v
<br />0
<br />z
<br />C
<br />C
<br />C
<br />J
<br />c
<br />k
<br />GENERAL NOTES
<br />GENERAL NOTES
<br />COMBINATION OF ROOF AND SOFFIT VENTS PER R806.2
<br />DRYWALL
<br />— DO NOT SCALE DRAWINGS
<br />o 40%-50% OF REQUIRED VENTILATION SHALL BE PROVIDED IN THE UPPER PORTION OF THE ATTIC
<br />- %" SAG —RESISTANT GYPSUM CEILING BOARD SHALL BE USED ON CEILINGS WITH 24" O.C. SPANS
<br />— ALL WORK MUST BE COMPLETED TO THE APPLICABLE FLORIDA BUILDING CODES
<br />LOCATED NO MORE THAN 3' BELOW THE RIDGE OR HIGHEST POINT OF THE SPACE. THE REMAINING
<br />ACCESSIBILITY
<br />— ANY ERRORS OR OMISSIONS SHALL BE REPORTED TO A PULTE REPRESENTATIVE
<br />VENTILATION SHALL BE OBTAINED THROUGH SOFFIT VENTS
<br />— ONE BATHROOM LOCATED ON HABITABLE GRADE LEVELS SHALL PROVIDE A DOOR THAT HAS A 29" CLEAR
<br />— CONTRACTORS SHALL MAINTAIN A CLEAN JOB SITE
<br />— PROVIDE MIN. 1" FREE SPACE BETWEEN INSULATION AND ROOF SHEATHING
<br />OPENING PER R320.1.1. A POWDER BATH CAN BE USED IF THERE ARE NO BATHS ON THE GROUND FLOOR
<br />— CONTRACTORS ARE RESPONSIBLE TO FOLLOW ALL APPLICABLE OSHA REGULATIONS
<br />— ATTIC ACCESS IS REQUIRED WHEN THE HEIGHT IS GREATER THAN 30" AND THE AREA IS GREATER
<br />WITH A TUB OR SHOWER
<br />TERMITE PROTECTION
<br />THAN 30 SF
<br />o ALL DOORS LEADING TO THE BATHROOM INCLUDING PRIVATE WATER CLOSET DOORS SHALL MEET THIS
<br />o THE HEIGHT IS MEASURED FROM THE TOP OF THE CEILING FRAMING MEMBERS TO THE BOTTOM OF
<br />REQUIREMENT.
<br />— TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMICIDES AND A CERTIFICATE OF COMPLIANCE
<br />THE ROOF FRAMING MEMBERS
<br />CLEAR OPENING CAN BE ACHIEVED WITH A 2/8 SWING DOOR OPENED AT 90 DEGREES OR A 2/6
<br />anfyr9
<br />SHALL BE ISSUED TO THE BUILDING DEPARTMENT
<br />a
<br />v
<br />Pu
<br />SOIL TREATMENT, BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD ARE ACCEPTABLE FORMS OF
<br />o MIN. ATTIC ACCESS SIZE IS TO BE 22" x30" WITH 30 OF UNOBSTRUCTED HEADROOM IN THE ATTIC
<br />POCKET DOOR
<br />d
<br />3 � ��' ��
<br />TREATMENT
<br />SPACE
<br />FIRE—RESISTANT CONSTRUCTION
<br />SITE ADDRESS
<br />IDENTIFICATION. THE ADDRESS SHALL BE NO
<br />— INSPECTION FOR TERMITES
<br />— BUILDINGS SHALL BE PROVIDED WITH APPROVED ADDRESS
<br />— DOORS FROM GARAGE TO THE RESIDENCE SHALL BE SOLID WOOD OF NOT LESS THAN 1 3/8" IN
<br />LESS THAN 4" IN HEIGHT AND VISIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY
<br />o PROVIDE 6" CLEARANCE FROM GRADE WITH EXTERIOR WOOD FRAMED WALLS
<br />THICKNESS, SOLID OR HONEYCOMB —CORE STEEL DOOR NOT LESS THAN 1 3/8" IN THICKNESS OR
<br />■ 4" CLEARANCE REQUIRED AT GARAGES AND PORCHES
<br />A 20—MIN. FIRE —RATED DOOR
<br />GUARDS AND WINDOW FALL PROTECTION
<br />— DUCTS IN THE GARAGE AND DUCTS PENETRATING WALLS OR CEILINGS SEPARATING THE DWELLING FROM
<br />— GUARDS SHALL BE PROVIDED WHEN WALKING SURFACES ARE LOCATED MORE THAN 30" ABOVE
<br />THE GARAGE SHALL BE CONSTRUCTED IN ACCORDANCE WITH R302.5.3
<br />GRADE (WITHIN 24" HORIZONTALLY) OR A.F.F.
