<br />ABBREVIATIONS
<br />AD
<br />ACCESS DOOR
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />BFF
<br />BELOW FINISHED FLOOR
<br />BOT
<br />BOTTOM
<br />CLG
<br />CEILING
<br />D
<br />DRAIN
<br />DN
<br />DOWN
<br />EL
<br />ELEVATION
<br />EQUIP
<br />EQUIPMENT
<br />EXIST
<br />EXISTING
<br />FD
<br />FLOOR DRAIN
<br />FL
<br />FLOOR
<br />F
<br />FIRE MAIN
<br />FS
<br />FLOW SWITCH
<br />GPM
<br />GALLONS PER MINUTE
<br />MAX
<br />MAXIMUM
<br />MIN
<br />MINIMUM
<br />NIC
<br />NOT IN CONTRACT
<br />SPK.
<br />SPRINKLER
<br />TS
<br />TAMPER SWITCH
<br />TYP
<br />TYPICAL
<br />UG
<br />UNDERGROUND
<br />UON
<br />UNLESS OTHERWISE NOTED
<br />VIF
<br />VERIFY IN FIELD
<br />LEGEND
<br />SPRINKLER HEAD - WHITE PENDENT (SEE SCHEDULE)
<br />--------- EXISTING PENDENT MOUNTED SPRINKLER HEAD
<br />AND ARMOVER
<br />' VALVE IN RISER
<br />I FLUSHING CONNECTION
<br />TOP CONNECTION, 45 OR 90 DEG.
<br />' 1 z SIDE CONNECTION
<br />----�� RISE OR DROP IN PIPE
<br />Q/ PRESSURE GAGE
<br />GATE VALVE
<br />-� v--z CHECK VALVE
<br />r---ryl BALL VALVE
<br />SPRINKLER HEAD
<br />(LER
<br />vvnvarww mvvn i �.�
<br />SPRINKLER HEAD
<br />o� OUICK RESPONSE CONCEALED SCALEMSPRINKLER HEAD DETAIL
<br />NOT TO
<br />MI
<br />FIRE PROTECTION DESIGN CRITERIA
<br />* First Floor
<br />* Fire Protection system to be designed to NFPA 13 and Authority having jurisdiction
<br />* Hazard Type: Light hazard
<br />* Sprinkler Head Design Area: 196 sq.ft.
<br />* Sprinkler Head Density: .15 gpm/sq.ft.
<br />* Sprinkler Head Response Type: Quick Response
<br />* System Coverage Area: Most remote 1500 sq.ft.
<br />* Sprinkler Head Temperature Rating: 135 degree F
<br />* All materials to be UL Listed and/or Factory Mutual approved.
<br />* All piping shall be pressure tested at 200 psi for 2 hour as per NFPA-13.
<br />* Fire sprinkler system to be centrally monitored.
<br />* Main and Branch piping 2" and under shall be black steel schedule 40 with threaded pipe
<br />utilizing grooved coupling and fitting, outlets to be welded groove-o-lets.
<br />* Provide signed and sealed hydraulic calculations.
<br />B'
<br />1
<br />4
<br />1
<br />1
<br />1
<br />_ 1
<br />A 1
<br />1
<br />1
<br />4
<br />Z:\rbk\EAST PASCO MEDICAL CENTER\081040 - Hyperboria Treatment\Design\081040_FP-1.dwg Mar 05, 2008 - 2:22pm joy.malllson
<br />FIRE PROTECTION GENERAL NOTES
<br />1. FIRE PROTECTION WORK SHALL BE DESIGNED, INSTALLED, AND TESTED IN ACCORDANCE WITH NFPA 13,
<br />LATEST EDITION OR AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION.
<br />2. INCLUDE ANY INCIDENTAL APPARATUS, APPLIANCES, MATERIAL LABOR AND SERVICES NECESSARY
<br />TO MAKE NEW WORK COMPLETE IN ALL RESPECTS AND FULLY READY FOR OPERATION.
<br />3. MAKE SUCH OFFSETS AND DEVIATIONS FROM WORK SHOWN ON THE DRAWINGS, AS MAY BE
<br />NECESSARY TO FIT THE ACTUAL SPACE CONDITIONS.
<br />4. THE INSTALLER SHALL VISIT THE JOB SITE, INSPECT ALL EXISTING CONDITIONS AFFECTING THE
<br />WORK. SUBMISSION OF HIS PROPOSAL SHALL BE CONSTRUED AS INDICATING SUCH KNOWLEDGE.
