Laserfiche WebLink
SPECIFICATIONS <br />1. CONSTRUCTION: <br />1. 1. 1. <br />ACI 318-05 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE <br />1.1.2. <br />ACI 530-05, ASCE 51TMS 402-05 & ACI 530.1415, ASCE 6/TMIS 602-05 <br />SPECIFICATIONS FOR MASONRY STRUCTURES. <br />ASTM C270-01a, C476-01, AND C90-01 SPECIFICATIONS FOR MASONRY STRUCTURES <br />NATIONAL DESIGN SPECIFICATIONS (NDS) FOR WOOD CONSTRUCTION, 2005 EDITION, AND ALL <br />ACCOMPANYING SUPPLEMENTS. <br />1.1.5. <br />FLORIDA RESIDENTIAL CODE (FRC), FLORIDA BUILDING CODE (FBC), 2007 EDITION, <br />(INCLUDING 2009 SUPPLEMENT). <br />"MANUAL OF STEEL CONSTRUCTION, ALLOWABLE STRESS DESIGN', BY THE AMERICAN <br />INSTITUTE OF STEEL CONSTRUCTION, (A1SC) 13TH EDITION. <br />1.1.7. <br />"DESIGN SPECIFICATION FOR LIGHT METAL PLATE CONNECTED WOOD TRUSSES"BY THE <br />TRUSS PLATE INSTITUTE TR11-02. <br />1.2. <br />DESIGN: <br />1.2.1. <br />ACI 318-05 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE <br />1.2.2. <br />ACI 530-05, ASCE 5/TMS 402-05 & ACI 530.1-05, ASCE 6/TMS 602-05 <br />SPECIFICATIONS FOR MASONRY STRUCTURES. <br />1.2.3. <br />ASTM C270-01a, C476-01, AND C90-01 SPECIFICATIONS FOR MASONRY STRUCTURES <br />1.2.4. <br />NATIONAL DESIGN SPECIFICATIONS (NDS) FOR WOOD CONSTRUCTION, 2005 EDITION, AND ALL <br />ACCOMPANYING SUPPLEMENTS. <br />1.2.5. <br />PLYWOOD DESIGN SPECIFICATIONS (APA) <br />1.2.6. <br />FLORIDA RESIDENTIAL CODE (FRC), FLORIDA BUILDING CODE (FBC), 2007 EDITION, <br />(INCLUDING 2009 SUPPLEMENT). <br />1.3. <br />SHOP DRAWINGS: <br />1.3.1. <br />THERE SHALL NOT BE ANY DEVIATIONS FROM THESE DESIGN PLANS BY OTHERS <br />DURING THE PREPARATION OF SHOP DRAWINGS WITHOUT WRITTEN APPROVAL FROM <br />THE ENGINEER OF RECORD. <br />1.3.2. <br />ALL SHOP DRAWINGS ARE TO BE SUBMITTED TO THE ENGINEER OF RECORD PRIOR TO <br />THE COMMENCEMENT OF CONSTRUCTION. <br />1.3.3. <br />ALL ROOF AND FLOOR TRUSS SHOP DRAWINGS ARE TO BE SIGNED AND SEALED BY A <br />FLA. REG. PE. AND SHALL INCLUDE: DRAWINGS AND CALCULATIONS, REACTIONS AND <br />BEARING POINTS, BRACING REQUIREMENTS, AND CONNECTIONS TO <br />SUPPORTING TRUSS MEMBERS. <br />2. DESIGN <br />LOADS <br />2.1. <br />DEAD LOADS: <br />2.1.1. <br />UNIT WEIGHT OF SOIL, COMPACTED: 120 PCF <br />2.1.2. <br />UNIT WEIGHT OF REINFORCED CONCRETE: 150 PCF <br />2.1.3. <br />UNIT WEIGHT OF 8"C.M.U. BLOCK: 55 PSF <br />2.1.4. <br />1ST FLOOR SUPERIMPOSED LOAD: 20 