ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />150A/200A INDOOR <br />PANEL CENTER <br />#14 to lights & outlets <br />#12 to appliances and GFI <br />#10 to WH <br />#a to Range <br />#6 to HVAC <br />v <br />�5 50=2/0 <br />200=4/0 in 2" Conduit <br />200 amp <br />150 amp <br />UNDERGROUND <br />Disconnect <br />SERVICE BY POWER CO. <br />INTERSYSTEM <br />4 Bare Cu Ground <br />BONDING <br />O *4 GROUNDING WIRE <br />TERMINATION PER <br />WITH CODE APPROVED <br />NEC 17, 250.94 <br />��J// CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />GENERAL ELECTRICAL NOTES: Typical 150-200 Amp Electrical Riser Diagram REV, 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan Is intended for bid purposes only. All work shall be done In strict accordance With the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSUUL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory, <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />With R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />I� <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />j3 <br />THREE-WAY SWITCH <br />�?4 <br />FOUR-WAY SWITCH <br />jR <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />116) <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />DB <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />a <br />TELEVISION (OPTIONAL) <br />© 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />own <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C� J <br />ROUGH -IN FOR OPT. CEILING FAN <br />a <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />J <br />OPT. CEILING FAN <br />G9 <br />(1) PHONE LINE, (1) DATA PORT <br />1.5"VTR ,111 <br />I� <br />I <br />I <br />I <br />r� <br />� i I <br />I I I I <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />SWITCH FOR DIS <br />KITCHEN <br />IGFI <br />IZE <br />DEDICATED <br />RECEPTACLE <br />I FOR MICROWAVE <br />IGFI RANGE HOOD <br />PER SPECS <br />/ I I <br />r----------- <br />ROUGH IN FOR 01// 1 1 1 <br />OPT. CLG. FAN/ I I <br />`LIGHT PRE -WIRED 7 <br />BEDROOM 2 <br />, I I <br />I I <br />( I I <br />I-----------� <br />( I <br />I <br />I <br />I I <br />I <br />I I <br />I 1 <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I 1 <br />I 1 <br />I I <br />I I <br />I <br />I <br />L---------------------------------------I <br />SWITCH FOR <br />DISPOSAL IN <br />CABI NET — <br />I( II <br />I I ALT 1 I <br />AC PAD <br />WP <br />GFI <br />DISC. <br />LU <br />LU Z <br />�OQ <br />S <br />� <br />LL <br />LU <br />O co <br />0 <br />to <br />�• ` PER SPECS �, <br />3711 <br />ELECTRICAL PLANS -A <br />OPTIONAL LIGHTING <br />SCALE: Y4"=1'-0" <br />SCALE: Y4"=1'-0" <br />Imo. <br />cl <br />tr. <br />C <br />O <br />'- <br />-o <br />a <br />O W <br />'-moo <br />C f0 f� C, <br />N ar <br />+Q C4 Y <br />a t~ c <br />y m <br />a <br />w R� <br />c E <br />O- U <br />M <br />N <br />O <br />N <br />1 <br />N <br />O <br />To the best of the Engineers knowledge, Information and belief, <br />the structural plans and specifications contained <br />within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential <br />7th Edition. <br />Engineers signature and seal is only for <br />the structural engineering portion of the drawing pages bearing <br />Engineers signature and seal. <br />th <br />a 8 <br />N <br />a N 19 <br />0 v <br />Ii N040� <br />4 M <br />LL <br />Lu <br />u- <br />a. <br />•� m Q1 <br />a <br />Z04 <br />a <br />000 <br />LL <br />co N <br />N MZ <br />Q0 <br />OU <br />9 <br />Z <br />W <br />El El <br />z <br />Z <br />W <br />N <br />W 0 <br />.O <br />� <br />w <br />LU <br />0 <br />z <br />J <br />tl C <br />G <br />ti <br />w <br />2p <br /><F <br />a p <br />nW <br />z® <br />i— rp <br />10 <br />U U <br />� U <br />ZU <br />E <br />*=wZ <br />�z <br />N M <br />C <br />$u <br />a3 ij <br />z1Zz <br />> <br />Z <br />55 J <br />a� <br />�2 <br />8$ <br />g0 <br />W <br />m <br />$ <br />as <br />.0 <br />_ <br />�6 <br />rn <br />B <br />co <br />N <br />= <br />N <br />M <br />L O <br />Cr <br />g <br />N <br />m <br />N <br />o <br />L 0 <br />U') <br />.� <br />c� <br />O <br />m NO <br />Qi <br />Ln <br />r <br />Q <br />N N <br />N <br />T <br />E <br />N cp <br />Z° <br />M <br />Z <br />Z <br />E <br />M <br />a� <br />U <br />_j q p <br />JOB <br />NO: <br />23-00511 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />