ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DIFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />F� <br />424 WEATHERPROOF DUPLEX OUTLET <br />1­�W.P' <br />4m, GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />tt�G . F. 1. <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 THREE-WAY SWITCH <br />6. <br />P4 FOUR-WAY SWITCH <br />$R RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />RECESSED LIGHT FIXTURE <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUSTFAN <br />EXHAUST FAN/LIGHT COMBINATION <br />MQ ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CHIMES (OPTIONAL) <br />FCH <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SMOKE DETECTOR <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB TELEPHONE/USB (OPTIONAL) <br />[TV] TELEVISION (OPTIONAL) <br />7TV 2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />0 THERMOSTAT <br />F_ <br />Wi ELECTRIC METER <br />WP7I ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />A IL CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />ELECTRICAL SPECIFICATION NOTES: <br />3" VTR ELECTRICAL CONTRACTOR MUST VERIFY <br />3" VTR JIL <br />JIL WITH THE SPECIFICATIONS FOR THE TYPE <br />I OF FIXTURE TO BE USED. LIGHT FIXTURES <br />I SHOWN ARE FOR LOCATION PURPOSES. <br />I <br />OPT. <br />I I LAV LAV <br />r I I <br />HANSON I <br />BOX 1 <br />HANSON <br />I L <br />I <br />BOX I J-'v <br />W/C <br />:L:AV SHOW <br />T <br />TUB/ SHOWER q-] DISCONNECT <br />0 <br />W/C SHOWER - - - - - - - - - - - - - - - - - - - -- - - - - <br />OUTDOOR LIVING <br />� STUDOR DB INK C.O. > <br />:'I U DBL SINK INSTALL LIGHT <br />VENT <br />W/ DISP. ROUGH -IN <br />LAV 2 3� FOR OPT. < <br />FAN/LIGHT WP <br />W/C <br />N3 GFI <br />PLUMBING RISER. <br />SCALE:NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS- <br />LINIT-A 1532 (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />godo <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />5200 <br />TOTAL: 31768 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 131j <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />IN <br />P Serial Cable <br />NEMA <br />3R r <br />Power Co. Feed 11 L #4 Solid COPPER Ground <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6'apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />WT. 4 �� 1111_�_' R-M- <br />I <br />DINING <br />KI TCHEN) <br />F - - - <br />GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />/,>ROUGH -IN\ <br />4_i' FOR OPT <br />LIG <br />\-->FAN/ HT <br />FOYER</, - <br />DE <br />ENtRY WPO' <br />LIGHT AS, <br />P 1 <br />P1 <br />ECS,),,,GFiE <br />EFR SPECS <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />W <br />I-_ <br />W <br />LL <br />8 <br />Z <br />W 0 <br />> <br />G91 <br />raEL - j <br />G <br />I <br />I UPSTAIRS t <br />(Nal <br />GFI <br />44" <br />@ <br />A.F.F. <br />0 <br />GARAGE <br />GARAGE <br />LIGHT AS <br />TER SPECS <br />GARAGE <br />ODOOR <br />GFI <br />r- - - - - - - - - - - - - - - - -- <br />_j <br />LU <br />Z <br />P: < <br />0- <br />_j <br />< <br />W <br />_j <br />> W <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />1ST ELECTRICAL - UNIT -A 1532. <br />SCALE: Y4"=l'-Q" <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />I I <br />L -1 <br />2ND ELECTRICAL - UNIT -A 1532. <br />SCALE: Y4"=1'-0" <br />Cv* <br />C11.411 <br />cm <br />C1.4 <br />=M <br />cri <br />tn <br />Or> <br />CNI <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained <br />within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineers signature and <br />seal is only for <br />the structural engineering portions of the drawing pages beadng <br />Engineers signature and seal. <br />E <br />C) 0 <br />S C-4 <br />- <br />C <br />0 <br />Uj <br />3 Lo <br />U- <br />r-- r'� :2 <br />N 0 <br />L'L Lu , <br />EL UJ <br />M- <br />_j LL LL <br />co Z <br />3: 0 <br />Z <br />-F <br />5 <br />9 <br />0 S <br />0 <br />W <br />o <br />co <br />M LLI <br />Z <br />Z <br />IL <br />co 0 <br />c� 0 <br />U.) C) <br />a <br />N <br />"'I <br />Z <br />b d <br />EIF <br />W <br />U) <br />4-J <br />LU <br />DU <br />0 <br />L.0 <br />JAM <br />YZ <br />LLj <br />E <br />8 <br />C) 0 3� <br />U) 0 <br />0� .0 (D <br />0 <br />CD <br />C.0 <br />C10 <br />Z <br />Z <br />_j <br />U_ <br />C6 E <br />0 <br />Z< <br />C) <br />U <br />C" <br />00 <br />C%O E <br />10 <br />0 <br />0 < <br />�z <br />�z <br />fo <br />0 <br />< <br />.0 <br />1, <br />0� <br />Z' <br />Z <br />_j <br />.0 <br />5 <br />02 <br />0 <br />0 <br />W <br />C) <br />< <br />< <br />Z <br />0 <br />-0 <br />03 <br />0 <br />.2 C) <br />00 <br />co <br />CU <br />0 <br />(.0 <br />C-4 <br />cvl:) <br />Co <br />LL <br />LO <br />E <br />60 <br />U) <br />0 <br />C:) <br />co <br />0 <br />M <br />LO <br />CN <br />C-4 <br />C) <br />C:) <br />CF) <br />C-4 <br />LA-) <br />c.6 <br />T__ <br />CV) <br />E <br />0 <br />cc <br />Z <br />E <br />a) <br />C: <br />cc <br />E <br />0 0 <br />_j <br />-0 ca <br />< 0 1 <br />a) <br />_j <br />JOB <br />NO: 23-05707-05712 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />