGEND, ABBREVIATIONS AND GENERAL NOTES <br />E-100 ELECTRICAL FLOOR PLAN AND POWER RISER DIAGRAM <br />�c: � l'i'n1���'®I'L `lam ?V���✓�-t� i ��=;v,1>�it�3r��� � it�- '��v1 <br />c <br />I <br />RISER SYMBOLS LEGEND <br />GROUND FAULT SENSOR <br />CIRCUIT BREAKER. AS INDICATED <br />DRAWOUT CIRCUIT BREAKER. AS INDICATED <br />Y <br />1' STARTER / CONTACTOR <br />T <br />OGENERATOR <br />b <br />SWITCH <br />THERMAL OVERLOAD ELEMENT <br />TRANSFORMER <br />FUSE <br />1 GROUND <br />—©-- RELAY COIL, NOTED WITH TEXT <br />b <br />FUSED SWITCH <br />p <br />A AUTOMATIC TRANSFER SWITCH <br />r <br />® METER SOCKET <br />! REVISION NO.: I DESCRIPTION: <br />1 <br />1 CONSULTANT <br />1 <br />FLORIDA <br />HOSPITAL <br />Zephyrhillr <br />r rSE& <br />DATE <br />3203 QUEEN PALM DRIVE <br />TAMPA, FLORIDA 33619 <br />PHONE (813) 241-6488 <br />FAX (813) 241-6498 <br />Board of Profonlonal Enginwa — Liaans" f 27336 <br />Building "M" <br />Wound Care Renovations <br />LEGEND, ABBREVIATIONS <br />AND GENERAL NOTES <br />1 RICHARD P. CHRUSZCZ, P.E. <br />1 FL 4M <br />1 <br />I z I 3 I 4 I 5 I 0 I 1 I 8 I 9 I 10 I 11 I 12 I 13 I 14 <br />Z:\rbk\EAST PASCO MEDICAL CENTER\081040 — Hyperboric Treatment\Design\081040_E-1.dwg Feb 14, 2008 — 1:50pm alejandro.velez <br />COMMISSION NUMBER <br />DATE: <br />2-15-08 <br />DRAWING NUMBER <br />E=001 <br />SHEET OF <br />