ELECTRICAL SPECIFICATIONS: <br />THE WORK UNDER THE REQUIREMENTS OF THESE SPECIFICATIONS SHALL BE IN <br />OCONFORMANCE WITH THE LATEST EDI11ON OF THE NATIONAL ELECTRICAL CODE. <br />THE INSTALLATION SHALL ALSO COMPLY WITH ALL APPLICABLE RULES AND <br />REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES. <br />ALL ELECTRICAL EQUIPMENT SHALL HAVE UL LABEL AND SHALL BE OF <br />O SPECIFICATION GRADE. <br />POWER DISTRIBUTION HOUSE PANELBOARD: PROVIDE DEAD —FRONT, <br />O3 SAFETY —TYPE POWER DISTRIBUTION PANELBOARDS AS INDICATED; WITH <br />PANELBOARD SWITCHING AND PROTECTIVE DEVICES IN QUANTITIES, RATINGS, <br />TYPES, AND WITH ARRANGEMENT SHOWN; WITH ANTI —TURN, SOLDERLESS <br />PRESSURE TYPE MAIN LUG CONNECTORS APPROVED FOR USE WITH COPPER <br />CONDUCTORS. <br />HOUSE PANELBOARDS SHALL BE EQUAL TO SQUARE D TYPE "NQOD". VOLTAGE <br />®SHALL BE AS INDICATED. ACCEPTABLE MFG.; G.E., SIEMENS AND <br />CUTLER —HAMMER. <br />OTENANT PANELBOARDS: PROVIDE DEAD —FRONT SAFETY TYPE LIGHTING AND <br />BRANCH CIRCUIT PANELBOARDS AS INDICATED; WITH SWITCHING AND PROTECTIVE <br />DEVICES IN QUANTITIES, RATINGS, TYPES AND ARRANGEMENTS SHOWN; WITH <br />ANTI —TURN, SOLDERLESS PRESSURE TYPE LUG CONNECTORS APPROVED FOR USE <br />WITH COPPER CONDUCTORS. <br />© TENANT PANELBOARDS SHALL BE SQUARE D TYPE "QO". PANELBOARD BOXES <br />SHALL BE FIVE AND THREE —FOURTHS INCHES (5 3/4") DEEP. VOLTAGE SHALL <br />BE AS INDICATED. <br />OALL PANELBOARDS SHALL BE CONNECTED, DISTRIBUTED PHASE WITH CIRCUIT <br />NUMBERING AS INDICATED ON THE DRAWINGS. PANELBOARDS SHALL BE <br />NUMBERED WITH ODD NUMBERS ON THE LEFT SIDE OF THE PANEL AND EVEN <br />NUMBERS ON THE RIGHT SIDE OF THE PANEL. <br />UNLESS OTHERWISE INDICATED, PROTECTIVE DEVICES SHALL BE MOUNTED WITH <br />®TOP OF CABINET OR ENCLOSURE 6'-6" ABOVE FINISHED FLOOR, SHALL BE <br />PROPERLY ALIGNED, AND SHALL BE ADEQUATELY SUPPORTED INDEPENDENTLY OF <br />THE CONNECTING RACEWAYS, ALL STEEL SHAPES, ETC., NECESSARY FOR THE <br />SUPPORT OF THE EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE <br />CONTRACTOR WHERE THE BUILDING STRUCTURE IS NOT SUITABLE FOR MOUNTING <br />THE EQUIPMENT DIRECTLY THEREON. UNLESS OTHERWISE INDICATED, ALL BRANCH <br />CIRCUIT PROTECTIVE DEVICES ENCLOSURES SHALL BE NEMA TYPE I, GENERAL <br />PURPOSE TYPE. CIRCUIT PROTECTIVE DEVICES INSTALLED OUTDOORS OR EXPOSED <br />TO THE WEATHER SHALL HAVE WEATHERPROOF ENCLOSURES, NEMA TYPE "3R" <br />OR TYPE "4". <br />O9 ALL SAFETY SWITCHES SHALL BE GENERAL DUTY TYPE. SWITCH MECHANISM <br />SHALL BE QUICK -MAKE, QUICK -BREAK. COVER SHALL BE INTERLOCKED WITH <br />MECHANISM TO PREVENT OPENING UNLESS SWITCH IS IN THE "OFF" POSITION. <br />ALL ENCLOSURES SHALL BE PRIMED AND FINISHED TO RESIST RUSTING AND <br />CORROSION. SWITCHES SHALL BE ITE, GENERAL ELECTRIC, SQUARE-D, OR <br />CUTLER -HAMMER. <br />10 CIRCUIT BREAKERS FOR MOUNTING IN HOUSE PANELBOARD SHALL BE BOLT —ON <br />TYPE, MOLDED PLASTIC CASE, AIR CIRCUIT BREAKER TYPE. BREAKERS SHALL <br />HAVE THERMAL MAGNETIC TRIP UNITS AND MULTI —POLE BREAKERS SHALL HAVE <br />A COMMON TRIP BAR SO THAT THE TRIPPING OF ONE POLE WILL AUTOMATICALLY <br />TRIP ALL POLES OF THE BREAKER. BREAKERS SHALL BE TRIP FREE AND TRIP <br />INDICATING AND SHALL HAVE QUICK —MAKE, QUICK —BREAK CONTACTS. <br />UPON COMPLETION OF WORK CORRECT ALL PANELBOARD CIRCUIT DIRECTORY <br />11 CARDS TO REFLECT AS —BUILT CONDITIONS. PANELBOARD DIRECTORIES SHALL BE <br />UPDATED WITH TYPEWRITTEN ACCURATE AND CURRENT INFORMATION BY THE <br />CONTRACTOR AT THE END OF CONSTRUCTION. DIRECTORIES SHALL REFLECT <br />RECORD CONDITIONS AND INCLUDE CIRCUIT NUMBER, TYPE AND LOCATION OF <br />LOAD. A SET OF AS —BUILT DRAWINGS SHALL ALSO BE PREPARED AND TURNED <br />OVER TO THE OWNER. <br />12 ALL CONDUCTORS SHALL BE THHN/THWN COPPER #12 MIN. AND INSTALLED IN A <br />COMPLETELY ENCLOSED RACEWAY SYSTEM. <br />13 UNLESS SPECIFICALLY NOTED ON DRAWINGS, RACEWAYS SHALL COMPLY WITH THE <br />FOLLOWING: <br />RACEWAYS EXPOSED TO THE WEATHER OR IN DAMP LOCATIONS <br />SHALL BE GALVANIZED RIGID STEEL WITH THREADED CONNECTIONS. <br />RACEWAYS SHALL BE SIZED FOR THE CONDUCTORS INSTALLED, <br />MINIMUM 1/2". FULL SIZE MC CABLE IS ACCEPTABLE IN DRY LOCATIONS. <br />HOMERUNS TO PANELS TO BE IN CONDUIT. <br />RACEWAYS RUN BELOW GRADE SHALL BE PVC , EXPOSED ON BUILDING <br />14 EXTERIOR SHALL BE RIGID STEEL CONDUIT. <br />ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE <br />15 AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND EQUIPMENT. <br />16 ALL RACEWAYS SHALL BE SECURELY SUPPORTED FROM THE BUILDING <br />STRUCTURE. <br />17 ALL RACEWAYS SHALL BE PROVIDED WITH EQUIPMENT GROUND CONDUCTOR. <br />ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE <br />18 SCREW FASTENED COVERS. OPEN KNOCK —OUTS OR HOLES IN BOXES SHALL BE <br />PLUGGED WITH A SUITABLE BLANKING DEVICES. <br />OUTLET BOXES FOR EXPOSED WALL MOUNTING AND OUTDOOR INSTALLATION <br />19 SHALL BE CAST METAL TYPE "FS" OR "FD" BOXES WITH SUITABLE GALVANIZED <br />SHEET STEEL COVERS, OR CAST METAL WEATHERPROOF OR VAPOR TIGHT COVERS <br />WHEN NOTED ON THE DRAWINGS. <br />QUNLESS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER N0. 