<br />THROUGH -PENETRATION DETAIL
<br />SYSTEM No. F-A-IG 5
<br />F RATIN05 - 2 HR
<br />1. FLOOR ASSEMBLY - THE FIRE -RATED UNPROTECTED CONCRETE AND STEEL FLOOR
<br />ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER
<br />SPECIFIED THE INDIVIDUAL D900 SERIES DESIGNS IN THE U.L. FIRE RESISTANCE
<br />DIRECTORY AND AS SUMMARIZED BELOW:
<br />A. CONCRETE - MIN 2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT
<br />(100-150 PCF) CONCRETE.
<br />B. STEEL FLOOR AND FORM UNITS* - COMPOSITE OR NON -COMPOSITE MAX
<br />3 IN. DEEP GALV FLUTED UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING
<br />DESIGN. MAX DIAM OF OPENING IS 6 IN.
<br />2. THROUGH PENETRATIONS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED
<br />EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM.
<br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH
<br />OPENINGS SHALL B MIN 0 IN. (POINT CONTACTS) TO MAX 1-7/8 IN. PIPE, CONDUIT OR
<br />TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY.
<br />THE FOLLOWING TYPES AND SIZES OF MTALLIC PIPES, CONDUITS OR TUBING MAY
<br />BE USED:
<br />A. STEEL PIPE
<br />B. IRON PIPE
<br />C. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC
<br />TUBING OR STEEL CONDUIT.
<br />D. COPPER TUBING
<br />E. COPPER PIPE
<br />3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
<br />PACKING MATERIAL - MIN 1-1/2 IN. THICKNESS OF MIN 4 PCF DENSITY MINERAL
<br />WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM.
<br />PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR AS
<br />REQUIRED TO ACCOMODATE THE REQUIRED THICKNESS OF FILL MATERIAL (ITEM 3B).
<br />FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 1/2 IN. THICKNESS OF FILL
<br />MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR. AT
<br />POINT CONTACT LOCATION BETWEEN PENETRANT AND CONCRETE, A MIN 1/2 IN.
<br />DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE CONCRETE/PENETRANT
<br />INTERFACE ON TOP SURFACE OF FLOOR.
<br />FIRESTOP SYSTEM INC. - 4800 DW
<br />*BEARING THE UL CLASSIFICATION MARKING
<br />THROUGH -PENETRATION DETAIL
<br />SYSTEM No.
<br />F RATIN65 - 2 HR
<br />SECTION A -A
<br />1. WALL ASSEMBLY - MIN 6-1/8 IN. THICK NORMAL WEIGHT OR LIGHTWEIGT
<br />(100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY U.L.
<br />CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 14-1/8 IN.
<br />SEE CONCRETE BLOCKS (CAZT) CATERGORY IN THE FIRE RESISTANCE DIRECTORY
<br />FOR NAME OF MANUFACTURER.
<br />2. THROUGH PENETRATIONS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED
<br />EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM.
<br />THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF
<br />OPENINGS SHALL BE MIN 3/8 IN. TO MAX 1 IN. PIPE, CONDUIT OR TUBING TO BE
<br />RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING
<br />TYPES AND SIZES OF MTALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
<br />A. STEEL PIPE
<br />B. IRON PIPE
<br />C. CONDUIT - NOMINAL 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC
<br />TUBING OR STEEL CONDUIT.
<br />D. COPPER TUBING
<br />E. COPPER PIPE
<br />3. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 1-1/4 IN. THICKNESS
<br />OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF
<br />OF WALL.
<br />FIRESTOP SYSTEM INC. - 4800 DW
<br />*BEARING THE UL CLASSIFICATION MARKING
<br />FIRE ALARM NOTES:
<br />SEQUENCE OF OPERATION:
<br />1. THE FIRE ALARM SYSTEM SHALL OPERATE AS FOLLOWS:
<br />A. MANUAL PULL STATION:
<br />1) IDENTIFY THE INDIVIDUAL STATION ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE ALARM AT THE FACP.