<br />EXTERIOR
<br />— 1h" GYP. BOARD SHALL BE INSTALLED ON GARAGE SIDE OF WALLS ABUTTING THE RESIDENCE AND GARAGE
<br />—GUARDS SHALL BE MIN. 36"
<br />— WATER RESISTANCE
<br />CEILING WITHOUT HABITABLE ROOMS ABOVE
<br />o EXCEPTION: 34" IS ALLOWED IF THE TOP OF THE GUARD SERVES AS A HANDRAIL ON THE OPEN SIDE
<br />o THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND CONSTRUCTED IN A MANNER THAT
<br />— 5/8" GYP. BOARD SHALL BE INSTALLED ON GARAGE CEILING W/ HABITABLE ROOMS ABOVE
<br />OF THE STAIRS
<br />PREVENTS THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A
<br />— ; " GYP. BOARD SHALL BE INSTALLED UNDER STAIRS FOR ENCLOSED ACCESSIBLE SPACES
<br />—GUARDRAILS SHALL NOT INCLUDE OPENINGS THAT WILL ALLOW THE PASSAGE OF A 4" SPHERE
<br />WATER—RESISTANT BARRIER BEHIND THE EXTERIOR VENEER AS REQUIRED BY R703.2 AND A MEANS
<br />OF DRAINING TO THE EXTERIOR WATER THAT ENTERS THE ASSEMBLY.
<br />— FIREBLOCKING SHALL BE INSTALLED PER R302.11
<br />— WINDOWS WHERE THE TOP OF THE SILL IS LESS THAN 24" A.F.F. AND GREATER THAN 72" ABOVE FINISHED
<br />■ THIS IS NOT REQUIRED OVER CMU
<br />— DRAFTSTOPPING SHALL BE INSTALLED PER R302.12 AND SHALL NOT EXCEED 1,000 SF. DRAFTSTOPPING
<br />GRADE OF OTHER SURFACE SHALL HAVE A WINDOW OPENING CONTROL DEVICE INSTALLED
<br />SHALL DIVIDE THE SPACE IN APPROXIMATELY EQUAL AREAS
<br />STAIRS
<br />— FLASHING
<br />o APPROVED CORROSION RESISTANT FLASHING SHALL BE INSTALLED IN A SHINGLE FASHION PER
<br />— MIN. CLEAR WIDTH 36"
<br />R703.4
<br />WINDOWS/DOORS
<br />o HANDRAILS SHALL NOT PROJECT MORE THAN 4 �" ON EITHER SIDE OF THE STAIRWAY
<br />— EXTERIOR PLASTER
<br />— FIELD SHALL VERIFY ALL WINDOW/DOOR ROUGH OPENINGS
<br />— MIN. HEADROOM 6'-8"
<br />o EXTERIOR PLASTER SHALL BE INSTALLED IN COMPLIANCE WITH ASTM C926, ASTM C1063 AND R703.7
<br />— PROVIDE EMERGENCY ESCAPE AND RESCUE WINDOW OR DOOR IN ALL BEDROOMS PER R310
<br />— MAX. RISE 7-3/4"
<br />— LATH
<br />o (*) DENOTES WINDOW SHALL COMPLY WITH EMERGENCY ESCAPE AND RESCUE (EERO) REQUIREMENTS
<br />— MIN. TREAD DEPTH 10"
<br />o LATH AND LATH ATTACHMENTS SHALL BE OF CORROSION RESISTANT MATERIALS. EXPANDED METAL
<br />o OPENINGS SHALL NOT BE LESS THAN 5.7 SF WITH A NET CLEAR OPENING OF MIN. 24" H AND
<br />—HANDRAILS
<br />OR WOVEN WIRE LATH SHALL BE ATTACHED WITH 1 1h" LONG, 11 GAGE NAILS HAVING
<br />MIN, 20" D
<br />A 7/16" HEAD, OR 7/8" LONG, 16 GAGE STAPLES, SPACE NOT MORE THAN 6" INTO FRAMING
<br />A.F.F.
