Laserfiche WebLink
PLAN NOTES <br />FL❑RIDA BUILDING C❑DE 2004 <br />FASTENING SCHEDULE <br />R502.1 Identification. <br />Load -bearing dimension lumber for joists, beams and girders shall be identified by a rade mark of a lumber grading or <br />inspection agency that has been appproved by an accreditation body that complies wi.Th DOC PS 20. In lieu of a grade mark, <br />a certificate of inspection issued by a lumber grading or inspection agency meeting the requirements of this section shall <br />be accepted. <br />R5021,1 Preservatively treated lumber. <br />Preservatively treated dimension lumber shall also be identified as required by Section R319.1. <br />R502.1.2 Blocking and subflooring. <br />Blocking shall be a minimum of utility grade lumber. Subflooring may be a minimum of utility grade lumber or No. 4 common <br />rade 5oards, <br />9 <br />R502.1.3 End- jointed lumber. <br />Appproved end-��''Iointed lumber identified by a grade mark conforming to Section R501.2 may be used interchangeably with <br />solid -sawn memlaers of the same species and grade. <br />R502.1.4 Prefabricated wood I- joists. <br />Structural cappacities and design provisions for prefabricated wood I -joists shalt be established and monitored in accordance <br />with ASTM D 5055. <br />R502.1.5 Structural glued laminated timbers. <br />Glued laminated timbers shall be manufactured and identified as required in AITC A190.1 and ASTM D 3737. <br />R502.2 Design and construction. <br />Floors shall be designed and constructed in accordance with the provisions of this chapter, Figure R502.2 and Sections <br />R319 and R320 or in accordance with AF&PA/NDS, <br />R502.2.1 Decks. <br />Where supported by attachment to an exterior wall, decks shall be positively anchored to the primary structure and <br />designed for both vertical and lateral loads as applicable. Such attachment shall not be accomplished by the use of <br />toenails or nails subject to withdrawal. Where positive connection to the primary building structure cannot be verified <br />during inspection, decks shall be self-supporting, For decks with cantilevered framing members, connections to exterior <br />walls or other framing members, shall be designed and constructed to resist uplift resulting from the full live load <br />specified in Table flirr'5 acting on the cantilevered portion of the deck. <br />R502.3 Allowable joist spans. <br />Spans for floor joists shall be in accordance with Tables R502,3.1(1) and R502,3.1C2). For other grades and species and for <br />other loading conditions, refer to the AF&PA Span Tables for Joists and Rafters, <br />R502.3.1 Sleeping areas and attic joists. <br />Table R502.3,1(1) shall be utilized to determine the maximum allowable span of floor oists that support sleepingg areas and <br />attics that are accessed by means of a fixed stairway provided that the design hive load does not exceed 30 sf <br />(1.44 kN/m2) and the design dead load does not exceed 10 psf WAS kN/m2). The allowable span of ceiling joists that support <br />attics utilized for limited storage or no storage shall be determined in accordance with Section R802,4. <br />R502.3.2 Other floor joists. <br />Table R502.3.1C2) shall be utilized to determine the maximum allowable span of floor joists that support all areas of the <br />building, other than sleeping and attics, provided that the design live load does not exceed 40 psf (1.92 kN/m2) and the <br />design dead does not exceed 10 psf WAS kN/m2). <br />R502.3,3 Floor cantilevers.. <br />Floor cantilever spans shall not exceed the nominal depth of the wood floor joist. Floor cantilevers constructed in <br />accordance with Table R502.3.3(1) shalt be permitted when supporting a light -frame bearing wall and roof only. Floor <br />cantilevers supporting an exterior balcony are permitted to be constructed in accordance with Table R502, 3,3(2). <br />R502,5 Allowable girder spans. <br />The allowable spans of girders fabricated of dimension lumber shall not exceed the values set forth in Tables <br />R502.5(l) and R502.5(2). <br />R503.1 Lumber sheathing. <br />Maximum allowable spans for lumber used as floor sheathing shall conform to Tables R503.1, R503.2.1.1C1) and R503.2.1.1C2). <br />R503.1.1 End joints, - <br />End joints in lumber used as subflooring shall occur over supports unless end matched lumber is used, in which case each <br />piece shall bear on at least two joists. Subflooring may be omitted when joist spacing does not exceed 16 inches (406 mm) <br />and a 1-inch (25,4 mm) nominal tongue -and -groove wood strip flooring is applied perpendicular to the joists, <br />SECTION R506 <br />C❑NCRETE FL❑❑RS (UN GR❑UND) <br />R506,1 General. - - <br />Concrete slab on ground floors shall be a minimum 3.5 inches (89 mm) thick (for expansive soils, see Section <br />R403,1.8 ). The specified compressive strength of concrete shall be as set forth in Section R402.2 <br />R506.2 Site preparation, <br />The area within the foundation walls shall have all vegetation, top soil and foreign material removed. <br />R506.2.1 Fill. <br />Fill material shall be free of ve etation and foreign material. The fill shall be compacted to assure uniform <br />support of the slab, and except where approved, the fill depths shall not exceed 24 inches (610 mm) for <br />clean sand or gravel and 8 inches (203 mm) for earth. <br />R506.2.2 Base. <br />A 4-inch-thick (102 mm) base course consisting of clean graded sand, ggravel, crushed stone or crushed <br />blast -furnace slag passing a 2-inch (51 mm) sieve shall be placed on the prepared subgrade when the slab <br />is below rade. <br />g <br />Exception: A base course is not required when the concrete slab is installed on well -drained or sand -gravel <br />mixture soils classified as Group I according to the United Soil Classification System in accordance with <br />T e R405,1 <br />abl <br />R506.2.3 Vapor retarder. <br />A 6 mil (0,006 inch; 152 pm) polyethylene or approved vapor retarder with joints tapped not less than <br />6 inches (152 mm) shall be placed between the concrete floor slab and the base course or the prepared <br />subgrade where no base course exists. <br />Exception: The vapor retarder may be omitted: <br />1. From garages, utility buildings and other unheated accessory structures. <br />2, From driveways, walks, patios and other flatwork not likely to be enclosed and heated at a later date, <br />3, Where approved by the building official, based on local site conditions. <br />R506.2,4 Joints. <br />Concrete slabs on ground shall be provided with joints in accordance with ACI 224.3R or other approved <br />methods. Joints shall be desi ned by an architect or engineer. <br />Exception: Joints are not required in unreinforced plain concrete slabs on ground or in slabs for one- and <br />two-family dwellings complying with one of the following: <br />1. Concrete slabs on ground containing synthetic fiber reinforcement. Fiber lengths and dosage amounts <br />shall comply with one of the following <br />(1) Fiber lengths shall be f inch to 2 inches (13 to 51 mm) in length. Dosage amounts shall c from <br />0.75 to 1.5 ,pounds per cubic yard (0.45 to 0,89 kg/m 3) in accordance with the manufacturer?s <br />rec mmendations, S, nt etic fibers hall co,m ly h gSTM C 1116. The m n fact er or supple <br />shah provide certiica ion of compliance wit ASwTM C 1116 when reques e� byEie building o� facial; or, <br />(2) Fiber length shall be from X inch to 2 inches (13 mm to 51 mm) in Lengc�th monofilament or fibrillated. <br />Dosage amounts shall be from 0,5 to 1.5 pounds per cubic yard (0.30 to 6.89 kg/m 3 ) to achieve <br />minimum 40 percent reduction of plastic shrinkage cracking of concrete versus a control mix in <br />accordance with ICB❑ AC32. Inde ndent to t results using minimum six (6) to tt s e amens shall be <br />provided to the cpmpliance with pI B A 2, Synthetic fiber shall comply with ATM �11c16, Para raph <br />4.1.3, Type III. The manufacturer or supplier shall provide certification of compliance with ASTM C1116 <br />when re ested b but din official. <br />2, Concrete sl% on rYoun� cd�tainin W .4 X W1.4 w wir r inf r m n f ri o in th <br />q 6x6 1 Bided e e o ce e t ab c l sated e <br />middle to the upperg one-third of tFie slp.b. Welded wire reinf r ementt fabric shall be supported with <br />approved materials or supports at spacings not to exceed 3Q feet (914 mm) or in accordance with the <br />manufacturer"s specifications, Welded plain wire reinforcement fabric for concrete shall conform to <br />. ASTM A 185, Standard Specification for Steel Welded Wire Reinforcement Fabric, Plain, for Concrete <br />Reinforcement . <br />R602.1 Identification. <br />Load -bearing dimension lumber for studs, plates and headers shall be identified by,a grade m44rk of a lumber grading <br />or inspection agency that has been approved by an accreditation body that complies with D❑l PS 20. In lieu of a g ade <br />" mark, a certification of 4)spection issued by a lumber grading or inspection agency meeting the requirements of this <br />section shal[ be accep e <br />R602.1,1 End -jointed lumber. <br />A roved end- jointed t tuber identified by a rac mark conforming to Section R602.1 may be used interchangeably with <br />s�Pd-sawn memkjers ofhe same species and -grade. <br />R602.1.2 Structural glued laminated timbers. <br />Glued laminated timbers shall be manufactured and identified as required in AITC A190.1 and ASTM D 3737. <br />R602.31 Stud size, height and spacing. <br />The size, height and spacing of studs shall be in accordance with Table R602.3<5). <br />Exceptions: <br />L Utility grade studs shall not be spaced more than 16 inches (406 mm) on center, shall not support more than a roof and <br />ceiling, and shall not exceed 8 feet (2438 mm) in height for exterior walls and load -bearing walls or 10 feet (3048 mm) <br />for interior nonload-bearing walls, <br />2. Studs more than 10 feet (3048 mm) in height which are in accordance with Table R602.3.1. <br />R602;4 Interior load -bearing walls. <br />Interior load -bearing walls shall be constructed, framed and fireblocked as specified for exterior walls. <br />R602.10 Wall bracing. <br />All exterior walls shall be braced in accordance with this section. In addition, interior braced wall lines shall be provided <br />in accordance with Section R602.10.1.1. <br />R602.10.3 Braced wall, panel construction methods, <br />The construction of braced wall panels shall be in accordance with one of the following methods: <br />1, Nominal 1-inch-hv-4-inch (25.4 mm by 102 mm) continuous diagonal braces let in to the top and bottom plates and the <br />intervenin studs or ap roved metal strap devices installed in accord�n e with the manufacturer?s specifications. The <br />tt- c h n 4 r s / r ) fr m <br />Le in bra ing shall be laced at an angle not more than 60 degrees 1,Oc6 rod) or less t a 5 deg ee CO 9 ad o <br />the horizontal. <br />m i kn i n m xim m of 24 in hes C 10 mm). <br />2. Wood boards of 5/8 inch C15.9 tutu) net minimu th c ess applied d agqo allyy on studs spaced a a u c 6 <br />Diagonal boards shall be attached to studs in accordance with TabCe R602.3(1). <br />3. Wood structural panel sheathing with a thickness not less than 5/16 inch (7,9 mm) for 16-inch (406 mm) stud spacing and <br />and not less ,than 3/8 inch (`D.5 mm) for 24-inch (610 mm) stud spacing. Wood structural panels shall be installed in <br />accordance with Table R602,3(3). <br />4. ❑ne-half-inch (12.7 mm) or 25/32-inch (19.8 mm) thick structural fiberboard sheathing applied vertically or horizontally on <br />on studs spaced a maximum f 16 inches (406 mm) on center. Structural fiberboard sheathing shall be installed in <br />accordance with Table R602. (1). <br />5. Gypsum board with minimum X-inch (12.7 mm) thickness placed on studs spaced a maximum of 24 inches (610 mm) on center <br />and fastened at 7 inches (178 mm) on center with the size nails specified in Table R602.3(1) for sheathing and <br />Table R702.3.5 for interior gypsum board. <br />6. Particleboard wall sheathing panels installed in accordance with Table R602.3<4) <br />7. Portland cement plaster on studs spaced a maximum of 16 inches (406 mm) on center and installed in accordance with <br />8. Hardboard panel siding when installed in accordance with Table R703.4. <br />Exception: Alternate braced wall panels constructed in accordance with Section R602.10.6 shall be permitted to replace any <br />of the above methods of braced wall panels. <br />Section R703.6, <br />R606.13 Beam supports. <br />Beams, ggirders or other concentrated fonds supported by a wall or column shall have a bearing of at least 3 inches (76 mm) <br />in lengtY� measured parallel to the beam upon solid masonry not less than 4 inches (102 mm) in thickness, or upon a metal <br />bearing plate of adequate design and dimensions to distribute the load safely, or upon a continuous reinforced masonry <br />member projecting not less than 4 inches (102 mm) from the face of the wall, <br />R606.13.1 Joist bearing. <br />Joists shall have a bearing of not less than lXinches (38 mm), except as provided in Section R606.13, and shall be <br />supported in accordance with Figure R606.10C1). <br />SECTION R607 <br />UNIT MAS❑NRY <br />R607.1 Mortar. <br />Mortar for use in masonry construction shall comply with ASTM C 270. The type of mortar shall be in <br />accordance with Sections 607,1,1 and R607.1.2 and shall meet the proportion specifications of Table R607,1 <br />or the property specifications of ASTM C 270, <br />R607,1.1 Foundation walls. <br />Masonry foundation walls constructed as set forth in Tables R404,1,1(1) through R404.1.1C4) and mortar shall <br />be Type M or S. <br />R607.1.2 All other masonry. <br />Mortar for masonry serving as the lateral -wind -force -resisting system shall be Type M, S or N mortar. <br />TABLE R607.1 Refer to table for Mortar Proportions <br />R607.2 Placing mortar