<br />NO ADDITIONAL PAYMENT WILL BE MADE ON CLAIMS THAT ARISE FROM THE CONTRACTOR'S
<br />FAILURE TO COMPLY WITH THIS REQUIREMENT.
<br />5. THE PLANS AND DIAGRAMS OF FIRE PROTECTION PIPING ARE SCHEMATIC ONLY AND SHOULD NOT
<br />BE SCALED. INSTALLER SHALL COORDINATE AT SITE WITH ALL PLUMBING, HVAC, FIRE PROTECTION,
<br />AND ELECTRICAL WORK SO AS NOT TO CONFLICT IN LOCATION WITH OTHER WORK UNDER THIS
<br />CONTRACT OR THAT MAY BE EXISTING. CONTRACTOR SHALL ADJUST PIPE ROUTING AS NECESSARY
<br />TO AVOID CONFLICTS WITH EXISTING DUCTWORK, EQUIPMENT, LIGHTING, ETC.
<br />6. INSTALLER SHALL NOT CUT ANY EXISTING STRUCTURAL MEMBERS WITHOUT FIRST SECURING WRITTEN
<br />APPROVAL FROM THE ARCHITECT.
<br />7. IN GEOGRAPHICAL LOCATIONS SUBJECT TO TEMPERATURES BELOW 40'F, PROVIDE PROTECTION FOR
<br />ALL EXPOSED FIRE PROTECTION PIPING IN ACCORDANCE WITH NFPA 13.
<br />8. PROVIDE TAMPER SWITCHES ON ALL VALVES THAT CAN SHUT OFF FLOW IN MAINS OR BRANCHES.
<br />CHAINS AND LOCKS IN LIEU OF TAMPER SWITCHES MAY BE USED AT OUTDOOR BACK FLOW
<br />PREVENTERS ONLY IF APPROVED BY THE AUTHORITY HAVING JURISDICTION.
<br />9. PIPE SIZED, GENERAL ROUTING, AND CONFIGURATION IN SYSTEMS REQUIRED TO BE HYDRAULICALLY
<br />CALCULATED SHALL BE INSTALLED PER THIS ENGINEER'S CONSTRUCTION DOCUMENTS. ANY
<br />DEVIATION SUBMITTED BY THE CONTRACTOR SHALL BE RE -DESIGNED BY THIS ENGINEER WITH
<br />RELATED RE -DESIGN FEES BORN BY THE CONTRACTOR.
<br />10. CONTRACTOR SHALL ARRANGE FOR, OBTAIN AND BEAR THE COST OF NECESSARY PERMITS, BONDS,
<br />AND FEES.
<br />11. ALL MATERIALS SHALL BE U.L. LISTED AND BEAR THE U.L. LABEL.
<br />12. CONDITIONS SHOWN AS EXISTING (LOCATIONS, MATERIALS, ELEVATIONS, SIZED, ETC.) ARE BASED
<br />ON AVAILABLE EXISTING DATA AND SHOULD BE INTERPRETED TO BE APPROXIMATE. CONTRACTOR
<br />SHALL VERIFY CONDITIONS IN THE FIELD. EXISTING CONDITIONS FOUND TO DEVIATE FROM THOSE
<br />SHOWN SHALL BE REPORTED TO THE ENGINEER.
<br />13. PENETRATIONS THROUGH FIRE RATED ASSEMBLIES, PENETRATIONS FOR PIPES, CONDUITS, OR OTHER
<br />PURPOSES THROUGH ASSEMBLIES (FLOORS, ROOF, WALLS, PARTITIONS, ETC.) WITH A REQUIRED
<br />FIRE RESISTANCE RATING FIRE STOP MATERIAL SHALL BE UL LISTED AND INSTALLED IN STRICT
<br />ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS TO MEET OR EXCEED THE FIRE RATING OF
<br />THE PENETRATED ASSEMBLY.
<br />14. BEFORE SHUTTING OFF ANY SECTION OF THE FIRE PROTECTION SYSTEM TO MAKE ADJUSTMENTS
<br />OR ADDITIONAL CONNECTIONS, COORDINATE WITH THE OWNER AND NOTIFY THE AUTHORITY
<br />HAVING JURISDICTION. PLAN THE WORK CAREFULLY AND ASSEMBLE ALL MATERIALS TO ENABLE
<br />COMPLETION IN THE SHORTEST POSSIBLE TIME. WORK SHALL BE USED TO COMPLETION WITHOUT
<br />INTERRUPTION, AND PROTECTION SHALL BE RESTORED AS PROMPTLY AS POSSIBLE.