<br />3) ILLUMINATE THE ALARM RED LED.
<br />4) SOUND AUDIBLE ALARM AND ACTUATE THE VISUAL ALARMS (STROBES)
<br />IN THE BUILDING.
<br />B. AN AREA SMOKE DETECTOR OR HEAT DETECTOR ,OR SPRINKLER WATER -
<br />FLOW SWITCH SHALL CAUSE THE FOLLOWING:
<br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION.
<br />2) A SIGNAL DEDICATED TO THE SPRINKLER SYSTEM WATER -FLOW ALARM
<br />SHALL NO BE ABLE TO BE SILENCED.
<br />C. SMOKE DETECTORS FOR ELEVATOR RECALL:
<br />1) PROVIDE OPERATION AS DESCRIBED FOR MANUAL ALARM PULL STATION.
<br />2) REFER TO ELEVATOR RECALL SEQUENCE OF OPERATION.
<br />D. SMOKE DUCT DETECTORS
<br />1) IDENTIFY THE INDIVIDUAL DETECTOR ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP.
<br />3) ILLUMINATE THE SUPERVISORY LED.
<br />4 SHUT DOWN ITS RESPECTIVE AIR HANDLER UNIT.
<br />E. FLOW BELL :
<br />1) FLOW BELL SHALL SOUND UPON THE ACTIVATION OF FLOW SWITCH ONLY.
<br />2) FLOW BELL SHALL SOUND AS LONG AS THE WATER IS FLOWING.
<br />3) FLOW BELL SHALL NO BE CAPLABLE OF BEING SILENCED FROM THE FACP.
<br />F. ACTIVATION OF ANY SUPERVISORY CIRCUIT OR TAMPER SWITCH SHALL CAUSE THE
<br />FOLLOWING ACTIONS AND INDICATIONS:
<br />1) IDENTIFY THE INDIVIDUAL CIRCUIT OR DEVICE ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE SUPERVISORY ALARM AT THE FACP.
<br />3) ILLUMINATE THE SUPERVISORY LED.
<br />G. RECEIPT OF A TROUBLE SIGNAL AT THE FACP SHALL CAUSE THE
<br />FOLLOWING ACTIONS AND INDICATIONS:
<br />1) IDENTIFY THE ORIGIN OF THE TROUBLE ON THE SYSTEM CONTROL PANEL.
<br />2) SOUND THE LOCAL AUDIBLE TROUBLE SIGNAL AT THE FACP.
<br />3) ILLUMINATE THE TROUBLE LED.
<br />ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE DISPLAYED ON
<br />THE MAIN FIRE ALARM PANEL AS WELL AS ON ALL REMOTE ANNUNCIATOR PANELS.
<br />ALARMS, TROUBLES AND SUPERVISORY SIGNALS SHALL BE TRANSMITTED TO
<br />A LISTED CENTRAL STATION.
<br />CENTRAL STATION / TRANSMISSION OF SIGNALS / MONITORING
<br />- ALL SIGNALS (ALARM/ TROUBLE/SUPERVISORY) WILL BE TRANSMITTED TO THE
<br />CENTRAL STATION.
<br />- THE MEANS OF TRANSMISSION IS WIRELESS DIALER.
<br />- ALL SIGNALS WILL BE TRANSMITTED AS FOLLOWS:
<br />A POINT ADDRESSABLE SIGNAL WILL BE TRANSMITTED TO THE CENTRAL STATION,
<br />SYSTEMS POINTS WILL BE IDENTIFY AT THE CENTRAL STATION AS FOLLOW:
<br />DEVICE TYPE ( PULL STATION, SMOKE, ETC) + DEVICE LOCATION
<br />(FLOOR + GENERAL DESCRIPTION) + INDIVIDUAL BUILDING PHYSICAL ADDRESS
<br />OR BUILDING NUMBER.