and masonry units. <br />R607,2.1 Bed and head joints. <br />Unless otherwise required or ind icated on the project drawings, head and bed joints shall be 3 / 8 inch <br />(9.5 mm) thick, except that the thickness of the bed joint of the starting course placed over <br />foundations shall not be less than '/< inch (6,4 mm) and not more than ? inch (19.1 mm). <br />R607.2.1.1 Mortar joint thickness tolerance. <br />Mortar joint thickness shall be within the following tolerances from the specified dimensions: <br />1. Bed joint: + 1 / 8 inch (3.2 mm). <br />2, Head joint: 4 inch (6.4 mm), + 3 / 8 inch (9.5 mm), <br />3. Collar joints: '/, inch (6,4 mm), + 3 / 8 inch (9.5 mm). <br />Exception: Nonload-bearing masonry elements and masonry veneers designed and constructed in accordance <br />with Section R703.7 are not required to meet these tolerances. <br />ReO7.2.2 Masonry unit placement. <br />The mortar shall be sufficiently plastic and units shalt be placed with sufficient pressure to extrude <br />mortar from the joint and produce a tight joint. <br />Deep furrowing of bed joints that produces voids shall not be permitted. Any units disturbed to the extent <br />that initial bond is broken after initial placement shall be removed and relaid in fresh mortar, Surfaces to <br />be in contact with mortar shall be clean and free of deleterious materials. <br />R607.2.2.1 Solid masonry. <br />All solid masonry units shalt be laid with full head and bed joints and all interior vertical joints that are <br />designed to receive mortar shall be filled, <br />R607.2.2.2 Hollow masonry. <br />For hollow masonry units, all head and bed joints shall be filled solidly with mortar for a distance in from <br />the face of the unit not less than the thickness of the face shell. <br />R607.3 Installation of wall ties. <br />The installation of wall ties shall be as follows: <br />1, The ends of wall ties sh all be embedded in mortar joints. Walt tie ends shall engage outer <br />face shells of hollow units by at least � inch (12.7 mm), <br />Wire wall ties shall be embedded at least 1% inches (38 mm) into the mortar bed of solid <br />masonry units or solid grouted hollow units. <br />2, Wall ties shall not be bent after being embedded in grout or mortar, <br />SECTION R613 <br />EXTERI❑R WIND❑WS AND DO❑R ASSEMBLIES <br />R613.1 General. <br />This section prescribes performance and construction requirements for exterior window systems installed in wall systems, <br />Waterproofing, sealing and flashing systems are not included in the scope of this section. <br />R6]3.2 Performance. <br />Exterior windows and doors shall be designed to resist the design wind loads specified in Table R301.2(2) adjusted for height <br />and exposure per Table R301.2(3). <br />R613.3 Exterior windows, sliding and patio glass doors. <br />R T tin n elin , <br />6]3 3.1 es g a d Lab g <br />Exterior windows and glass doors shall be tested by an approved independent tespting laboratory, and shall be labeled with <br />n r ved lotbelyldentifya:n,$ the m Y ufacturer, performance sharp ante tto indicatepCorvpdaPeedwi h �et�requiremeriprin <br />es o Qabo cr evalu ,ti n en . or Miami -Dade notice o acce <br />one of the following specifications: <br />ANSI/AAMA/NWWDA 101/I.S. 2-97 or 101/I.S. 2/NAFS or TAS 202 (HVHZ shall comply with TAS 202 utilizing ASTM E 1300-98 or <br />ASTM E 1300-02). <br />Glass Strength: Determination of load resistance of glass for specified loads of products tested and certified in <br />accordance with s. R613.3.1 shall be designed to comply with ASTM E 1300. <br />R613.3.2 Supplemental label. <br />A supplemental temporary label conforming to AAMA 203, Procedural Guide for the Window Inspection and Notification System, <br />shall be acceptable for establishing calculated allowable design pressures higher than indicated on the label required by <br />R613.3.1 for window sizes smaller than that required by the ANSL/AAMA/NWWDA 101/IS2 test requirements. This supplemental <br />label shall remain on the window until final approval by the building official. <br />R613.4 Exterior door assemblies. <br />Exterior door assemblies not covered b R613,3 or R613.4.1 shall be tested for structural integqrity in accordance with <br />ASTM F 33Q Procedure A t toad f 1. times the re wired desi re sure load. The o dd� shall be s t ined for pp <br />seconds with no permanent cieforma�ion of an main fr�me or par�e� �iem�ner in excess or �.4 percent a i 's span oflter <br />the load is remove H�/HZ shall c m t with TAyS 202. After ash ecifie�� .l adin the e shall b o glass br akage, <br />permanent damageo fasteners, �ia�dyware parts, or an oteher d5c mage whic� caseshe door oiae inoperabele, <br />The minimum test sizes and minim m design press res, shplyl be as indicated in Tapble R613.4 <br />The unit size tested shall uali all unit sm l.Yer in with a d/or height pf the same operation type and be limited to <br />ases where frame, panels net �tructura memabers main ain e same Profile as tested, <br />�613.4.1 <br />Sectional garage doors shall be tested for determination of structural performance under uniform static air pressure <br />ddiffer n e in accordance with ANSI/DASMA 108 or TAS 202 (HVHZ shall comply with TAS 202). <br />R613.4. �ustom do rs. <br />Custom Cone of a kind) exterior dgor assemblies shall be tested by an approved testing laboratory or be engineered in <br />accordance with accepted engineering practices, <br />R613,4.3 <br />DQorbe°i� ercnhan ea e to e b e rora o°rvecl rri lest eovi e tti n emit ertificapt' en s Y t-v to to ortor c�r engineer <br />y r{ �tl ty �g 0 p d ghat ih 'door com i� ri i5 d q �° gryea er <br />structural erfogrmance as demonstrated b accepted engineering practices. <br />RC�1l3.4.33.1 Option l ext ri r ddoor compone, t testing. <br />With tY e excepion o HR/HZ, exterior si�e-hinged door s embli s n t covered ,bb Section RR613.3 shp ll have the o tion to <br />have the components of, the assembly tested and rateq for $-truc�urol integrity in accordance with the followinpp <br />Window and door assemblies shall be b Nored in accordance with the published manufacturers recommendations td achieve <br />R613.5 Windborne debris protection. <br />R613.6 Anchorage methods. <br />specification+ <br />R613.6.1 Anchoring requirements. <br />the design pressure specified. Substitute anchoring systems used for substrates not specified by the fenestration <br />manufacturer shall provide equal or greater anchoring performance as demonstrated by accepted engineering practice. <br />R613,6.2 Masonry, concrete or other structural substrate. <br />Where the wood shim or buck thickness is less than 1% inches (38 mm), window and door assemblies shall be anchored through <br />the main frame or by jamb clip or subframe system, in accordance with the manufacturers published Installation instructions. <br />Anchors shall be securely fastened directly into the masonry, concrete or other structural substrate