<br />15. WHERE ELECTRICAL PANELS EXIST, PROVIDE DEFLECTORS ON ELECTRICAL EQUIPMENT TO PREVENT
<br />WETTING PANELS. SPRINKLER PIPING SHALL NOT BE INSTALLED DIRECTLY ABOVE ELECTRIC PANELS.
<br />16. PROVIDE FLUSHING CONNECTION AT END OF SPRINKLER SYSTEM WHERE LAY -IN CEILING OCCURS.
<br />ALL SPRINKLER PIPING THAT REQUIRES CHANGE IN ELEVATION DUE TO COORDINATION ROUTING OF
<br />PIPING SHALL HAVE FLUSH CONNECTION AT ALL LOWER ELEVATION. THE SPRINKLER SYSTEM SHALL
<br />BE INSTALLED WITH COMPLETE DRAINABLE SYSTEM.
<br />17. VERIFY THE EXACT LOCATION OF EXISTING FIRE PROTECTION PIPING, FROM THE ACTUAL JOB SITE.
<br />ALL NEW LINES ARE TO BE ROUTED TO AND/OR FROM VERIFIED LOCATIONS. TAPS, WHEN NOT
<br />PROVIDED BY PREVIOUS INSTALLER SHALL BE PROVIDED BY THIS INSTALLER.
<br />18. PROVIDE AND MAINTAIN TEMPORARY CONNECTIONS TO KEEP EXISTING FIRE PROTECTION SYSTEM
<br />IN SERVICE. ANY SHUT DOWNS ARE TO BE APPROVED BY OWNER'S REPRESENTATIVE.
<br />19. NEW SPRINKLER HEADS IN RENOVATION AREA SHALL BE QUICK RESPONSE TYPE.
<br />20, ALL SPRINKLER HEADS SHALL BE U.L. LISTED AND INSTALLED IN ACCORDANCE WITH THEIR
<br />LISTING REQUIREMENTS. ALL ESCUTCHEONS AND ACCESSORIES SHALL BE METAL.
<br />21. ALL WORK IS TO BE FREE OF DEFECTS IN WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE (1)
<br />YEAR FROM DATE OF FINAL ACCEPTANCE. ALL DEFECTS WHICH DEVELOP OR ARE DISCOVERED
<br />WITHIN THIS PERIOD SHALL BE REPAIRED BY THE CONTRACTOR TO THE SATISFACTION OF THE
<br />OWNER AT NO ADDITIONAL COST TO THE OWNER.
<br />22. UPON COMPLETION OF THE WORK UNDER THIS CONTRACT, THE CONTRACTOR SHALL REMOVE ALL
<br />TOOLS, APPLIANCES, SURPLUS MATERIALS, AND SCRAP. ALL IDENTIFIED EXISTING EQUIPMENT TO
<br />BE REMOVED SHALL BE TURNED OVER TO THE OWNER.
<br />23. WHEN CONFLICTS OCCUR IN SPECIFICATIONS OR IN THE DRAWINGS, OR BETWEEN EITHER, THE ITEMS
<br />OF GREATER QUANTITY OR HIGHER COST SHALL BE PROVIDED.
<br />24. THE CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES IN ORDER TO AVOID CONFLICTS.
<br />25. CONTRACTOR IS RESPONSIBLE FOR REMOVING AND REINSTALLING ALL CEILING TILES AND GRIDS AS
<br />NECESSARY TO INSTALL NEW SPRINKLER SYSTEM.
<br />26. COORDINATE EXACT LOCATION OF SPRINKLERS AND PIPING WITH CEILING, ELECTRICAL,
<br />MECHANICAL, AND STRUCTURAL ELEMENTS OF BUILDING. MAKE MODIFICATIONS WITHOUT
<br />ADDITIONAL COST TO THE OWNER.
<br />27. PROVIDE ALL HANGERS AS REQUIRED TO COMPLY WITH NFPA 13.
<br />28. TAMPER SWITCHES AND FLOW SWITCHES TO BE PROVIDED AND INSTALLED BY FIRE PROTECTION
<br />CONTRACTOR AND CONNECTED BY FIRE ALARM CONTRACTOR. COORDINATE TO VERIFY
<br />COMPATIBILITY OF SWITCHES AND LOCATIONS.
<br />29. PROVIDE ALL DRAINS AS REQUIRED BY NFPA 13.
<br />30. PROVIDE CONNECTION TO CITY MAIN AND PAY ALL FEES ASSOCIATED.
<br />31. EQUIP ALL GATE AND BUTTERFLY VALVES WITH LOCKING DEVICES AND TAMPER SWITCHES IF
<br />REQUIRED BY AUTHORITY HAVING JURISDICTION.
