ELECTRICAL SPECIFICATIONS:
<br />THE WORK UNDER THE REQUIREMENTS OF THESE SPECIFICATIONS SHALL BE IN
<br />OCONFORMANCE WITH THE LATEST EDI11ON OF THE NATIONAL ELECTRICAL CODE.
<br />THE INSTALLATION SHALL ALSO COMPLY WITH ALL APPLICABLE RULES AND
<br />REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES.
<br />ALL ELECTRICAL EQUIPMENT SHALL HAVE UL LABEL AND SHALL BE OF
<br />O SPECIFICATION GRADE.
<br />POWER DISTRIBUTION HOUSE PANELBOARD: PROVIDE DEAD —FRONT,
<br />O3 SAFETY —TYPE POWER DISTRIBUTION PANELBOARDS AS INDICATED; WITH
<br />PANELBOARD SWITCHING AND PROTECTIVE DEVICES IN QUANTITIES, RATINGS,
<br />TYPES, AND WITH ARRANGEMENT SHOWN; WITH ANTI —TURN, SOLDERLESS
<br />PRESSURE TYPE MAIN LUG CONNECTORS APPROVED FOR USE WITH COPPER
<br />CONDUCTORS.
<br />HOUSE PANELBOARDS SHALL BE EQUAL TO SQUARE D TYPE "NQOD". VOLTAGE
<br />®SHALL BE AS INDICATED. ACCEPTABLE MFG.; G.E., SIEMENS AND
<br />CUTLER —HAMMER.
<br />OTENANT PANELBOARDS: PROVIDE DEAD —FRONT SAFETY TYPE LIGHTING AND
<br />BRANCH CIRCUIT PANELBOARDS AS INDICATED; WITH SWITCHING AND PROTECTIVE
<br />DEVICES IN QUANTITIES, RATINGS, TYPES AND ARRANGEMENTS SHOWN; WITH
<br />ANTI —TURN, SOLDERLESS PRESSURE TYPE LUG CONNECTORS APPROVED FOR USE
<br />WITH COPPER CONDUCTORS.
<br />© TENANT PANELBOARDS SHALL BE SQUARE D TYPE "QO". PANELBOARD BOXES
<br />SHALL BE FIVE AND THREE —FOURTHS INCHES (5 3/4") DEEP. VOLTAGE SHALL
<br />BE AS INDICATED.
<br />OALL PANELBOARDS SHALL BE CONNECTED, DISTRIBUTED PHASE WITH CIRCUIT
<br />NUMBERING AS INDICATED ON THE DRAWINGS. PANELBOARDS SHALL BE
<br />NUMBERED WITH ODD NUMBERS ON THE LEFT SIDE OF THE PANEL AND EVEN
<br />NUMBERS ON THE RIGHT SIDE OF THE PANEL.
<br />UNLESS OTHERWISE INDICATED, PROTECTIVE DEVICES SHALL BE MOUNTED WITH
<br />®TOP OF CABINET OR ENCLOSURE 6'-6" ABOVE FINISHED FLOOR, SHALL BE
<br />PROPERLY ALIGNED, AND SHALL BE ADEQUATELY SUPPORTED INDEPENDENTLY OF
<br />THE CONNECTING RACEWAYS, ALL STEEL SHAPES, ETC., NECESSARY FOR THE
<br />SUPPORT OF THE EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE
<br />CONTRACTOR WHERE THE BUILDING STRUCTURE IS NOT SUITABLE FOR MOUNTING
<br />THE EQUIPMENT DIRECTLY THEREON. UNLESS OTHERWISE INDICATED, ALL BRANCH
<br />CIRCUIT PROTECTIVE DEVICES ENCLOSURES SHALL BE NEMA TYPE I, GENERAL
<br />PURPOSE TYPE. CIRCUIT PROTECTIVE DEVICES INSTALLED OUTDOORS OR EXPOSED
<br />TO THE WEATHER SHALL HAVE WEATHERPROOF ENCLOSURES, NEMA TYPE "3R"
<br />OR TYPE "4".