material. Unless <br />otherwise tested bucks shall extend beyond the interior face of the, window or door frame such that full support of the <br />frame is rovidec(. Shims shall be made from materials ca able of sustainingq a plicable loads, located and, applied in a <br />thicknesspcapable of sustainin ap plicable toads. Anchorsp shall be provided to transfer load from the window or door <br />frame to the rough opening s.4 rate, <br />/here the wood buck thickn ss is 1Y i the C3g mm) or rea er, the buck sh ll be secure, fastened to tra sf r ,gad to <br />the masonry concr�te or o her stru� uraT substrate nl the buck shall ex end beyond tyhe interior face of t�e window <br />or door frr,e. Win ow and door assem ies shall be, anchored througgh the main frame or by amb clip or subrame system <br />fir thro h the fllan e to tie secured ood buck ccgrdance itT) th anuf,acturers ubli hed installat on i tructions. <br />nless o-erwise tes�ed, bucks shall extend beyondn t�e interior ace o W window or door Frame such t at t support <br />of the frame is provided. Shims shall be made from materials capable of sustaining a plicable loads, located and applied in a <br />thickness caiiable of sustaining applicable loads. Anchors shall be provided to transfer load from the window or door frame <br />assembly to he secured wood buck. . <br />R613.6.3 Wood or other approved framing material. <br />Where the framing material is wood or other approved framing material, window and glass door assemblies shall be anchored <br />thr u h the m in frame or b amb 4li or ubfram s stem or throu h t e fl n e n,accorda ce with the anufa tur r?s <br />publ4i,sV�ed Instalation instru t)ior� . Shimsp, $hat be , m dPe iXrom m terials pqqb e o �us�gming apprc ble toed Lot tec� ann� <br />applied in a thickness capable o sustainin ap pl:caable loads. �nchors sat I provided to transfer load rom he window <br />or door frame to the rough opening subsrate. <br />R613.7 Mullions occurring between individual window and glass door assemblies. <br />R613.7.1 Mullions. <br />Mullion other than mull, w ch ar an me r t part of a window or, lq�ss cl asse bt tested ant{ labeled in <br />actor , ce with Section 3. halg bb test dab an ap roved testln Tabora or r""�� en i e d rdan itth <br />n in ran roc6ice. OI meti s L tse er ormance crit ria cited i Soe: ons ��1P3,/r�C, f��l ,c/ and 613,7.4. <br />accepp.ed e g ee q p t p <br />R613,7.2 Load- tr- - er, <br />Mulligns shall he designed to transfer the design pressure loads applied by the window and door assemblies to the rough <br />openingg substrate. <br />R613.7,3 Deflection. <br />Mullions shall be capable of resisting the design pressure loads applied by, the window and door assemblies to be supported <br />without deflecting more than L/175, where L is the span of the mullion in inches. <br />R613.7.4 Structural safety factor. <br />Mullions shall be capable of resisting a load of 1.5 times the desi n Pressure loads appplied by the window and door <br />assemblies to be supported without exceeding the appropriate ma erial stress levels, If tested by an approved laboratory, <br />the 15 times the design pressure load shall be sustained for 10 seconds, and the permanent deformation shall not exceed <br />0.4 percent of the mullion span after the 1,5 times design pressure load is removed. <br />R802.1 Identification. <br />Load -bearing dimension lumber for rafters, trusses and ceiling joists shall be identified by a grade mark of a lumber <br />grading or inspection a envy that has been approved by an accreditation body that complies with DOC PS 20. In lieu of a <br />rade mark, a certificage of inspection issued by a lumber grading or inspection agency meeting the requirements of this <br />ection shall be accepted. <br />R802.1.1 Blocking. <br />Blocking shall be a minimum of utility grade lumber. <br />R802,1,2 End- 'ointed lumber. <br />Approved end -jointed lumber identified by a grade mark conforming to Section R802,1 may be used interchangeably with <br />solid -sawn members of the same species and grade. <br />R802.1.3.1 Labelin <br />h n in: <br />Fire -retardant reated lumber and wood structural panels shall be labeled. The label s all co to <br />1, The identification mark of an approved agency in accordance with Section 1703.5 of the Florida Building Code, Building. <br />2. Identification of the treating manufacturer. <br />3. The name of the fire -retardant treatment. <br />4. The species of wood treated. <br />5, Flame spread and smoke developed rating. <br />6, Method drying after treatment, <br />7. Conformance with appropriate standards in accordance with Sections R802.1.3.2 through R802,1,3.5. <br />8, For FRTW exposed to weather, damp or wet location, the words ?No increase in the listed classification when subjected <br />to the Standard Rain Test? (ASTM D 2898). <br />R802.1.3.2 Strength adjustments, <br />Design values for untreated, lumber and wood, structural panels as specified in Section R802,1, shall be adjusted for fire <br />retardant -treated wood. Ad stm nts to ddesigqn values shall be based upon an approved m ,thod of investigation which takes <br />into consideration the effect s of the anticipbted temperature and humidity to which the fire -retardant -treated wood <br />will be sub ected, the type of treatment and redrying procedures. <br />R802,1,3.2.1 Wood structural panels. <br />The effect of treatment and the method of redrying after treatment, and exposure to hi h temperatures and high <br />- 9g i i r n with <br />- h l be determ ned n acco da ce <br />humidities on the flexure properties of fire retardant treated softwood plywood s a t <br />ASTM5Da5516orThe test data developed b ASTM ) 5516 shall be used to dey el ad'u ttm nt f ctors, ma ;mum load and <br />a p s both for untreated plyw�od desi n values in accordance with ,R�TM �30 Eac� manufncurer shads publish <br />the allowable maximum loads and spans for serve as floor and roof sheathing for their treatment, <br />R802.1.3.2.2 Lumber. <br />For each species of wood treated the effect of the treatment and the method of redrying after treatment and exposure <br />to high temperatures and higqh humidities on the allowable design properties of fire -retardant -treated lumber shall be <br />determined in accordance witTi ASTM D 5664. The test data developed by ASTM D 5664 shall be used to develop modification <br />factors for use at or near room temperature and at elevated temperatures and humidity in accordance with an approved <br />method of investigation. Each manufacturer shall publish the modification factors for service at temperatures of not less <br />than 80'F (26.7°C) and for roof framing. The roof framing modification factors shall take into consideration the <br />climatological location. <br />R802,1,3.3 Exposure to weather. <br />Where fire -retardant -treated wood is exposed to weather, or damp or wet locations, it shall be identified as 'Exterior' to <br />indicate there is no increase in the listed