<br />- THE FIRE ALARM DIALER IS AN OPTIONAL BOARD THAT MOUNTS INSIDE I
<br />THE FIRE ALARM CABINET ON TOP OF THE FIRE ALARM MAIN BOARD.
<br />CODES & FLAN NOTES
<br />ALL DRAWINGS ARE SCALED TO 1/8 = 1Ft UNLESS OTHERWISE NOTED.
<br />COORDINATE WITH SPRINKLER CONTRACTOR EXACT LOCATION OF ALL
<br />TAMPER AND FLOW SWITCHES.
<br />INSTALL STROBE BOX FOR FUTURE ADA USE IN ALL 1ST FLOOR APARTMENT'S
<br />BATHROOMS.
<br />CONFIRM LOCATION OF POWER SUPPLIES IN BLDGS PRIOR TO ROUGH IN.
<br />REFER TO FLOOR PLANS FOR LOCATION OF DUCT DETECTORS (SUPPLY OR
<br />RETURN SIDE), COORDINATE WITH MECHANICAL CONTRACTOR THE ACTUAL
<br />LOCATIONS OF THE AHUs.
<br />ALL STROBES WILL BE SET @ 75cd UNLESS NOTED.
<br />CEILING HEIGHT IS 10ft UNLESS NOTED.
<br />UNDERGROUND WIRE USED AS SLC FOR COMMUNICATION BETWEEN BUILDINGS
<br />IS SUITABLE FOR WET LOCATIONS / DIRECT BURIAL.
<br />ANY PROPOSED INTERCONNECTION OF PANELS WILL BE A "NON -LATCHING"
<br />CONFIGURATION PANEL RESET FROM 1 LOCATION.
<br />FIRE ALARM SYSTEM PROVIDED IS FULLY ADDRESSABLE.
<br />SMOKE DETECTORS FOR SMOKE COMPARTMENTS WILL BE PROVIDED
<br />AS PER NFPA-72 17.7.5.6.5.1 (A)
<br />COORDINATE WITH MECHANICAL CONTRACTOR LOCATION OF SMOKE DAMPERS
<br />SINGLE STATION 120 AC SMOKE DETECTOR AND C/O DETECTORS PROVIDED BY
<br />ELECTRICAL CONTRACTOR ON SEPARATE PERMIT.
<br />ELECTRICAL LOAD, PANEL, BREAKER LOCKOUT IS ON SEPARATE PERMIT
<br />PERMIT #########. FBC 107.2
<br />INSTALLATION SHALL BE IN ACCORDANCE WITH 2O20 FFPC 7TH ED., NFPA 72 2016 ED
<br />NFPA 1 2018 ED., NFPA 101 2018 ED. AND NFPA 13 2016 ED.
<br />24/5 STANDBY TEST IS REQUIRED BEFORE FINAL FIRE. IF BUILDING IS OCCUPIED
<br />DURING THIS TEST, FIREWATCH WILL BE REQUIRED.
<br />ALL AUDIBLE DEVICES LOCATED INSIDE SLEEPING AREAS MEET NFPA-72 (2016)
<br />18.4.5.3 FOR LOW FREQUENCY REQUIREMENTS
<br />- ALL NEW SYSTEMS SHALL INCLUDE A DOCUMENT CABINET.
<br />** 24/5 STANDBY TEST REQUIRED IF ANY PART OF THE BLDG IS OCCUPIED
<br />BY TENANTS DURING THIS TEST, A FIRE WATCH IS REQUIRED FROM
<br />7AM-7PM.
<br />ELECTRICAL MOUNTING BOX
<br />FOR THE CEILING MOUNTED
<br />NOTIFICATION DEVICES.
<br />"CADDY" T-GRID BOX HANGER ACOUSTICAL TILE CEILING
<br />SUPPORT, OR EQUAL. "CADDY'- GRID SUPPORT FRAMING.
<br />REFERENCE NO. CEC 30-302(3).