<br />O9 ALL SAFETY SWITCHES SHALL BE GENERAL DUTY TYPE. SWITCH MECHANISM
<br />SHALL BE QUICK -MAKE, QUICK -BREAK. COVER SHALL BE INTERLOCKED WITH
<br />MECHANISM TO PREVENT OPENING UNLESS SWITCH IS IN THE "OFF" POSITION.
<br />ALL ENCLOSURES SHALL BE PRIMED AND FINISHED TO RESIST RUSTING AND
<br />CORROSION. SWITCHES SHALL BE ITE, GENERAL ELECTRIC, SQUARE-D, OR
<br />CUTLER -HAMMER.
<br />10 CIRCUIT BREAKERS FOR MOUNTING IN HOUSE PANELBOARD SHALL BE BOLT —ON
<br />TYPE, MOLDED PLASTIC CASE, AIR CIRCUIT BREAKER TYPE. BREAKERS SHALL
<br />HAVE THERMAL MAGNETIC TRIP UNITS AND MULTI —POLE BREAKERS SHALL HAVE
<br />A COMMON TRIP BAR SO THAT THE TRIPPING OF ONE POLE WILL AUTOMATICALLY
<br />TRIP ALL POLES OF THE BREAKER. BREAKERS SHALL BE TRIP FREE AND TRIP
<br />INDICATING AND SHALL HAVE QUICK —MAKE, QUICK —BREAK CONTACTS.
<br />UPON COMPLETION OF WORK CORRECT ALL PANELBOARD CIRCUIT DIRECTORY
<br />11 CARDS TO REFLECT AS —BUILT CONDITIONS. PANELBOARD DIRECTORIES SHALL BE
<br />UPDATED WITH TYPEWRITTEN ACCURATE AND CURRENT INFORMATION BY THE
<br />CONTRACTOR AT THE END OF CONSTRUCTION. DIRECTORIES SHALL REFLECT
<br />RECORD CONDITIONS AND INCLUDE CIRCUIT NUMBER, TYPE AND LOCATION OF
<br />LOAD. A SET OF AS —BUILT DRAWINGS SHALL ALSO BE PREPARED AND TURNED
<br />OVER TO THE OWNER.
<br />12 ALL CONDUCTORS SHALL BE THHN/THWN COPPER #12 MIN. AND INSTALLED IN A
<br />COMPLETELY ENCLOSED RACEWAY SYSTEM.
<br />13 UNLESS SPECIFICALLY NOTED ON DRAWINGS, RACEWAYS SHALL COMPLY WITH THE
<br />FOLLOWING:
<br />RACEWAYS EXPOSED TO THE WEATHER OR IN DAMP LOCATIONS
<br />SHALL BE GALVANIZED RIGID STEEL WITH THREADED CONNECTIONS.
<br />RACEWAYS SHALL BE SIZED FOR THE CONDUCTORS INSTALLED,
<br />MINIMUM 1/2". FULL SIZE MC CABLE IS ACCEPTABLE IN DRY LOCATIONS.
<br />HOMERUNS TO PANELS TO BE IN CONDUIT.
<br />RACEWAYS RUN BELOW GRADE SHALL BE PVC , EXPOSED ON BUILDING
<br />14 EXTERIOR SHALL BE RIGID STEEL CONDUIT.
<br />ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE
<br />15 AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND EQUIPMENT.
<br />16 ALL RACEWAYS SHALL BE SECURELY SUPPORTED FROM THE BUILDING
<br />STRUCTURE.
<br />17 ALL RACEWAYS SHALL BE PROVIDED WITH EQUIPMENT GROUND CONDUCTOR.
<br />ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE
<br />18 SCREW FASTENED COVERS. OPEN KNOCK —OUTS OR HOLES IN BOXES SHALL BE
<br />PLUGGED WITH A SUITABLE BLANKING DEVICES.