12 AWG. <br />MINIMUM. OR SIZE AS SHOWN ON DRAWINGS. CONDUCTORS SHALL HAVE TYPE <br />'THHN/THWN' INSULATION. <br />21 SPLICES, TAPS AND ATTACHMENT FITTINGS AND LUGS SHALL BE ELECTRICALLY <br />AND MECHANICALLY SECURE AND SOLDERLESS FOR CONDUCTORS SIZES No. 8 <br />AWG AND LARGER. THERE SHALL BE PLENTY OF SLACK CABLE IN BOXES, <br />OUTLETS AND CABINETS TO INSURE THAT THERE IS NO BINDING AT THE <br />BUSHINGS. ALL LUGS SHALL BE OF THE CORRECT SIZES FOR THE CONDUCTORS <br />JOINED AND IN NO CASE SHALL STRANDS BE CUT FROM A CONDUCTOR IN ORDER <br />TO FIT THE CONDUCTOR INTO A LUG. TAPING OF JOINTS SHALL BE WITH VINYL <br />PLASTIC ELECTRICAL TAPE TO SECURE INSULATION STRENGTH EQUAL TO THAT OF <br />THE CONDUCTORS JOINED. <br />QTHE INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY <br />GROUNDED AS REQUIRED BY THE NEC AND AS SPECIFIED HEREINAFTER. <br />Q CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS. <br />THE CONTRACTOR SHALL VERIFY ALL LOCATIONS WITH THE OWNER PRIOR TO <br />® INSTALLATION. THEY SHALL NOT BE CHARGED FOR MINOR LOCATION CHANGES <br />PRIOR TO INSTALLATIONS. LOCATIONS ARE APPROXIMATE. (DO NOT SCALE <br />DRAWINGS). <br />QTHESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL ELECTRICAL LAYOUTS <br />FOR BIDDING PURPOSES ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR <br />TO PREPARE DETAILED SHOP DRAWINGS AND CONFIRM SPACE ALLOCATIONS. <br />©THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES FOR <br />ELECTRICAL CONDUIT ROUTING AND EQUIPMENT PLACEMENT. AVOID <br />INTERFERENCE WITH ARCHITECTURAL AND STRUCTURAL FEATURES SUCH AS: <br />BEAMS, FOOTINGS, WINDOWS, ETC. NOTIFY ARCHITECT IMMEDIATELY OF ANY <br />CONFLICTS. <br />©THE ELECTRICAL CONTRACTOR THE HVAC FOREMAN AND GENERAL CONTRACTOR <br />PROJECT MANAGER SHALL INSPECT & REVIEW THE CONDITIONS, AND SHALL <br />COORDINATE THEIR WORK SO AS TO PROVIDE ADEQUATE SPACE ALLOWANCE <br />ABOVE CEILING FOR ALL TRADES. <br />THE PLANS SHOW THE LOCATION OF ALL FIXTURES AND EQUIPMENT AND ARE <br />INTENDED TO DEPICT THE GENERAL INTENT OF THE WORK IN SCOPE, LAYOUT AND <br />QUALITY OF WORKMANSHIP. THEY ARE NOT INTENDED TO SHOW IN MINUTE DETAIL <br />EVERY AND ALL ACCESSORIES INTENDED FOR THE PURPOSE OF EXECUTION OF <br />THE WORK, BUT SHALL BE UNDERSTOOD THAT SUCH DETAILS WILL BE PART OF <br />THIS WORK. <br />®THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE AND <br />FUNCTIONAL SYSTEM: CONTROLS, AND CONNECTIONS TO NEW SERVICES, <br />SUPPORTS, AND HARDWARE REQUIRED FOR THE SATISFACTORY OPERATION OF <br />THE SYSTEM, WHETHER SPECIFICALLY SHOWN OR NOT ON THE DRAWINGS. <br />30 WHERE DRAWINGS AND SPECIFICATIONS CONFLICT, IT SHALL BE THE <br />RESPONSIBILITY OF THIS CONTRACTOR TO BRING SUCH CONFLICT TO THE <br />ATTENTION OF THE ENGINEER FOR CLARIFICATION. <br />ELECTRICAL SYMBOL LEGEND <br />SYMBOL <br />DESCRIPTI❑N <br />M❑UNTING <br />1 X 4 FLUORESCENT FIXTURE <br />SEE FIXTURE <br />�-V-� <br />LETTER INDICATES TYPE <br />SCHEDULE <br />2 X 4 FLUORESCENT FIXTURE <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />SCHEDULE <br />SHADING DENOTES FIXTURE WITH EM BATTERY PACK. <br />SEE FIXTURE <br />'NL' DENOTES FIXTURE UNSWITCHED FOR NIGHT LIGHT <br />SCHEDULE <br />FLUORESCENT STRIP FIXTURE <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />SCHEDULE <br />[] <br />FLUORESCENT WALL BRACKET FIXTURE <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />SCHEDULE <br />PL FLUORESCENT DOWNLIGHT <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />SCHEDULE <br />I4 EX <br />EXIT -SHADING DENOTES FACEPLATE LOCATION. LETTER <br />SEE FIXTURE <br />INDICATES TYPE. PROVIDE ARROWS AS REQUIRED. <br />SCHEDULE <br />SINGLE POLE SWITCH (20A-120/277) <br />48" AFF OR AS <br />S S3 So <br />3' DENOTES 3-WAY 0 DENOTES OCCUPANCY SENSOR <br />NOTED <br />Go: <br />DUPLEX RECEPTACLE, 125V, 20A <br />18" AFF OR AS <br />IG DENOTES ISOLATED GROUND <br />NOTED <br />DUPLEX RECEPTACLE, 125V, 20A <br />18" AFF OR AS <br />NOTED <br />DUPLEX RECEPTACLE, 125V, 20A <br />48" AFF OR AS <br />NOTED <br />QUADRAPLEX RECEPTACLE, 125V, 20A <br />18" AFF OR AS <br />NOTED <br />® <br />POWER / TELEPHONE POLE <br />SEE DETAIL OR <br />AS NOTED <br />OUTLET BOX OR J-BOX FOR POWER AND DATA <br />18" AFF OR <br />® Q <br />SUPPLY TO FURNITURE SYSTEMS <br />AS NOTED <br />0 <br />COMBINATION VOICE/DATA OUTLET <br />18, AFF OR AS <br />NOTED <br />0 <br />T.V. OUTLET <br />18" AFF OR AS <br />NOTED <br />PANELBOARD 120/208V <br />SEE PANELSCHEDULE <br />RACEWAY CONCEALED IN WALL OR ABOVE CEILING <br />SEE SPECIFICATIONS <br />HOMERUN TO PANEL. LETTERS INDICATE PANEL, <br />NUMBERS INDICATE CIRCUIT. NOTE: HASH MARKS <br />SEE SPECIFICATIONS <br />INDICATES THE NUMBER OF WIRES EXCLUDING <br />THE REQUIRED EQUIPMENT GROUND. <br />MOTOR, NUMERAL INDICATES HORSEPOWER <br />AS NOTED <br />$ <br />MOTOR RATED SWITCH WITH OVERLOAD <br />MOUNTED ADJACENT <br />RELAYS IF REQUIRED. <br />TO EQUIPMENT <br />NON -FUSIBLE SAFETY SWITCH -SIZE AS NOTED <br />SEE SPECIFICATIONS <br />FUS13LE SAFETY SWITCH -SIZE AS NOTED <br />SEE SPECIFICATIONS <br />17- <br />FIRE ALARM DUCT DETECTOR ('RA'DENOTES <br />MOUNTED IN <br />RETURN AIR 'SA' DENOTES SUPPLY AIR) <br />HVAC DUCTWORK <br />® <br />FAN OR AIR HANDLER SHUTDOWN RELAY <br />MOUNTED <br />O T ADJACENT <br />EQUIPMENT O <br />® <br />FIRE ALARM VISUAL SIGNAL <br />80" AFF OR <br />AS NOTED <br />Q <br />FIRE ALARM MANUAL PULLSTATION <br />48" AFF OR <br />AS NOTED <br />FIRE ALARM AUDIBLE/VISUAL SIGNAL. ADA <br />80" AFF OR <br />®4 <br />COMPATIBLE <br />AS NOTED <br />Q <br />FIRE ALARM SMOKE DETECTOR <br />ON CEILING OR <br />AS NOTED <br />FAW <br />FIRE ALARM PANEL ('FACP' DENOTES FIRE ALARM <br />60" AFF OR <br />r__ <br />FAA <br />CONTROL PANEL, 'FAA' DENOTES ANNUNCIATOR) <br />AS NOTED <br />EX <br />DENOTES EXISTING DEVICE OR CIRCUIT TO REMAIN <br />R <br />DENOTE NEW LOCATION FOR RELOCATED DEVICE <br />3O (�) j <br />REFER TO LIKE NUMBERED NOTES <br />NOTE: ALL MOUNTING HEIGHTS SHOWN ARE TO THE TOP OF THE <br />DEVICE UNLESS NOTED OTHERWISE. <br />NOT ALL SYMBOLS APPEAR ON PLANS. <br />. -j:' Re] ilk <br />AFF <br />- ABOVE FINISHED FLOOR <br />AHU <br />- AIR HANDLING UNIT <br />BFG <br />- BELOW FINISHED GRADE <br />C <br />- CONDUIT <br />CW <br />- COOL WHITE <br />DACP <br />- DOOR ALARM CONTROL PANEL <br />DIN <br />- DOWN <br />EF <br />- EXHAUST FAN <br />EG <br />- EQUIPMENT GROUND <br />ENCL <br />- ENCLOSURE <br />EWC <br />- ELECTRIC WATER COOLER <br />EWH <br />- ELECTRIC WATER HEATER <br />WX <br />- EXPLOSION PROOF <br />FCU <br />- FAN COIL UNIT <br />FHP <br />- FRACTIONAL HORSE POWER <br />FLA <br />- FULL LOAD AMPERES <br />G <br />- GROUND <br />GFI <br />- GROUND FAULT INTERRUPTER <br />HID <br />- HIGH INTENSISTY DISCHARGE <br />HORIZ <br />- HORIZONTAL <br />IG <br />- ISOLATED GROUND <br />LW <br />- LIGHT WHITE <br />HP <br />- HORSEPOWER, HEAT PUMP <br />HVAC <br />- HEATING, BENTILATING, AIR CONDITIONING <br />JB <br />- JUNCTION BOX <br />LRA <br />- LOCKED ROTOR AMPERES <br />MCB <br />- MAIN CIRCUIT BREAKER <br />MLO <br />- MAIN LUGS ONLY <br />N <br />- NEUTRAL <br />NIL <br />- NIGHT LIGHT <br />OB <br />- OUTLET BOX <br />PB <br />- PULL BOX, PUSH-BUTTON <br />PS <br />- PAY STATION <br />RECEPT <br />- RECEPTACLE <br />SF <br />- SUPPLY FAN <br />SPEC <br />- SPECIFICATIONS <br />SWECS <br />- SMOKE WARNING EMERGENCY CALL SYSTEM <br />TL <br />- TWISTLOCK <br />TTB <br />- TELEPHONE