<br />o EERO WINDOW SILLS SHALL BE INSTALLED NO MORE THAN 44" A.F.F
<br />o 34"-38" ABOVE SLOPE PLANE
<br />MEMBERS
<br />o HANDRAILS SHALL BE CONTINUOUS FOR THE FULL LENGTH OF THE FLIGHT ON STAIRWAYS OF MORE
<br />— ONE EGRESS DOOR SHALL BE PROVIDED PER DWELLING UNIT WITH A CONTINUOUS AND UNOBSTRUCTED
<br />THAN FOUR RISERS
<br />o WEEP SCREEDS, A minimum 0.019—inch (0.5 mm) (No. 26 galvanized sheet gage),
<br />PATH WITHOUT GOING THROUGH A GARAGE
<br />0 1 i/ "-2 " GRIP SIZE OR GRASPABLE FINGER RECESS
<br />corrosion —resistant weep screed or plastic weep screed, with a minimum vertical attachment flange of 3 i�
<br />o MIN. CLEAR WIDTH 32" WHEN OPEN AT 90 DEGREES
<br />inches (89 mm) shall be provided at or below the foundation plate line on exterior stud walls in accordance
<br />with ASTM C926. The weep screed shall be placed not less than 4 inches (102 mm) above the earth or 2
<br />o MIN. HEIGHT 78"
<br />ELECTRICAL
<br />inches (51 mm) above paved areas and shall be of a type that will allow trapped water to drain to the
<br />o FINISHED FLOOR SHALL BE MAX. 1 1/2" BELOW TOP OF THRESHOLD
<br />— SMOKE ALARMS COMPLYING WITH NFPA 72 SHALL BE INSTALLED:
<br />exterior of the building. The weather —resistant barrier shall lop the attachment flange. The exterior lath
<br />shall cover and terminate on the attachment flange of the weep screed.
<br />o PORCH SHALL BE MAX. 7-3/4" BELOW TOP OF THRESHOLD FOR IN —SWING DOORS
<br />o IN EACH SLEEPING ROOM
<br />— SIDING
<br />— OPENINGS SHALL BE PROTECTED IN WIND —BORN DEBRIS AREAS IN ACCORDANCE WITH R301.2.1.2
<br />o OUTSIDE EACH SLEEPING ROOM
<br />o FIBER —CEMENT SIDING IS TO BE INSTALLED IN ACCORDANCE WITH ASTM C1186 AND R703.10
<br />— TEMPERED GLASS SHALL BE INSTALLED WITH THE FOLLOWING
<br />o ON EACH ADDITIONAL STORY
<br />— MASONRY
<br />o FIXED AND OPERABLE PANELS IN DOORS
<br />o CANNOT BE INSTALLED WITHIN 3' HORIZONTALLY OF A BATHROOM THAT CONTAINS A BATHTUB OR
<br />o BRICK IS TO BE INSTALLED PER R703.8
<br />GLAZING WITHIN 24" OF EITHER SIDE OF DOOR IN THE PLANE OF THE DOOR IN A CLOSED
<br />SHOWER
<br />o ADHERED MASONRY IS TO BE INSTALLED PER R703.12
<br />POSITION
<br />— SMOKE ALARMS SHALL BE HARD —WIRED W/ BATTERY BACKUP AND INTERCONNECTED IN SUCH A MANNER
<br />■ GLAZING IS ON A WALL PERPENDICULAR TO THE PLANE OF THE DOOR IN A CLOSED POSITION
<br />THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL ALARMS
<br />ROOFING
<br />AND WITHIN 24" OF THE HINGE SIDE OF AN IN —SWING DOOR.