<br />OUTLET BOXES FOR EXPOSED WALL MOUNTING AND OUTDOOR INSTALLATION
<br />19 SHALL BE CAST METAL TYPE "FS" OR "FD" BOXES WITH SUITABLE GALVANIZED
<br />SHEET STEEL COVERS, OR CAST METAL WEATHERPROOF OR VAPOR TIGHT COVERS
<br />WHEN NOTED ON THE DRAWINGS.
<br />QUNLESS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER N0. 12 AWG.
<br />MINIMUM. OR SIZE AS SHOWN ON DRAWINGS. CONDUCTORS SHALL HAVE TYPE
<br />'THHN/THWN' INSULATION.
<br />21 SPLICES, TAPS AND ATTACHMENT FITTINGS AND LUGS SHALL BE ELECTRICALLY
<br />AND MECHANICALLY SECURE AND SOLDERLESS FOR CONDUCTORS SIZES No. 8
<br />AWG AND LARGER. THERE SHALL BE PLENTY OF SLACK CABLE IN BOXES,
<br />OUTLETS AND CABINETS TO INSURE THAT THERE IS NO BINDING AT THE
<br />BUSHINGS. ALL LUGS SHALL BE OF THE CORRECT SIZES FOR THE CONDUCTORS
<br />JOINED AND IN NO CASE SHALL STRANDS BE CUT FROM A CONDUCTOR IN ORDER
<br />TO FIT THE CONDUCTOR INTO A LUG. TAPING OF JOINTS SHALL BE WITH VINYL
<br />PLASTIC ELECTRICAL TAPE TO SECURE INSULATION STRENGTH EQUAL TO THAT OF
<br />THE CONDUCTORS JOINED.
<br />QTHE INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY
<br />GROUNDED AS REQUIRED BY THE NEC AND AS SPECIFIED HEREINAFTER.
<br />Q CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS.
<br />THE CONTRACTOR SHALL VERIFY ALL LOCATIONS WITH THE OWNER PRIOR TO
<br />® INSTALLATION. THEY SHALL NOT BE CHARGED FOR MINOR LOCATION CHANGES
<br />PRIOR TO INSTALLATIONS. LOCATIONS ARE APPROXIMATE. (DO NOT SCALE
<br />DRAWINGS).
<br />QTHESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL ELECTRICAL LAYOUTS
<br />FOR BIDDING PURPOSES ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR
<br />TO PREPARE DETAILED SHOP DRAWINGS AND CONFIRM SPACE ALLOCATIONS.
<br />©THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES FOR
<br />ELECTRICAL CONDUIT ROUTING AND EQUIPMENT PLACEMENT. AVOID
<br />INTERFERENCE WITH ARCHITECTURAL AND STRUCTURAL FEATURES SUCH AS:
<br />BEAMS, FOOTINGS, WINDOWS, ETC. NOTIFY ARCHITECT IMMEDIATELY OF ANY
<br />CONFLICTS.
<br />©THE ELECTRICAL CONTRACTOR THE HVAC FOREMAN AND GENERAL CONTRACTOR
<br />PROJECT MANAGER SHALL INSPECT & REVIEW THE CONDITIONS, AND SHALL
<br />COORDINATE THEIR WORK SO AS TO PROVIDE ADEQUATE SPACE ALLOWANCE
<br />ABOVE CEILING FOR ALL TRADES.
<br />THE PLANS SHOW THE LOCATION OF ALL FIXTURES AND EQUIPMENT AND ARE
<br />INTENDED TO DEPICT THE GENERAL INTENT OF THE WORK IN SCOPE, LAYOUT AND
<br />QUALITY OF WORKMANSHIP. THEY ARE NOT INTENDED TO SHOW IN MINUTE DETAIL
<br />EVERY AND ALL ACCESSORIES INTENDED FOR THE PURPOSE OF EXECUTION OF
<br />THE WORK, BUT SHALL BE UNDERSTOOD THAT SUCH DETAILS WILL BE PART OF
<br />THIS WORK.
<br />®THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE AND
<br />FUNCTIONAL SYSTEM: CONTROLS, AND CONNECTIONS TO NEW SERVICES,
<br />SUPPORTS, AND HARDWARE REQUIRED FOR THE SATISFACTORY OPERATION OF
<br />THE SYSTEM, WHETHER SPECIFICALLY SHOWN OR NOT ON THE DRAWINGS.