<br />CEILING GRID ELECTRICAL BACK -BOX ATTACHMENT
<br />FIRE ALARM DEVICE LEGEND
<br />SYMBOL
<br />DEVICE DESCRIPTION
<br />FACP
<br />0
<br />FIRE ALARM CONTROL PANEL
<br />w
<br />FO
<br />REMOTE ANNUNCIATOR PANEL
<br />z_
<br />m
<br />U
<br />FCPS
<br />0
<br />POWER SUPPLY EXPANDER
<br />wFp
<br />FIRE ALARM TERMINAL CABINET
<br />z
<br />d
<br />Mlc
<br />0
<br />REMOTE MICROPHONE PANEL
<br />AUDIO
<br />AUDIO PANEL
<br />DIALER
<br />0
<br />FIRE ALARM DIALER
<br />SYMBOL
<br />DEVICE DESCRIPTION
<br />Ell
<br />HORN/STROBE WALL MOUNT
<br />FQ< Wp
<br />HORN/STROBE OUTDOOR
<br />CM
<br />HORN/STROBE CEILING MOUNT
<br />Hl< LF
<br />LOW FREQUENCY FREQUENCY
<br />O
<br />SPEAKER/STROBE WALL MOUNT
<br />U
<br />Wp
<br />SPEAKER/STROBE OUTDOOR
<br />LL
<br />CM
<br />SPEAKER/STROBE CEILING MOUNT
<br />O
<br />Z
<br />❑s
<br />SPEAKER
<br />F'
<br />STROBE
<br />F' Wp
<br />STROBE OUTDOOR
<br />CM
<br />STROBE CEILING MOUNT
<br />©4
<br />LOW FREQUENCY HORNS
<br />SMOKE SOUNDER BASE
<br />SPRINKLER BELL
<br />SYMBOL
<br />DEVICE DESCRIPTION
<br />PULL STATION
<br />FF]
<br />FEWId
<br />PULL STATION OUTDOOR
<br />8
<br />SMOKE PHOTO DETECTOR
<br />BION
<br />SMOKE ION DETECTOR
<br />O
<br />BcO
<br />SMOKE C/O DETECTOR
<br />Q
<br />®
<br />HEAT DETECTOR
<br />F-
<br />z
<br />1 M:,:::-
<br />DUCT DETECTOR SUPPLY SIDE
<br />DUCT DETECTOR RETURN SIDE
<br />©s g
<br />FLOW SWITCH
<br />®
<br />BEAM DETECTOR
<br />M❑
<br />MONITOR MODULE
<br /><
<br />MINI -HORN
<br />(DwP
<br />HEAT DETECTOR WEATHER PROOF
<br />u) SYMBOL
<br />DEVICE DESCRIPTION
<br />Os g
<br />TAMPLR SWITCH
<br />®
<br />RELAY
<br />Z
<br />EOL
<br />END OF LINE RESISTOR
<br />U suRa
<br />SURGE SUPRESSOR
<br />DOOR HOLDER
<br />CO
<br />Rrs
<br />REMOTE TEST SWITCH
<br />c ❑
<br />CONTROL MODULE
<br />LU
<br />LOCK BOX (PROVIDED BY OTHERS)
<br />U
<br />CEILING MOUNTED
<br />SMOKE/HEAT
<br />DETECTOR
<br />24" MIN HANDICAP
<br />BEDROOM STROBE
<br />MORE THAN TWO APPLIANCES
<br />IN THE SAME ROOM OR ADJACENT
<br />SPACE WITHIN THE FIELD OF VIEW
<br />SHALL FLASH IN SYNCHRONIZATION.
<br />80" MIN
<br />96" MAX
<br />NFPA 72 2016
<br />(ADAAG)
<br />80" ABOVE HIGHEST FLOOR
<br />LEVEL OR 6" BELOW CEILING
<br />TO THE BOTTOM OF THE
<br />STROBE. WHICHEVER IS LOWER.