<br />— CARBON MONOXIDE ALARMS ARE REQUIRED TO BE INSTALLED WITHIN 10' OF ALL BEDROOMS
<br />— UNDERLAYMENT R905.1.1
<br />o WINDOWS
<br />o COMBINATION SMOKE/CARBON MONOXIDE ALARMS ARE PERMITTED
<br />o Unless otherwise noted underlayment for asphalt shingles, metal roof shingles, mineral —surfaced roll
<br />GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL THAT MEETS ALL OF THE FOLLOWING
<br />— THE BRANCH CIRCUIT SUPPLYING THE RECEPTACLE(S) IN A GARAGE SHALL NOT SUPPLY OUTLETS OUTSIDE
<br />roofing, slate and slate —type shingles, wood shingles, wood shakes and metal roof panels shall
<br />CONDITIONS SHALL BE CONSIDERED TO BE A HAZARDOUS LOCATION:
<br />OF THE GARAGE AND NOT LESS THAN ONE RECEPTACLE OUTLET SHALL BE INSTALLED FOR EACH MOTOR
<br />conform to the applicable standards listed in this chapter. Underlayment materials required to
<br />• WHEN EXPOSED AREA IS OVER 9 SF
<br />VEHICLE SPACE
<br />comply with ASTM D226, D1970, D4869 and D6757 shall bear a label indicating compliance to the
<br />. BOTTOM EDGE OF GLAZING IS LESS THAN 18" A.F.F.
<br />—GROUND—FAULT CIRCUIT PROTECTION; ALL 120V SINGLE PHASE, 15 & 20 AMP OUTLETS INSTALLED
<br />indicated
<br />standard designation and, if applicable, type classification indicated in Table R905.1.1. Underlayment
<br />THE TOP EDGE OF THE GLAZING IS MORE THAN 36 INCHES (914 MM) ABOVE THE FLOOR;
<br />OUTDOORS, IN BATHROOMS, IN KITCHENS, GARAGES, LAUNDRY AND AT DISHWASHER SHALL HAVE GFCI
<br />shall be applied and attached in accordance with Table .1,
<br />•
<br />CIRCUIT BREAKERS OR RECEPTACLES
<br />AND
<br />ONE OR MORE WALKING SURFACES ARE WITHIN 36 INCHES (914 MM), MEASURED
<br />— BRANCH CIRCUITS THAT SUPPLY 120—VOLT, SINGLE PHASE, 15 & 20 AMP OUTLETS INSTALLED IN
<br />■ Exception: A reinforced synthetic underlayment that is approved as an alternate to
<br />•
<br />KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
<br />underlayment complying with ASTM D226 Type II and having a minimum tear strength in
<br />HORIZONTALLY AND IN A STRAIGHT LINE, OF THE GLAZING
<br />SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
<br />accordance with ASTM D1970 or ASTM D4533 of 20 pounds shall be permitted. This
<br />o WINDOWS ADJACENT TO THE BOTTOM STAIR LANDING
<br />SHALL BE PROTECTED WITH ARC —FAULT CIRCUIT —INTERRUPTER PROTECTION PER FBCR E3902.16 AND
<br />underlayment shall be installed and attached in accordance with the underlayment attachment
<br />WHEN BOTTOM EDGE OF GLAZING IS LESS THAN 36" ABOVE THE PLANE OF THE WALKING
<br />SHALL BE LISTED AS TAMPER —RESISTANT
<br />methods of Table R905.1.1 for the applicable roof covering and slope, except metal cap nails
<br />SURFACE
<br />— NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
<br />shall be required where the ultimate design wind speed, equals or exceeds 150 mph.