<br />30 WHERE DRAWINGS AND SPECIFICATIONS CONFLICT, IT SHALL BE THE
<br />RESPONSIBILITY OF THIS CONTRACTOR TO BRING SUCH CONFLICT TO THE
<br />ATTENTION OF THE ENGINEER FOR CLARIFICATION.
<br />ELECTRICAL SYMBOL LEGEND
<br />SYMBOL
<br />DESCRIPTI❑N
<br />M❑UNTING
<br />1 X 4 FLUORESCENT FIXTURE
<br />SEE FIXTURE
<br />�-V-�
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />2 X 4 FLUORESCENT FIXTURE
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />SHADING DENOTES FIXTURE WITH EM BATTERY PACK.
<br />SEE FIXTURE
<br />'NL' DENOTES FIXTURE UNSWITCHED FOR NIGHT LIGHT
<br />SCHEDULE
<br />FLUORESCENT STRIP FIXTURE
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />[]
<br />FLUORESCENT WALL BRACKET FIXTURE
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />PL FLUORESCENT DOWNLIGHT
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />I4 EX
<br />EXIT -SHADING DENOTES FACEPLATE LOCATION. LETTER
<br />SEE FIXTURE
<br />INDICATES TYPE. PROVIDE ARROWS AS REQUIRED.
<br />SCHEDULE
<br />SINGLE POLE SWITCH (20A-120/277)
<br />48" AFF OR AS
<br />S S3 So
<br />3' DENOTES 3-WAY 0 DENOTES OCCUPANCY SENSOR
<br />NOTED
<br />Go:
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />18" AFF OR AS
<br />IG DENOTES ISOLATED GROUND
<br />NOTED
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />18" AFF OR AS
<br />NOTED
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />48" AFF OR AS
<br />NOTED
<br />QUADRAPLEX RECEPTACLE, 125V, 20A
<br />18" AFF OR AS
<br />NOTED
<br />®
<br />POWER / TELEPHONE POLE
<br />SEE DETAIL OR
<br />AS NOTED
<br />OUTLET BOX OR J-BOX FOR POWER AND DATA
<br />18" AFF OR
<br />® Q
<br />SUPPLY TO FURNITURE SYSTEMS
<br />AS NOTED
<br />0
<br />COMBINATION VOICE/DATA OUTLET
<br />18, AFF OR AS
<br />NOTED
<br />0
<br />T.V. OUTLET
<br />18" AFF OR AS
<br />NOTED
<br />PANELBOARD 120/208V
<br />SEE PANELSCHEDULE
<br />RACEWAY CONCEALED IN WALL OR ABOVE CEILING
<br />SEE SPECIFICATIONS
<br />HOMERUN TO PANEL. LETTERS INDICATE PANEL,
<br />NUMBERS INDICATE CIRCUIT. NOTE: HASH MARKS
<br />SEE SPECIFICATIONS
<br />INDICATES THE NUMBER OF WIRES EXCLUDING
<br />THE REQUIRED EQUIPMENT GROUND.
<br />MOTOR, NUMERAL INDICATES HORSEPOWER
<br />AS NOTED
<br />$
<br />MOTOR RATED SWITCH WITH OVERLOAD
<br />MOUNTED ADJACENT
<br />RELAYS IF REQUIRED.
<br />TO EQUIPMENT
<br />NON -FUSIBLE SAFETY SWITCH -SIZE AS NOTED
<br />SEE SPECIFICATIONS
<br />FUS13LE SAFETY SWITCH -SIZE AS NOTED
<br />SEE SPECIFICATIONS
<br />17-
<br />FIRE ALARM DUCT DETECTOR ('RA'DENOTES
<br />MOUNTED IN
<br />RETURN AIR 'SA' DENOTES SUPPLY AIR)
<br />HVAC DUCTWORK
<br />®
<br />FAN OR AIR HANDLER SHUTDOWN RELAY
<br />MOUNTED
<br />O T ADJACENT
<br />EQUIPMENT O
<br />®
<br />FIRE ALARM VISUAL SIGNAL
<br />80" AFF OR
<br />AS NOTED
<br />Q
<br />FIRE ALARM MANUAL PULLSTATION
<br />48" AFF OR
<br />AS NOTED
<br />FIRE ALARM AUDIBLE/VISUAL SIGNAL. ADA
<br />80" AFF OR
<br />®4
<br />COMPATIBLE
<br />AS NOTED
<br />Q
<br />FIRE ALARM SMOKE DETECTOR
<br />ON CEILING OR
<br />AS NOTED
<br />FAW
<br />FIRE ALARM PANEL ('FACP' DENOTES FIRE ALARM
<br />60" AFF OR
<br />r__
<br />FAA
<br />CONTROL PANEL, 'FAA' DENOTES ANNUNCIATOR)
<br />AS NOTED
<br />EX
<br />DENOTES EXISTING DEVICE OR CIRCUIT TO REMAIN
<br />R
<br />DENOTE NEW LOCATION FOR RELOCATED DEVICE
<br />3O (�) j
<br />REFER TO LIKE NUMBERED NOTES
<br />NOTE: ALL MOUNTING HEIGHTS SHOWN ARE TO THE TOP OF THE
<br />DEVICE UNLESS NOTED OTHERWISE.
<br />NOT ALL SYMBOLS APPEAR ON PLANS.
<br />. -j:' Re] ilk
<br />AFF
<br />- ABOVE FINISHED FLOOR
<br />AHU
<br />- AIR HANDLING UNIT
<br />BFG
<br />- BELOW FINISHED GRADE
<br />C
<br />- CONDUIT
<br />CW
<br />- COOL WHITE
<br />DACP
<br />- DOOR ALARM CONTROL PANEL
<br />DIN
<br />- DOWN
<br />EF
<br />- EXHAUST FAN
<br />EG
<br />- EQUIPMENT GROUND
<br />ENCL
<br />- ENCLOSURE
<br />EWC
<br />- ELECTRIC WATER COOLER
<br />EWH
<br />- ELECTRIC WATER HEATER
<br />WX
<br />- EXPLOSION PROOF
<br />FCU
<br />- FAN COIL UNIT
<br />FHP
<br />- FRACTIONAL HORSE POWER
<br />FLA
<br />- FULL LOAD AMPERES
<br />G
<br />- GROUND
<br />GFI
<br />- GROUND FAULT INTERRUPTER
<br />HID
<br />- HIGH INTENSISTY DISCHARGE
<br />HORIZ
<br />- HORIZONTAL
<br />IG
<br />- ISOLATED GROUND
<br />LW
<br />- LIGHT WHITE
<br />HP
<br />- HORSEPOWER, HEAT PUMP
<br />HVAC
<br />- HEATING, BENTILATING, AIR CONDITIONING
<br />JB
<br />- JUNCTION BOX
<br />LRA
<br />- LOCKED ROTOR AMPERES
<br />MCB
<br />- MAIN CIRCUIT BREAKER
<br />MLO
<br />- MAIN LUGS ONLY
<br />N
<br />- NEUTRAL
<br />NIL
<br />- NIGHT LIGHT
<br />OB
<br />- OUTLET BOX
<br />PB
<br />- PULL BOX, PUSH-BUTTON
<br />PS
<br />- PAY STATION
<br />RECEPT
<br />- RECEPTACLE
<br />SF
<br />- SUPPLY FAN
<br />SPEC
<br />- SPECIFICATIONS
<br />SWECS
<br />- SMOKE WARNING EMERGENCY CALL SYSTEM
<br />TL
<br />- TWISTLOCK
<br />TTB
<br />- TELEPHONE TERMINAL BOARD
<br />TVTB
<br />- TELEVISION TERMINAL BOARD
<br />UNO
<br />- UNLESS NOTED OTHERWISE
<br />VERT
<br />- VERTICAL
<br />WM
<br />- WATT MISER
<br />WP
<br />- WEATHERPROOF
<br />WW
<br />- WARM WHITE
<br />XFMR
<br />- TRANSFORMER
<br />ELECTRICAL POWER PLAN DRAWING NOTES: O
<br />SCALD 1/4"il'-" 1. ELECTRICAL WORK IN THIS AREA IS EXISTING TO REMAIN.
<br />HVAC UNITS DISCONNECT AND FEEDER SCHEDULE
<br />UNIT ID.
<br />WIRE AND CONDUIT SIZES
<br />DISCONNECT
<br />MCA/MOCP
<br />CU-1
<br />3 # 8 AND 1 #10 E.G. - 3/4" C
<br />60/3/45/3R
<br />26
<br />45
<br />CU-2
<br />3 # 8 AND 1 #10 E.G. - 3/4" C
<br />60/3/40/3R
<br />23
<br />40
<br />AHU-1
<br />3 # 6 AND 1 #10 E.G. - 1" C
<br />60/3/50
<br />46
<br />50
<br />AHU-2
<br />2 # 8 AND 1 #10 E.G. - 3/4" C
<br />60/2/40
<br />37
<br />EEI
<br />* VERIFY HVAC UNIT INFORMATION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH -IN.
<br />2. PROVIDE A FLUSH MOUNTED WP JUNCTION BOX FOR FUTURE TENANT SIGN.
<br />ROUTE HOMERUN VIA TIMECLOCK.
<br />3. EXTEND A 1" CONDUIT TO TELEPHONE COMPANY TERMINAL CABINET.
<br />FURNISH WITH PULLSTRING.
<br />4. PROVIDE FINAL CONNECTION TO THE ROOFTOP UNITS. REFER TO THE HVAC
<br />UNITS DISCONNECT AND FEEDER SCHEDULE.
<br />5. OUTLET MOUNTED IN MILL WORK COORDINATE EXACT LOCATION WITH
<br />VERIZON AND GENERAL CONTRACTOR
<br />6. PROVIDE FINAL CONNECTION TO THE ELECTRIC WATER HEATER.
<br />2 POLE 30 AMP SWITCH FLUSH MOUNTED ADJACENT TO .Ta,ki,,A
<br />HEATER FOR A LOCAL DISCONNECT. -lv ZI
<br />7. PROVIDE FINAL CONNECTION TO THE ELECTRIC WATER
<br />RECEPTACLE CORD AND CAP IF REQUIRED. COORDINATE
<br />8. CEILING MOUNTED RECEPTACLE FOR SHOW WINDOW LIGHTING.
<br />5. RECEPTACLE FOR TELEPHONE EQUIPMENT AND TIMECLOCK LOCATION. SEE
<br />THE ELEVATION AT TENANT PANEL DETAIL ON SHEET E1.
<br />ova.0U
<br />i IS ovoce
<br />Z
<br />N
<br />J
<br />N
<br />#
<br />�
<br />�
<br />7
<br />—
<br />Z
<br />i.0
<br />w ft*lrm a w D�ai, L_c
<br />iw�1Owr
<br />CwwAW . e °VAC`sK
<br />.iuch qj IF
<br />1Ks' +o wK .;Ivv
<br />Aww 6= ~ 71Ue 17
<br />oR au ufaa stele. coat
<br />L:..
<br />v�
<br />v/
<br />W
<br />J
<br />W
<br />z
<br />p
<br />OiR
<br />N
<br />o
<br />J
<br />L�
<br />v
<br />U)
<br />p�
<br />W
<br />6L
<br />cIf _
<br />7
<br />cl
<br />Wes=
<br />W d
<br />IL
<br />c� N
<br />LI!OOLUEDATE
<br />-08
<br />JOB No.
<br />9012
<br />OHEET TITLE
<br />ELECTRICAL POWER
<br />RAN
<br />REVIOIONO
<br />A
<br />02-19-09
<br />DRAWN *R
<br />DEMNED �
<br />REVISED
<br />OHEET No.
<br />
|