flame spread index as defined in Section R802.1.3 when subjected to ASTM D 2ege, <br />R802.1.3.4 Interior applications. <br />Interior fire -retardant -treated wood shall have a moisture content of not over 28 percent when tested in accordance <br />with ASTM D 3201 procedurggs at 92 percent relative humidity. Interior fire -retardant -treated wood shall be tested in <br />accordance with Section R9W.1.3.2.1 gr, R802.1f.3.2.2. Interior fire -retardant -treated wood designated as Type A shall be <br />tested in accordance with he provisions o this section. <br />R802.1.3.5 Moisture content. <br />Fire-retardant-treuated wood shall[ be dried to a moisture conteent of 19 percent or less for luumber and 15 ppercheQnt or <br />exceecP those userd cinuki�n drylntg theolumber nndrplywood subrriitedffor theatests describ deink�Sect%r�eOt2u .ClSfor not <br />plywood and R802.1.3,2.2 for lumber. <br />R802,1,4 Structural glued laminated timbers. <br />Glued laminated timbers shall be manufactured and identified as required in AITC A190,1 and ASTM D 3737. <br />R802,2 Design and construction. <br />Roof -ceilings shall be desigqned and constructed in accordance with the provisions of this chapter and Figgures R606,1OC1) <br />or in accordance with AFPA/NDS, Components of roof -ceilings shall be fastened in accordance with Table R602.30). <br />R802.3 Framing details, <br />Rafters shall be framed to ridge board or to each other with a gusset plate as a tie. Rid e board shall be at least <br />1-inch (25.4 mm) nominal thickness and not less in depth than the cut end of the rafter. At all valleys and hips there <br />shall be a valley or hip rafter not less than 2-inch (51 mm) nominal thickness and not less in depth than the cut end of <br />the rafter, Hip and valley rafters shalt be supported at the ridge by a brace to a bearing partition or be desi ned to <br />Carry and tribute the specif; to d at th,o point. Where th roof pitch is less than three units yerti aL in 1 units <br />horizontal -percent slope), s rucatural members that suppor rai'ters and ceiling joists, such as ridge �eams, nips and <br />valleys, shall be designed as beams. <br />R802.3.1 Ceiling joist and rafter connections. <br />Ceiling joists and rafters shall be nailed to each other in accordance with Tables R602.3(1) and R802.5.1<9), and the assembly <br />shall be nailed to the top wall plate in accordance with Table R602.3C1), Ceiling joists shall be continuous or securely joined <br />where they ,meet over inter; r partitions and nailed to adjacent rafters to provide a continuous tie across the building <br />when such joists are paralle� to the rafters. <br />Where ceiling joists are not parallel to rafters, subflooring or metal straps attached to the ends of the rafters shall <br />be installed in a manner, to provide a continuous tie across the buildinc� or rafters shall be tied to 1-inch by 4-inch <br />(25.4 mm by 102 mm) (nominal) minimum -size crossties. The connections shdT� be in accordance with Table R602,3C1) or connections <br />of equivalent capacities shall be provided. Where ceiling joists or rafter ties are not provided at the top plate, the ridge <br />formed by these rafters shall also be supported byy a girder designed in accordance with accepted engineering practice. <br />Rafter ties shall be spaced not more than 4 feet (1219 mm) on center. <br />R802.3.2 Ceiling joists lapped. <br />Ends of ceiling joists shall be lapped a minimum of 3 inches (76 mm) or butted over bearing partitions or beams and toenailed <br />to the bearin member. When eiling tt5 are used to provide resistance to rafter thrust, lapped joists shall be nailed <br />toggether in a cordance with able RblVlh and butted joists shall be tied together in a manner to resist such thrust. <br />R802.4 Allowable ceiling joist spans. <br />Spans for ceiling oists shall be in accordance with Tables R802.4(1) and R802.4(2). For other grades and species and for <br />other loading conditions, refer to the AF&PA Span Tables for Joists and Rafters. <br />R802.5 Allowable rafter spans. <br />Spans for rafters shall be in accordance with Tables R802,5.10) and R802,5.1(2). For other grades and species and for other <br />loading conditions, refer to the AF&PA Span Tables for Joists and Rafters. The span of each rafter shall be measured <br />along the horizontal projection of the rafter. <br />R802.5.1 Purlins. <br />Purlins are permitted to be installed to reduce the span of rafters as shown in Fi ure R802.5.1, Purlins shall be sized no <br />less than the required size of the rafters that they support. Purlins shall be continuous and shall be su ported by <br />2-inch by 4-inch (51 mm by 102 mm) braces installed to bearing walls at a slope not less than 45 degrees from the <br />horizontal. The braces shall be spaced not more than 4 feet <1219 mm) on center and the unbraced length of braces <br />shall not exceed 8 feet (2438 tutu). <br />R802.6 Bearing. <br />The ends of each rafter or ceiling joist shall have not less than IYa inches (38 mm) of bearing on wood or metal and <br />not less than 3 inches (76 mm) on masonry or concrete. <br />R802.6.1 Finished ceiling material. <br />If the finished ceiling material is installed on the ceiling prior to the attachment of the ceilin to the walls, such as in <br />construction at a factory, a compression strip of the same thickness as the finish ceiling material shall be installed <br />direct, above the top plate, of bearin walls if the com ressive strength of the finish ceiling material is less than the <br />loads it will be r quired ,to withstand, Me compression strip shall cover the entire tenth of such top plate and shall be <br />at least one -hat the width of the top plate. It shall be of material capable of tran matting the loads transferred <br />through it. <br />R802.7 Cutting and notching. <br />Structural roof members shall not be cut, bored or notched in excess of the limitations specified in this section. <br />R802.7.1 Sawn lumber. <br />Notches in solid lumber oists, rafters and beams shall not exceed one -sixth of the depth of the member, shall not be <br />tongrr than one-third o the depth of the member and shall not be located in the middle one-third of the span. Notches <br />at the ends of the member shall not exceed one-fourth the depth of the member. The tension side of members 4 inches <br /><102 tutu) or greater in nominal thickness shall not be notched except at the ends of the members. The diameter of the <br />holes bored or cut into members shall not exceed one-third the depth of the member. Holes shall not be closer than <br />2 inches (51 mm) to the top or bottom of the member or to an other hole located in the member. Where the member is <br />also notched, the hole shall not be closer than 2 inches (51 mm)Y to the notch. <br />Exception: Notches on cantilevered portions of rafters are permitted provided the dimension of the remaining portion of <br />the rafter is not less than 4-inch nominal (102 mm) and the length of the cantilever does not exceed 24 inches (610 mm). <br />R802.7.2 Engineered wood products. <br />Cuts, notches and holes bored in laminated veneer lumber, glue -laminated members or I- joists are not permitted unless the <br />the effect of such penetrations is specifically considered in the design of the member. <br />R802,8 Lateral support. <br />Rafters and ceiling joists having a depth -to -thickness ratio exceeding 5 to 1 based an nominal dimensions shall be provided <br />with lateral support at points of bearing to prevent rotation. <br />R802.8.1 Bridging. <br />Rafters and ceiling oists having a depth -to -thickness ratio exceeding 6 to 1 based on nominal dimensions shall be <br />supported laterally �y solid blocking, diagonal bridging (wood or metal) or a continuous 1-inch by 3-inch (25.4 mm by 76 mm) <br />wood strip nailed across the rafters or ceiling joists at intervals not exceeding 8 feet (2438 mmX <br />R802.9 Framing of openings. <br />❑penings in roof and ceiling framing shall be framed with header and trimmer ,joists. When the header joist span does not <br />exceed 4 feet (1219 mm), the header joist may be a single member the same size as the ceiling joist or rafter. Single <br />trimmer �.1o�asts ma be used, to Carry a sin le he der ' t that is located within 3 feet (914 mm) of ,the trimmer foist <br />bearin Vhen th header joist s avS excee s fl Bet c1219 tutu), the trimmer joists, and the header oist shall be doubled <br />and of sufficient cross section to support, the ceilingq �IIoists or rafter framing into the header. Fo proved hangers shall <br />be used for the header oist to trimmer joist connec`tibns when the header joist span exceeds 6 feet (1829 mm). Tail <br />��fists over 12 feet .C365� m ) ion shall be supported at the header by framing anchors or on ledger strips not less <br />an 2 inches by 2 inches (1 mm �y 51 tutu). <br />R802.10 Wood trusses. <br />R802.10.1 Truss design drawings. <br />Truss design drawings prepared in conformance with Section R802.10.1, shall be provided to the building official and approved <br />prior to installation. Truss design drawings shalt include, at a minimum, the information specified below. Truss design drawing <br />shall be provided with the shipment of trusses delivered to the jobsite. <br />1, Slope or depth, span and spacing. <br />2. Location of all joints. <br />3. Required bearing widths. <br />4, Design loads as applicable. <br />4.1. Top chord live load. <br />4.2. Top chord dead load. <br />4.3. Bottom chord live load. <br />4.4, Bottom chord dead load. <br />4.5. Concentrated loads and their points of application. <br />4.6. Controlling wind and earthquake loads. <br />5. Adjustments to lumber and joint connector design values for conditions of use. <br />6, Each reaction force and direction. <br />7. Joint connector type and description (e.g., size, thickness or gauge), and the dimensioned location of each joint <br />connector except where symmetrically located relative to the joint interface. <br />8. Lumber size, species and grade for each member. <br />9. Connection requirements or: <br />9.1. Truss to truss girder. <br />9.2. Truss ply to ply. <br />9.3. Field splices. <br />10. Calculated deflection ratio and/or maximum description for live and total load. <br />11. Maximum axial compression forces in the truss members to enable the building designer to design the size, connections <br />and anchorage of the permanent continuous lateral bracing. Forces shall be shown on the truss design drawing or on <br />supplemental documents, <br />12. Required permanent truss member bracing location. <br />R802.10.2 Design. <br />Wood trusses shall be designed in accordance with gccepted en ineering practice. The design and manufactu <br />re of metal <br />plate connected wood trusses shall comply with ANSI/TP1 ]. The russ desigqn drawings shall be prepared by a registered <br />professional where required by the statutes of the jurisdiction in which the project is to be constructed in accordance <br />with Section R106.1, <br />R802.10.3 Bracing. <br />Trusses shall be braced to revent rotation and provide lateral stability in accordance with the requirements specified <br />in the construction documents for the buildin and on the individual tr 5s design drawings. In the absence of specific <br />bracing requirements, trusses shall be bracedg in accordance with I PI/Hy . <br />R802.10.4 Alterations to trusses. <br />Truss members shall not be cut, notched, drilled spliced or otherwise altered in an way without the approval of a <br />registered design professional. Alterations resul+ing in the addition of load (e. HVAC equipment, water heater) that <br />exceeds the de ' n,load for the truss shalt not be permitted without verification that the truss is capable of supporting <br />such additional o�ding. <br />R802.10.5 Truss to wall connection. <br />Trusses shall be connected to wall fates by the use of approved connector having a resistance to up lift of not less <br />than 175 pounds (79,45 kg.) and shah be installed in accordance with the manusfacturer?s specifications. For roof assemblies <br />subject to wind uplift pressures of 20 pounds pper square foot (0,958 kN/m2) or greater, as established in Table R301,2(2), <br />ad 'usted for height and exposure per Table R301.2(3), see section R802.11. <br />RU2.11 Roof tie -down, <br />R802.11,1 Uplift resistance. <br />Roof assemblies which are subject to wind uplift pressures of 20 pounds per square foot (0.958 kN/m2) or greater shall <br />have roof rafters or trusses attached to their supportin wall assemblies by connections capable of providin the <br />resistance required in Table R802.11. Wind uplift pressures shhall be determined using an effective wind area of 1g00 square <br />feet (9.3 m2) and Zone 1 in Table R301.2(2), as adjusted for height and exposure per Table R301.2<3). <br />A continuous load path shall be provided to transmit the uplift forces from the rafter or truss ties to the foundation, <br />SECTION R803 <br />R❑❑F SHEATHING <br />R803,1 Lumber sheathing. <br />Allowable spans for lumber used as roof sheathing shall conform to Table R803,1, Spaced lumber sheathing for wood shingle <br />and shake roofing shall conform to the requirements of Sections R905,7 and R905,8. <br />R803.2 Wood structural panel sheathing. <br />R803.2.1 Identification and grade. <br />Wood structural anels shall conform to DOC PS 1, DOC PS 2 or, when manufactured in Canada, CSA 0437, and shall be <br />identified by rade mark or certifi to of inspection issued by an approved agency. Wood structural panels shall comply <br />with the grads specified in Table R503.2.1.1C1). <br />R803.2.1.1 Exposure durability. <br />All wood structural anels, when designed to be permanently exposed in outdoor applications, shall be of an exterior <br />exposure durability. Blood structural ppanel roof sheathing exposed to the underside may be of interior type bonded with <br />exterior glue, identified as Exposure 1. <br />R803.2.1,2 Fire -retardant -treated plywood. <br />The allowable unit stresses for fire -retardant -treated plywood including fastener values, shall be developed from an <br />4pproved method of invest; ati n th t considers th effects of an ici ated tem rature and hu idity to which the <br />q p t p -r r nt- reated <br />fire -retardant -treated plywood will Vie subjected, t�e type of treatm�nt and re�rying process.he fire eta da t <br />plywood shall be graded by an approved agency. <br />Allowable s ans, <br />R803 2 2 p <br />The maximum allowable spans for wood structural panel roof sheathing shall not exceed the values set forth in <br />Table R503,2.1.1<1), <br />R803.2,3 Installation. <br />Wood sttructural panel used as roof sheathing shall be installed with joints staggered or nonstaggered in accordance with <br />Table R602.3(1), or APA E30 for wood roof framing or with Table R804.3 for steel roof framing. <br />R807,1 Attic access. <br />In buildinggs with combustible ceiling or roof construction, an attic access opening shall be provided to attic areas that <br />exceed 30 square feet C2.8 m2) and have a vertical height of 30 inches (762 mm) or greater. <br />The row h-framed o enin shalt not be less than 22 inches by 30 inches (559 mm by 762 mm) and shall be located in a hallway <br />or otherr readily accpessibte location. A 30-inch (762 mm) minimum unobstructed headroom in the attic space shall be provided <br />at some point above the access opening. See Section M1305.1.3 for access requirements where mechanical equipment is located <br />in attics, <br />13-103.2 Details, plans and specifications. <br />Plans and specifications shall be submitted with each application for a building permit. Energyy code calculations shall be made <br />a part of the plans and specifications of the building. The building official shall require, sub ect, to the exceptions in <br />Section 481,229, Florida Statutes, and Section 471,003, Florida Statut s, that plans and specifications be prepared by an <br />en in e , or arch'te t license to p a tice in the state of Florid . the lans nd s ci, ioations includin the ever c de <br />ff 9 <br />ca ugaons, shahow, m sufi ten �et il, all p rtment data anal featupres thep�uildm and the eq�ipment and s�ems <br />aa Q qq q m ri U-va ues fie <br />m in n limite to: des �n crit na ex nor en elo e om oneR ate, als <br />as rein qq�o erne� chid g u r1 p p m nt e ui me�ht ant} s stems controls <br />and o%er yse��retrinent-vdaaa stoIn�dlcaet nC�n o Ma�ncs� wit�i�e ruir ar>Ptps oafe Coc�eQu P e q P Y <br />P <br />NFIP 44 CFR 60.3.c.5 <br />All foundation walls and other exterior walls below the base flood elevation (BFE) shall be designed to preclude finished <br />living space and designed to have openings to allow unimpeded movement of flood water. <br />Hydro -Static openings and construction must comply with NFIP 44 CFR 60.3.c.5. Note: There should be a minimum of two <br />openings each, on two seperate walls. (1 square inch for every square foot, please provide calculations on plans for the <br />required area,) Any additional questions, please consult the Local ❑fficials Guide to Implementing the National Flood <br />Insurance Program in Florida pages 5-16. <br />Brick veneer must be installed in compliance with the requirements of FBC Residential section R703.7,2.1 <br />New to existing connection detail is required and must comply with the requirements of FBC Residential 2004 Section <br />R602 or R606, <br />13-610,1,ABC.3,5.2 Air -handling units. <br />306.3.2 Air -handling units. <br />Air -handling units shall be allowed in residential attics if the following conditions are met: <br />L The service panel of the equipment is located within 6 feet (1829 mm) feet of an attic access. <br />2. A device is installed to alert the owner or shut the unit down when the condensation drain is not working properly. <br />3. The attic access opening is of sufficient size to replace the air handler. <br />4. A notice is posted on the electric service panel indicating to the homeowner that the air handler is located in the attic. <br />Said notice shall be in all capitals, in 16-point type, with the title and first paragraph in bold: <br />NOTICE T❑ HOMEOWNER <br />OPERATION p OUR E IAIR � ONDI� ONING SYSTEM, YOU IMUSTTNENSUkE STHAT AREGULARTMAINTENANCE RIS P❑ERFRdRMEDICIENT, AND EC❑N❑MIC <br />YOUR AIR-CONDITIONING SYSTEM IS EQUIPPED WITH ❑NE ❑R BOTH ❑F THE FOLL❑WING: 1) A DEVICE THAT WILL ALERT YOU WHEN THE <br />CONDENSATION DRAIN IS N❑T W❑RKING PROPERLY, ❑R 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE CONDENSATION DRAIN <br />ENSURE PROPER WORKING ORDER NOFATHESEADEVI�ESOBEFOREE�ACH SEASONO�F PIEAKPOP�RA�IONERVICE, IT IS RECOMMENDED THAT Y❑U <br />MINIMUM CATEG❑RY CLASSIFICATI❑N ❑F GLAZING <br />HEADER SCHEDULE F❑R FBC TABLE 2308,9.5 <br />HEADER AND GIRDER SPANSa F❑R EXTERI❑R BEARING WALLS <br />(Maximum Spans for Douglas Fir -Larch, Hem -Fir, Southern Pine and <br />Spruce-Pine-Firb and Required Number of Jack Studs) <br />HEADERS <br />SUPPORTING <br />Roof & Ceilin g <br />20 <br />Building <br />widths <br />28 <br />(feet) <br />36 <br />SIZE <br />Span NJd <br />Span NJd <br />Span <br />NJd <br />2-2 X 4 <br />3-6 1 <br />3-2 1 <br />2-10 <br />1 <br />2-2 X 6 <br />5-5 1 <br />4-8 1 <br />4-2 <br />1 <br />2-2 X 8 <br />6-10 1 <br />5-11 2 <br />5-4 <br />2 <br />2-2 X 10 <br />8-5 2 <br />7-3 2 <br />6-6 <br />2 <br />2-2 X 12 <br />9-9 2 <br />8-5 2 <br />7-6 <br />2 <br />3-2 X 8 <br />e-4 1 <br />7-5 1 <br />6-8 <br />1 <br />3-2 X 10 <br />10-6 1 <br />9-1 2 <br />6-6 <br />2 <br />3-2 X 12 <br />12-2 2 <br />10-7 2 <br />9-5 <br />2 <br />4-2 X 10 <br />11-8 1 <br />10-6 1 <br />9-5 <br />2 <br />4-2 X 12 <br />14-1 1 <br />12-2 2 <br />10-11 <br />2 <br />For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.8 N/m2. <br />a, Spans are given in feet and inches (ft-in). <br />b, Tabulated values are for No. 2 grade lumber, <br />c. Building width is measured perpendicular to the ridge. For widths between those shown, <br />spans are permitted to be interpolated. <br />d. NJ - Number of jack studs required to support each end, Where the number of <br />required jack studs equals one, the header is <br />permitted to be supported by an approved framing anchor attached to the full -height <br />wall stud and to the header, <br />rn .1.11 T Tani <br />�OCTFNFR <br />NUMRFR ❑F SPACING <br />BAND JOIST T❑ SILL ❑R T❑P PLATE, T❑E NAIL <br />8d <br />6' O.C. <br />JOIST TO BAND JOIST, FACE NAIL <br />16d COMM❑N <br />3 <br />J❑IST T❑ SILL ❑R GIRDER, TOE NAIL <br />8d COMM❑N <br />3 <br />BRIDGING TO J❑IST, T❑E NAIL EACH END <br />8d C❑MMON <br />2 <br />LEDGER STRIP <br />16d COMMON <br />3 AT EACH JOIST <br />1X6 ❑R LESS SUBFLO❑R TO EACH JOIST, FACE NAIL <br />8d COMMON <br />2 <br />OVER 1X6 SUBFL❑❑R T❑ EACH JOIST, FACE NAIL <br />8d CDMM❑N <br />3 <br />2-INCH SUBFLO❑R TO JOIST OR GIRDER, BLIND AND FACE NAIL <br />16d C❑MM❑N <br />2 <br />SOLE PLATE T❑ J❑IST OR BLOCKING, FACE NAIL <br />16d COMMON <br />16' D.C. <br />TOP ❑R SOLE PLATE T❑ STUD, END NAIL <br />16d COMMON <br />2 <br />STUD TO S❑LE PLATE, TOE NAIL <br />8d COMM❑N <br />4 <br />DOUBLED STUDS, FACE NAIL <br />10d COMMON <br />24' D.C. <br />D❑UBLE TOP PLATES, FACE NAIL <br />10d COMMON <br />16' O.C. <br />TOP PLATES, LAP AND INTERSECTIONS, FACE NAIL <br />- <br />2-16d OR 3-10d COMMON <br />CONTINUOUS HEADER, TW❑ PIECES <br />16d COMMON <br />16' ❑.C. ALONG EACH EDGE <br />CEILING J❑ITS T❑ PLATE, T❑E NAIL <br />8d COMMON <br />3 <br />CONTINUOUS HEADER TO STUD, TDE NAIL <br />8d C❑MMON <br />3 <br />CEILING JOISTS, LAPS OVER PARTITIONS, FACE NAIL <br />- <br />3-16cl OR 4-10d C❑MM❑N <br />CEILING JOISTS TO PARALLEL RAFTERS, FACE NAIL <br />- <br />3-16d OR 4-10d COMMON <br />RAFTER TO PLATE, TOE NAIL <br />8d COMMON <br />3 <br />1-INCH BRACE TO EACH STUD AND PLATE, FACE NAIL <br />8d C❑MM❑N <br />2 <br />IX8 ❑R LESS SHEATHING TO EACH BEARING, FACE NAIL <br />8d COMMON <br />2 <br />OVER IX8 SHEATHING TO EACH BEARING, FACE NAIL <br />Sd COMMON <br />3 <br />BUILT-UP CORNER STUDS <br />16d COMMON <br />24' O.C. <br />BUILT-UP GIRDERS AND BEAMS, ❑F THREE MEMBERS <br />20d C❑MMDN <br />32' O.C. AT TOP AND BOTTOM <br />AND STAGGERED 2 ENDS AND <br />AT EACH SPLICE <br />2-INCH PLANKS <br />16d COMMON <br />2 EACH BEARING <br />STUDS T❑ SOLE PLATE, END NAIL <br />16d C❑MMDN <br />2 EACH END <br />W❑❑D STRUCTUAL PANEL SUBFLO❑RING7 <br />15/32', 1/2', 7/16' <br />6d COMMON, ANNULAR <br />6' ❑.C, EDGES AND <br />❑R SPIRAL THREAD <br />12' ❑.C. INTERMEDIATE <br />19/32', 3/4' <br />8d COMMON ❑R 6d ANNULAR <br />6' D.0 EDGES AND <br />❑R SPIRAL THREAD <br />12' INTERMEDIATE <br />1', 1-1/8' <br />lOd COMMON OR 8d ANNULAR <br />6' ❑.C. EDGES AND <br />OR SPIRAL THREAD <br />6' D.C. INTERMEDIATE <br />15/32', 1/2', 7/16' <br />16ga GALVANIZED WIRE STAPLES, 3/8' <br />4' O.C. EDGES AND <br />MINIMUM CROWN 1-5/e' LENGTH <br />7' O.C. INTERMEDIATE <br />19/32', 5/8' <br />16ga GALVANIZED WIRE STAPLES, 3/8' <br />2-1/2' ❑.C. EDGES AND <br />MINIMUM CROWN 1-5/8' LENGTH <br />4' D.C. INTERMEDIATE <br />W0❑D STRUCTURAL PANEL R0❑F & WALL SHEATHING <br />6d COMMON (WALL) <br />8' O.0 EGDES AND <br />AND PARTICLEBOARD WALL SHEATHING 1/2' ❑R LESS <br />6d COMMON (ROOF) <br />12' O.C. INTERMEDIATE <br />15/32' - 19/32' <br />8d COMM❑N <br />6' ❑.C. EDGES AND <br />16ga GALVANIZED WIRE STAPLES, 3/8' <br />12' O.C. INTERMEDIATE <br />MIN. CROWN LENGTH ❑F 1' PLUS <br />19/32' - 3/4' <br />8d COMMON <br />4' D.C, EDGES AND <br />16ga GALVANIZED WIRE STAPLES, 3/8' <br />8' O.C. INTERMEDIATE <br />MIN. CR❑WN LENGTH ❑F V PLUS <br />7/8' - I' <br />8d COMM❑N <br />2' D.C. EDGES AND <br />16ga GALVANIZED WIRE STAPLES, 3/8' <br />5' ❑.C. INTERMEDIATE <br />MIN, CROWN LENGTH OF 1' PLUS <br />FIBERB❑ARD SHEATHING1 <br />6d COMMON NAIL ❑R 11 ga <br />6' O.C. AT EDGES, 12' ❑.C. <br />1/2' REGULAR <br />GALV. R❑❑FING NAIL 1-1/2' LONG <br />AT OTHER BEARING AREAS <br />WITH 7/16' HEAD <br />FIBERBOARD SHEATHING1 <br />8d C❑MM❑N NAIL ❑R 11 ga <br />3' ❑.C. AT EDGES, 6' ❑.C. <br />L/2' STRUCTURAL <br />GALV. ROOFING NAIL 1-1/2' LONG <br />AT ❑THER BEARING AREAS <br />WITH 7/16' HEAD <br />FIBERB❑ARD SHEATHING1 <br />8d C❑MMON NAIL ❑R 11 ga <br />3' D.C. AT EDGES, 6' D.C. <br />25/32' STRUCTURAL <br />GALV, ROOFING NAIL 1-3/4' L❑NG <br />AT ❑THER BEARING AREAS <br />WITH 7/16' HEAD <br />GYPSUM SHEATHING <br />1/2' <br />11 ga. 1-1/2' GALVANIZED <br />4' D.C. AT EDGES <br />7/16' HEAD <br />8' ❑.C. AT ❑THER BEARINGS <br />5/8' <br />11 ga. 1-3/4' GALVANIZED <br />4' ❑.C. AT EDGES <br />7/16' HEAD <br />8' ❑.C. AT ❑THER BEARINGS <br />GYPSUM WALLBOARD <br />i/2' <br />1-3/8"2 DRYWALL NAIL <br />7' ❑.C. ❑N CEILINGS <br />8' O.C. ❑N WALLS <br />5/8" <br />1-1/2'2DRYWALL NAIL <br />7' ❑.C. ❑N CEILINGS <br />8' ❑.C, ON WALLS <br />PARTICLEBOARD SIDINGS <br />5/16' - 1/2' <br />6d4 <br />5/8' <br />8dq <br />3/4' <br />8d4 <br />HARDBOARD LAP SIDINGS <br />8d8CORROSI❑N-RESISTANT <br />16' O.C. AT T❑P <br />DIRECT TO STUDS <br />WITH MINIMUM SHANK <br />AND BOTTOM EDGES <br />DIAMETER OF 0.099 INCH <br />AND MINIMUM HEAD <br />DIAMETER ❑F 0.024 INCH. <br />HARDBOARD LAP SIDING <br />1Od6CDRROSION-RESISTANT <br />16' ❑.C, AT T❑P <br />OVER SHEATHING <br />WITH MINIMUM SHANK <br />AND B❑TTOM EDGES <br />DIAMETER ❑F 0.099 INCH <br />AND MINIMUM HEAD <br />DIAMETER OF 0.024 INCH. <br />HARDBOARD LAP SIDING <br />6d6CORR❑SI❑N-RESISTANT <br />6' O.C. AT EDGES <br />OVER SHEATHING <br />WITH MINIMUM SHANK <br />AND 12' ❑.C. AT <br />DIAMETER OF 0,099 INCH <br />INTERMEDIATE SUPP❑RTS <br />AND MINIMUM HEAD <br />DIAMETER ❑F 0.024 INCH. <br />HARDBOARD LAP SIDING <br />8d6C❑RR❑SI❑N-RESISTANT <br />6' O.C. AT EDGES <br />❑VER SHEATHING <br />WITH MINIMUM SHANK <br />AND 12' ❑.C. AT <br />DIAMETER ❑F 0.099 INCH <br />INTERMEDIATE SUPPORTS <br />AND MINIMUM HEAD <br />DIAMETER ❑F 0.024 INCH. <br />NOTES: <br />1. FIBERB❑ARD SHEATHING MAY BE STAPLED USING 16 a GALVANIZED STAPLES 1-1/8' LONG FOR 1/2' SHEATHING AND <br />1-1/2' L❑NG F❑R 25'/32' SHEATHING. STAPLES M HAVE MINIMUM CROWN ❑F 7/16' AND SPACED 3' ❑.C. AT EDGES <br />AND 6' ❑.C. AT ❑THER BEARINGS. <br />2. DRYWALL NAILS SHALL CONFORM TO ASTM C514. <br />3. SIDING APPLIED T❑ 5/8' NET WOOD SHEATHING. 15/32' STRUCTUAL PANEL ❑R 1/2' PARTICLEBOARD SHEATHING. <br />4. C❑RR❑SI❑N-RESISTANT NAILS SPACED 6' O.C. AT EDGE AND 8' ❑.C. AT INTERMEDIATE SUPPORTS. NAILS <br />SHALL HAVE A MINIMUM EDGE DISTANCE OF 3/8'. <br />5. SIDING APPLIED T❑ STUDS SPACED 16' O.C. MAXIMUM <br />6, SIDING APPLIED DIRECTLY T❑ STUDS SPACED 24' O.C. MAXIMUM. <br />7. USE ANNULAR ❑R SPIRAL THREAD NAILS FOR C❑MBINATI❑N SUBFLODR/UNDERLAYMENT (SINGLE FLOOR). <br />8. NAIL MUST BE OF SUFFICIENT LENGTH T❑ ACCOMMODATE THICKNESS ❑F SIDING AND SHEATHING, IF USED, AND ALLOW <br />MINIMUM STD PENETRATION ❑F 1-1/2'. <br />9. FOR 1-INCH WOOD STRUCTURAL PANELED, 12' ❑.C. INTERMEDIATE NAILING SHALL BE PERMITTED. <br />TABLE R301.2.1.2 <br />WIND-B❑RNE DEBRIS PR❑TECTI❑N FASTENING SCHEDULE F❑R W❑❑D STRUCTURAL PANELS <br />FASTENER TYPE FASTENER SPACING (in.) 1,2 <br />Panel span <br />2 foot panel span <br />< 4 foot <br />panel span <br />< 6 foot <br />panel span <br /><- 2 ft <br />< 4 foot <br />< 6 foot <br />< 8 foot <br />2 #6 Wood Screw 3 <br />16 <br />16 <br />12 <br />9 <br />2 #8 Wood Screws 3 <br />16 <br />16 <br />12 <br />12 <br />Double -Headed Nails 4 <br />12 <br />6 <br />4 <br />3 <br />SI: 1 inch = 25.4 mm, 1 foot = 305 mm. <br />1. This table is based on a maximum wind speed of 130 mph (58 m/s) and mean roof height of 33 feet (10 m) or less. <br />2. Fasteners shall be installed at opposing ends of the wood structural panel. <br />3, Where screws are attached to masonry or masonry/stucco, they shall be attached using vibration -resistant <br />anchors havin a minimum withdrawal capacity of 490 lb (2180 kN). <br />4, Nails shall be �Od common or 12d box double -headed nails, <br />