<br />FINISHED
<br />FLOOR
<br />3' (MIN)
<br />PER NFPA 7
<br />AUDIO/VISUAL
<br />& VISUAL -ONLY
<br />DEVICES
<br />A/C SUPPLY DIFFUSER
<br />CEILING MOUNTED NOTIFICATION
<br />DEVICE (TO BE WHITE).
<br />SEE PLAN FOR LOCATION.
<br />MANUAL
<br />PULL
<br />STATION
<br />48" (ADA)
<br />TO THE WORKING MECHANISM
<br />48" ALSO MEETS THE
<br />REQUIREMENTS OF NFPA 72 2016
<br />5'-0
<br />MAX FROM EXIT DOOR
<br />o
<br />MAGNETIC
<br />DOOR
<br />HOLDER
<br />ACCEPTABLE
<br />DO NOT INSTALL
<br />IN THIS AREA
<br />WALL MOUNTED
<br />HEAT DETECTOR -
<br />TO THE BOTTOM.
<br />WALL MOUNTED
<br />SMOKE DETECTOR -
<br />TO THE TOP.
<br />4"
<br />4"
<br />12" (MAX)
<br />Q
<br />REMOTE
<br />/-ANNUNCIATOR
<br />w Q o
<br />X
<br />0
<br />o
<br />Ln
<br />IMPORTANT NOTE NOTE
<br />NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE CHECK WITH MANUFACTURE'S INSTALLATION SHEET
<br />THE PLAN VIEW LAYOUT OF THE FIRE ALARM SYSTEM TO VERIFY WHICH FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF
<br />DEVICES APPLY, AND WHICH DO NOT. j BACK BOXES, AND WIRING REQUIREMENTS.
<br />FIRE ALARM DEVICE MOUNTING GUIDE
<br />TYPICAL SPRINKLER CLOSET WITH FIRE ALARM PANEL >
<br />INSTALLATION DIAGRAM. •
<br />10 g rJ 6 i/ �i •
<br />1 m
<br />FACP m
<br />'-
<br />MAIN TAMPERS AND WATERFLOWS
<br />,a
<br />=
<br />=
<br />Breaker Box
<br />d 2 FCPS
<br />EXTERIOR MAIN TAMPERS, BACKFLOWS, ETC.
<br />3)
<br />Oti
<br />INSTALLATION NOTES:
<br />1. 120voc Line in 1/2" or 3/4" EMT conduit, PVc or Flex
<br />supplied by electrical contractor.
<br />2. 120voc surge protector, supplied by Fire Alarm contractor,
<br />Installed by Electrical Contractor on Electrical breaker Panel.
<br />3. Splice Box, Installed and Supplied By Electrical Contractor.
<br />4. FACP, Supplied and Installed by Fire Alarm Contractor.
<br />5. FCPS, Supplied and Installed by Fire Alarm Contractor.
<br />6. 3/4" EMT Conduit or Flex Supplied By Electrical Contractor.
<br />7. PVC Box 6x6x4, Supplied and Installed by Electrical Contractor.
<br />8. 3/4" PVC Conduit for Underground Connection Front/To other
<br />Fire Alarm Closets.
<br />9. WaterFlow Sensor.
<br />10. Water Tamper.
<br />11. Surge Protector, Supplied and Installed BY Fire Alarm Contractor.
<br />12. 3/4 EMT Conduit or Flex Supplied By Electrical Contractor.
<br />13. 4 Square PVC Splice Box, Supplied and Installed by Fire Alarm
<br />Contractor,
<br />14. 1/2" or 3/4" PVC Conduit or Seal tight Flex Supplied By
<br />Electrical Contractor.
<br />15. 3/4" PVC Conduit for Underground Connection To Outside Tampers.
<br />16. Single gong Box attached to Water Tamper, Supplied and
<br />nstolled By E13ctrical Contractor.