<br />32. PENDENT MOUNTED SPRINKLER HEADS SHALL BE ALIGNED WITHIN NORMAL FABRICATION AND
<br />INSTALLATION TOLERANCES AND WILL BE CENTERED IN CEILING TILES.
<br />33. FIRE SPRINKLER SYSTEM CONSISTS OF 6 SPRINKLER HEADS AND HYDRAULIC
<br />EXISTING 3" DOMESTIC WATER SUPPLY IS A MAX. FLOW OF 175 GPM
<br />DRAWING SYMBOLS
<br />POINT OF NEW CONNECTION
<br />4>_POINT OF INTERFACE BETWEEN CONTRACTORS
<br />® KEYED NOTES
<br />DRAWING INDEX
<br />FIRE PROTECTION
<br />FP-001 ABBREVIATIONS, LEGENDS AND GENERAL NOTES
<br />FP-100 FIRE PROTECTION FLOOR PLAN
<br />FIRE SPRINKLER HEAD SCHEDULE
<br />SYMBOL METAL FINISH TEMPERATURE K-FACTOR N.P.T. ORIFICE PLATE MANUFACTURER MODEL
<br />0 CPENDENTD WHITE 155' F 5.6 1 /2" 0.5 WHITE TYCO TY3531
<br />NOTE:
<br />THESE ARE STANDARD SYMBOLS AND GENERAL NOTES AND MAY NOT ALL APPEAR
<br />ON THE PROJECT DRAWINGS; FIOVVEVBi WHEREVER THE 3YM601_ APPEARS ON THE
<br />PROJECT DRAWNC38, THE ITEM SHALL BE FRONDED AND INSTALLED.
<br />EXISTING GYP BOARD CLG.-/
<br />THREADED ROD - 2" SUPPLY
<br />(TYP) FIRE SERVICE
<br />PIP ( HA) GER�
<br />TYP
<br />NEW LAY -IN
<br />CEILING
<br />NOTES
<br />1. DEVICE MUST BE INSTALLED LEVEL.
<br />2. ALL JOINTS SHALL BE SCREWED (U.O.N.)
<br />3. WILKINS DC 950 SCREW TYPE UL/FM APPROVED 2" SIZE
<br />4. INSTALL DDC VALVE ASSEMBLY MIN. 1'-6" t OF PIPING OFF
<br />EXISTING WEST WALL
<br />1" DRAIN OFFSET
<br />AND DROP IN NEW
<br />CHASE WALL AND
<br />OPEN END 6" ABV.
<br />EXTERIOR SLAB
<br />OS&Y VALVES (TYP)
<br />DOUBLE DETECTOR CHECK
<br />BACKFLOW PREVENTER
<br />ASSEMBLY
<br />BACKFLOW PREVENTER DETAIL NOT TO SCALE
<br />NEW
<br />3CH. 40) ARMOVER
<br />NEW CONCEALED MOUNTED
<br />SPRINKLER LOCATION
<br />IN CENTER OF CEILING TILE
<br />COORDINATE WITH ALL LIGHTING
<br />AND DIFFUSER LOCATIONS (TYP)
<br />CONTINUOUS THREADED
<br />ROD
<br />12" MAXIMUM
<br />CLEVIS HANGER
<br />FM/UL APPROVED
<br />(TYP)
<br />SPRINKLER PIPING ARMOVER DETAIL
<br />NOT TO SCALE
<br />8 9 10 11 12 I 13 14
<br />1
<br />1
<br />1
<br />1
<br />1 FIRE MARSHALL COMMENTS
<br />REVISION NO.: DESCRIPTION:
<br />CONSULTANT
<br />KPI 1RNGRMLC ING. 'INC.
<br />I
<br />FLORIDA
<br />HOSPITAL
<br />Zephyrhillr
<br />03/07/08
<br />DATE
<br />3203 QUEEN PALM DRIVE
<br />TAMPA, FLORIDA 33619
<br />PHONE (813) 241-6488
<br />FAX (813) 241-6498
<br />Board of Professional Engineers - Lleense / 27336
<br />Building "M"
<br />Wound Care Renovations
<br />LEGEND, ABBREVIATIONS
<br />AND GENERAL NOTES
<br />COMMISSION NUMBER
<br />GUY VAN MEULEBROUCK, RE
<br />kL LIC. No. 53808 DATE:
<br />o�
<br />2-15-08
<br />DRAWING NUMBER
<br />FP=001
<br />SHEET OF
<br />T- It -fT- F- i