<br />■ WHEN GLAZING IS WITHIN 60" OF BOTTOM STAIR LANDING
<br />HIGH —EFFICACY LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY INSTALLED LIGHTING
<br />— FLASHING R903.2
<br />FIXTURES SHALL CONTAIN ONLY HIGH —EFFICACY LAMPS
<br />o WET AREAS
<br />o Flashings shall be used to seal roofing systems, where the system is interrupted or terminated and
<br />shall be installed in a manner that prevents moisture from entering the wall and roof through
<br />GLAZING IN WALLS OR ENCLOSURES CONTAINING OR FACING HOT
<br />joints in copings, through moisture permeable materials and at intersections with parapet walls and
<br />TUBS, SPAS, BATHTUBS, SHOWERS OR SWIMMING POOLS SHALL BE TEMPERED IF SILL HEIGHT IS
<br />other penetrations through the roof plane.
<br />LESS THAN 60" A.F.F., MEASURED VERTICALLY ABOVE ANY STANDING OR WALKING SURFACE.
<br />— ASPHALT SHINGLES SHALL BE INSTALLED PER R905.2
<br />SHOWER AND/OR TUB ENCLOSURES SHALL BE TEMPERED
<br />— CLAY AND CONCRETE TILE SHALL BE INSTALLED PER R905.3
<br />WOOD
<br />— METAL ROOF SHINGLES SHALL BE INSTALLED PER R905.3.8
<br />— ALL WOOD IN CONTACT WITH CONCRETE SHALL BE PRESSURE —PRESERVATIVE —TREATED WOOD
<br />INSULATION
<br />'
<br />VENTILATION Z ATTIC ACCESS
<br />— INSULATION SHALL BE INSTALLED PER APPROVED LOT SPECIFIC ENERGY CALCULATIONS
<br />— MIN. NET FREE VENTILATION SHALL BE 1 /150 OF THE AREA OF VENTED SPACE WHEN USING SOFFIT
<br />—INSULATE, THERMO—PLY AND SEAL AREAS BEHIND TUBS OR SHOWERS ON EXTERIOR WALLS
<br />VENTS ONLY PER R806.2
<br />— INSTALL WOOD SHEATHING OR THERMO—PLY ON ATTIC SIDE WHEN CONDITIONED SPACE ABUTS
<br />— MIN. NET FREE VENTILATION SHALL BE 1/300 OF THE AREA OF VENTED SPACE WHEN USING A
<br />UNCONDITIONED ATTIC SPACE TO CREATE A 6—SIDED INSULATION ASSEMBLY
<br />a
<br />CD
<br />N
<br />O
<br />N
<br />S
<br />af
<br />0
<br />U
<br />O
<br />w `
<br />O
<br />[IwJ
<br />14
<br />M0
<br />\'J
<br />?
<br />r�
<br />v
<br />VJ
<br />�
<br />�i
<br />0r
<br />Q`n
<br />�+
<br />o
<br />v
<br />�
<br />�
<br />N
<br />`Y'
<br />U
<br />72
<br />o
<br />N
<br />*PU Ite
<br />PRODUCT MANAGER
<br />RELEASE
<br />DATE: XX XX XXXX
<br />REV DAIS/DESMPTO
<br />PROJECT TYPE
<br />Single Family
<br />SPECIFICATION LEVEL
<br />Pulte
<br />PLAN NAME
<br />Cedar
<br />NPC CHILD NUMBER
<br />2810.500
<br />SHEET
<br />GO.02
<br />
|