<br />17. 4 Square Box with Rised P-Ring For Smoke Detector, Supplied
<br />By Electrical Contractor.
<br />18. Breaker Lock, Supplied By Electrical Contractor.
<br />ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING ALL THE
<br />NECESSARY HARDWARE (BOXES, CONNECTORS, CONDUITS, Etc.) AS WELL AS
<br />PARTIAL INSTALLATION AS PER INSTALLATION NOTES.
<br />_�,.., - I. IYiWI V �vR.iVNo 1'G':li -
<br />--= __-=-- - - - _ =- - _ _
<br />-7 If
<br />li.11 770
<br />-�
<br />\\ _-
<br />-,
<br />--- l
<br />_ - I------ --
<br />Building Type II - Bldg 1
<br />_ Imo- 1 �' .; -�_� - .. I I _ � �•
<br />r 2 '
<br />13
<br />I
<br />t _
<br />a - Ot-
<br />o-
<br />r
<br />n
<br />t- 'I
<br />9
<br />1 - L rY
<br />---I
<br />I _
<br />------------
<br />-------------
<br />Building Type I - Bldg 4
<br />�I -
<br />_._ ..
<br />m
<br />SITE PLAN
<br />THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND
<br />SEALED BY SAMUEL P. DEAN, P.E. ON [11.282022] USING
<br />A SHA-t AUTHENTICATION CODE. PRINTED COPIES OF
<br />THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
<br />SEALED AND THE SHA-1 AUTHENTICATION CODE MUST
<br />BE VERIFIED ON ANY ELECTRONIC COPIES.
<br />erie, rl,,-
<br />Fire Alarm & C mmunicati ns
<br />Cust mer Service is ur Greatest Techn I gy.
<br />SUPERIOR FIRE ALARM 8c
<br />COMMUNICATIONS
<br />6201 JOHNS ROAD
<br />SUITE 9
<br />TAMPA, FL 33634
<br />81 3- 81 8- 4444
<br />CERTIFIED ALARM SYSTEM
<br />:>
<br />CONTRACTOR 1
<br />LICENSE EF 20001162
<br />U.
<br />.,
<br />cn
<br />-IC7
<br />S
<br />E
<br />>1
<br />IC-
<br />-�
<br />N
<br />O
<br />N
<br />0
<br />0)
<br />-�-�
<br />6b
<br />JZ
<br />O~
<br />U 0
<br />:T
<br />ICn
<br />A
<br />g
<br />a w �
<br />0
<br />O O
<br />b. tv
<br />LL
<br />�LL
<br />J
<br />Q Z
<br />CAD DATE:
<br />9/9/2022
<br />NO. ISSUE/REVISION
<br />DATE
<br />Digitally signed
<br />`. 5•.�GENS�.
<br />No 83915
<br />by Samuel P.
<br />^�
<br />Dean
<br />p'. STATE OF
<br />Date: 2022.1 1.28
<br />T .0 P.,:�
<br />aPtk.Q.
<br />09:20:02-05'00'
<br />SAMUEL P. DEAN P.E.
<br />CONSULTING ENGINEER
<br />REGISTRATION NUMBER 83915
<br />CA # 29694
<br />1503-A WEST BUSCH BLVD.
<br />TAMPA FLORIDA 33612
<br />PHONE: (813) 961-3075
<br />FAX: (813) 961-1031
<br />email: sdeon@beltengineering.com
<br />I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE AND BELIEF
<br />ALL OF THE STRUCTURAL ELEMENTS AND SYSTEMS FOR THIS
<br />STRUCTURE HAVE BEEN DESIGNED TO BE IN COMPLIANCE
<br />WITH THE FLORIDA BUILDING CODE 7TH EDITION 2020. ALL
<br />OTHER ELEMENTS, SYSTEMS AND ASSEMBLIES ARE THE
<br />TOTAL RESPONSIBILITY OF OTHERS.
<br />511EET:
<br />f I RE ALARM
<br />fA- I of 3