TERMINAL BOARD <br />TVTB <br />- TELEVISION TERMINAL BOARD <br />UNO <br />- UNLESS NOTED OTHERWISE <br />VERT <br />- VERTICAL <br />WM <br />- WATT MISER <br />WP <br />- WEATHERPROOF <br />WW <br />- WARM WHITE <br />XFMR <br />- TRANSFORMER <br />ELECTRICAL POWER PLAN DRAWING NOTES: O <br />SCALD 1/4"il'-" 1. ELECTRICAL WORK IN THIS AREA IS EXISTING TO REMAIN. <br />HVAC UNITS DISCONNECT AND FEEDER SCHEDULE <br />UNIT ID. <br />WIRE AND CONDUIT SIZES <br />DISCONNECT <br />MCA/MOCP <br />CU-1 <br />3 # 8 AND 1 #10 E.G. - 3/4" C <br />60/3/45/3R <br />26 <br />45 <br />CU-2 <br />3 # 8 AND 1 #10 E.G. - 3/4" C <br />60/3/40/3R <br />23 <br />40 <br />AHU-1 <br />3 # 6 AND 1 #10 E.G. - 1" C <br />60/3/50 <br />46 <br />50 <br />AHU-2 <br />2 # 8 AND 1 #10 E.G. - 3/4" C <br />60/2/40 <br />37 <br />EEI <br />* VERIFY HVAC UNIT INFORMATION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH -IN. <br />2. PROVIDE A FLUSH MOUNTED WP JUNCTION BOX FOR FUTURE TENANT SIGN. <br />ROUTE HOMERUN VIA TIMECLOCK. <br />3. EXTEND A 1" CONDUIT TO TELEPHONE COMPANY TERMINAL CABINET. <br />FURNISH WITH PULLSTRING. <br />4. PROVIDE FINAL CONNECTION TO THE ROOFTOP UNITS. REFER TO THE HVAC <br />UNITS DISCONNECT AND FEEDER SCHEDULE. <br />5. OUTLET MOUNTED IN MILL WORK COORDINATE EXACT LOCATION WITH <br />VERIZON AND GENERAL CONTRACTOR <br />6. PROVIDE FINAL CONNECTION TO THE ELECTRIC WATER HEATER. <br />2 POLE 30 AMP SWITCH FLUSH MOUNTED ADJACENT TO .Ta,ki,,A <br />HEATER FOR A LOCAL DISCONNECT. -lv ZI <br />7. PROVIDE FINAL CONNECTION TO THE ELECTRIC WATER <br />RECEPTACLE CORD AND CAP IF REQUIRED. COORDINATE <br />8. CEILING MOUNTED RECEPTACLE FOR SHOW WINDOW LIGHTING. <br />5. RECEPTACLE FOR TELEPHONE EQUIPMENT AND TIMECLOCK LOCATION. SEE <br />THE ELEVATION AT TENANT PANEL DETAIL ON SHEET E1. <br />ova.0U <br />i IS ovoce <br />Z <br />N <br />J <br />N <br /># <br />� <br />� <br />7 <br />— <br />Z <br />i.0 <br />w ft*lrm a w D�ai, L_c <br />iw�1Owr <br />CwwAW . e °VAC`sK <br />.iuch qj IF <br />1Ks' +o wK .;Ivv <br />Aww 6= ~ 71Ue 17 <br />oR au ufaa stele. coat <br />L:.. <br />v� <br />v/ <br />W <br />J <br />W <br />z <br />p <br />OiR <br />N <br />o <br />J <br />L� <br />v <br />U) <br />p� <br />W <br />6L <br />cIf _ <br />7 <br />cl <br />Wes= <br />W d <br />IL <br />c� N <br />LI!OOLUEDATE <br />-08 <br />JOB No. <br />9012 <br />OHEET TITLE <br />ELECTRICAL POWER <br />RAN <br />REVIOIONO <br />A <br />02-19-09 <br />DRAWN *R <br />DEMNED � <br />REVISED <br />OHEET No. <br />