PSF <br />2.1.5. <br />UNIT WEIGHT OF 2X4 PARTITION WALLS: 11 PSF <br />2.1.6. <br />UNIT WEIGHT OF 2x6 BEARING WALLS: 12 PSF <br />2.1.7. <br />BALCONIES & DECKS: 15 PSF <br />2.1.8. <br />TILE ROOF <br />TOPCHORD: 15 PSF <br />BOTTOM CHORD: 10 PSF <br />2.1.9. <br />SHINGLE ROOF <br />TOPCHORD: 7 PSF <br />BOTTOM CHORD: 1OPSF <br />2.1.10. <br />FLOOR TRUSSES 15 <br />2.2. <br />LIVE LOADS: <br />2.2.1. <br />SIDEWALK AND DRIVEWAY LOAD: 250 PSF <br />2.2.2. <br />GARAGELOADS: 40 PSF <br />2.2.3. <br />PARTITIONED ROOMS: 40 PSF <br />2.2.4. <br />BALCONY AND DECKS: 60 PSF-UNDER 100 sq. ft. <br />2.2.5. <br />STAIRWAYS AND LANDINGS: 40 PSF <br />2.2.6. <br />2.2.7. <br />FLOOR TRUSS <br />TOP CHORD MINIMUM: 40 PSF <br />2.2.8. <br />ROOF TRUSS <br />TOP CHORD MINIMUM: 20 PSF <br />BOTTOM CHORD (WIO STORAGE): 10 PSF (NON -CONCURRENT) <br />2.3. <br />RAILING LOADS: <br />2.3.1. <br />ALL RAILING AND GUARD RAIL SYSTEM'S ARE TO BE DESIGNED TO WITHSTAND A <br />CONCENTRATED LOAD OF 200 POUNDS APPLIED AT ANY POINT AND IN ANY <br />DIRECTION ON THE RAILING. <br />2.3.2. <br />ALL RAILING AND GUARD RAIL SYSTEM'S ARE TO BE DESIGNED TO WITHSTAND A <br />HORIZONTAL LOAD OF 50 PLF ON THE GUARDRAIL AND A SIMULTANEOUS LOAD <br />OF 100 PLF APPLIED VERTICALLY DOWNWARD AT THE TOP OF THE GUARDRAIL <br />2.3.3. <br />GUARDRAIL SYSTEM SHALL BE DESIGNED TO WITHSTAND 2001b CONCENTRATED <br />HORIZONTAL LOAD APPLIED ON 1 SQ. FT. AT ANY POINT IN THE SYSTEM. <br />2.3.4. <br />2.3.1.,2.3.2 & 2.3.3. ARE NOT REQUIRED TO BE APPLIED SIMULTANEOUSLY, BUT EACH <br />SHALL BE APPLIED TO PRODUCE THE MAXIMUM STRESSES IN THE MEMBER COMPONENTS. <br />2.4. <br />WIND LOADS: <br />2.4.1. WIND DESIGN TO BE CONDUCTED IN ACCORDANCE WITH SECT. R301.2 OF THE FBC 2007 EDITION, <br />AND CONDUCTED BASED ON A120 MPH 3 SECOND GUST, EXPOSURE -C, IMPORTANCE FACTOR <br />"I"= 1.0. ENCLOSED BUILDING <br />2.4.2. NET UPLIFT DEAD LOADS - 10 PSF SHINGLE, 15 PSF TILE <br />2.4.3. WIND LOAD DETERMINATION BASED ON ASCE 7-05 <br />2.5. DEFLECTIONS: <br />2.6.1. FLOOR TRUSSES SHALL LIMIT DEFLECTION TO 1/360 TIMES THE SPAN FOR LIVE LOADS AND 1/240 TIMES <br />THE SPAN FOR TOTAL LOAD. <br />3. DESIGN METHOD <br />3.1. LOAD FACTOR DESIGN: <br />3.1.1. THE LOAD FACTOR DESIGN METHOD WAS USED TO DESIGN: <br />CAST -IN -PLACE CONCRETE SLABS AND FOOTINGS <br />3.2. SERVICE LOAD DESIGN: <br />3.2.1. THE SERVICE LOAD DESIGN METHOD WAS USED TO DESIGN: <br />MASONRY WALLS AND LINTELS <br />INTERIOR AND EXTERIOR WOOD FRAMING AND SHEATHING <br />STAIRS AND FLOOR FRAMING <br />ROOF FRAMING, SHEATHING AND UPLIFT <br />3.3. LOAD COMBINATIONS FOR LRFD DESIGNS: <br />3.3.1. THE FOLLOWING LOAD COMBINATIONS WERE DESIGNED FOR: <br />TOTAL DL + FLOOR LL + ROOF LL <br />TOTAL DL + FLOOR LL + WL <br />TOTAL DL + WIL <br />3.3.2. ALL ROOF AND FLOOR TRUSSES SHALL BE DESIGNED TO RESIST THE WORST LOAD <br />COMBINATION RESULTING IN THE MAXIMUM STRESSES PLACED ON THAT COMPONENT. <br />BOTH PARTIAL, FULL, AND ALTERNATING SPAN LOADING ARE TO BE CONSIDERED. <br />3.4. DESIGN ASSUMPTIONS: <br />3.4.1. ALL FOUNDATIONS ARE CENTERED UNDER SUPPORTED COLUMNS AND WALLS UNLESS <br />SHOWN OTHERWISE IN THE DESIGN PLANS. <br />4. MATERIALS <br />4.1. REINFORCING STEEL: <br />4.1.1. <br />REINFORCING STEEL SHALL BE ASTM A615-04a MIN. GRADE 40, fy = 40 Ksi <br />4.1.2. <br />LAP SPLICE SHALL BE AS FOLLOWS: #5 BAR 25", #4 BAR 20", #3 BAR 20". <br />4.1.3. <br />ALL DIMENSIONS PERTAINING TO THE LOCATION OF REINFORCING ARE TO THE <br />CENTERLINE OF EACH BAR EXCEPT WHERE THE COVER DIMENSION IS SHOWN TO THE <br />FACE OF THE CONCRETE. <br />4.1.4. <br />REINFORCING DETAIL DIMENSIONS ARE OUT TO OUT OF BARS. <br />4.1.5. <br />REINFORCING MECHANiCAL COUPLERS ARE TO DEVELOP 125 % OF THE REQUIRED <br />YIELD STRENGTH OF THE BAR AND ARE TO BE APPROVED BY THE ENGINEER OF <br />RECORD. <br />4.1.6. <br />DESIGN COVER REQUIREMENTS: <br />C-1-P CONCRETE FORMED AGAINST EARTH: <br />3' <br />C-1-P CONCRETE EXPOSED TO EXTERIOR: <br />2' <br />C-1-P CONCRETE NOT EXPOSED: <br />GROUT FILLED MASONRY: <br />1)!r <br />4.1.7. <br />WELDED WIRE FABRIC (WWF): ASTM Al 85-01 <br />y4" <br />4.1.8. <br />DETAIL REINFORCEMENT IN ACCORDANCE WITH ACI 318-05 (STRUCTURAL CONCRETE) <br />ACI 530-5 (MASONRY STRUCTURES) <br />4.2. CONCRETE: <br />4.2.1. <br />CONCRETE TYPE <br />MIN. 28 DAY <br />DESIGN ft) <br />MODULES OF <br />ELASTICITY <br />DESIGN (E) <br />C-1-P CONCRETE (NORMAL WEIGHT) <br />2,500 Psi <br />2,850 Ksl <br />C-1-P CONCRETE (NORMAL WEIGHT) HERNANDO CO. ONLY <br />3,000 Psi <br />3,122 Ksi <br />C-1-P GROUT <br />3,000 Psi <br />3,122 Ksi <br />4.2.2. <br />CONCRETE SHALL CONSIST OF 1" MAXIMUM AGGREGATE CONCRETE MIX WITH SLUMP <br />BETWEEN 6"AND 7"AT TIME OF PLACEMENT. SEE SPECIFICATIONS FOR ADDITIONAL <br />CRITERIA. <br />4.2.3. <br />GROUT SHALL CONSIST OF PEA ROCK (3/8' MAXIMUM AGGREGATE) CONCRETE MIX <br />WITH SLUMP BETWEEN 8"AND 1 0"AT TIME OF PLACEMENT. SEE SPECIFICATIONS FOR <br />ADDITIONAL CRITERIA. <br />4.2.4. <br />CONSTRUCTION JOINTS WILL BE PERMITTED <br />4.2.5. <br />METHOD OF CONCRETE FORMING, PLACEMENT AND CURING SHALL BE CONDUCTED IN <br />ACCORDANCE WITH THE SPECIFICATIONS AS STATED. <br />4.2.6. <br />EARTH SUPPORTED SLABS (EXCLUDING EXTERIOR WALKWAYS & DRIVEWAYS): <br />3 1/2"MIN. THICKNESS W/ MIN. REINFORCEMENT OF 6.0 x 6.0 W/ 1.4 x 1.4 WWF @ <br />MID -DEPTH OF SLAB. FIBER MESH PER DESIGN MIX MAY BE USED I.L.O. WWF @ <br />CONTRACTORS DISCRETION. <br />4.2.7. <br />CONCRETE PLACEMENT PRACTICES SHALL BE IN ACCORDANCE W/ ALL <br />ACI- MCP 20(9 STANDARDS. <br />4.3. <br />CONCRETE MASONRY: <br />4.3.1. <br />FILLED CELLS W/ (1) #5 BAR SHALL BE LOCATED PER PLAN. <br />4.3.2. <br />LOAD BEARING CONCRETE MASONRY BLOCK SHALL BE ASTM C90-03, TYPE 11 <br />NON -MOISTURE CONTROLLED. <br />4.3.3. <br />ALL CELLS & CAVITIES BELOW GRADE WILL BE FILLED W1 CONCRETE IN ALL <br />STEM WALLS. <br />4.3.4. <br />THE AGGREGATE STRENGTH OF THE BLOCK AND MORTAR SHALL BE F'm = 1,500 PSI <br />MINIMUM. <br />4.3.5. <br />METHOD OF CONCRETE MASONRY PLACEMENT AND CONSTRUCTION SHALL BE <br />CONDUCTED IN ACCORDANCE WITH THE SPECIFICATIONS AS STATED. <br />4.3.6. <br />MORTAR SHALL BE ASTMI C270-4 TYPE"S" FOR ALL MASONRY CONSTRUCTION. <br />4.4. <br />STRUCTURAL LUMBER: <br />4.4.1.1. <br />INTERIOR LOAD BEARING WA_LLS SPF, fb = 675 PSI, E 1200 Ksl <br />ALL EXTERIOR FRAMING SPF, fb = 675 PSI, E = 1200 Ks! <br />4.4.1.2. <br />ALL FRAME WALLS TO BE CONSTRUCTED USING SPF, <br />STUD QUALITY OR BETTER <br />4.4.2. <br />ALL PLYWOOD USED FOR EXTERIOR APPLICATIONS <br />SHALL BE APA RATED SHEATHING EXP 1 U.N.O. <br />4.4.3. <br />ALL PLYWOOD USED FOR INTERIOR APPLICATIONS SUCH AS SUB FLOORING AND <br />SHEARWALLS SHALL BE APA RATED SHEATHING EXP 1 U.N.O. <br />4.4.4. <br />IF OSB BOARD IS TO BE USED IN PLACE OF PLYWOOD IS TO HAVE SIMILAR OR <br />GREATER SECTION PROPERTIES. <br />4.4.5. <br />ONLY STRUCTURAL LUMBER TO BE USED FOR AN EXTERIOR APPLICATION. WOOD IN <br />CONTACT WITH CONCRETE IS TO RECEIVE A STANDARD GRADE PRESSURE TREATING. <br />4.4.6. <br />WHEN PRE ENGINEERED TRUSSES ARE CALLED FOR ON THE PLANS THE <br />MANUFACTURER IS TO SUBMIT SHOP DRAWINGS TO THE ENGINEER OF RECORD. <br />4.4.7. <br />DESIGN, FABRICATE AND ERECT WOOD TRUSSES IN ACCORDANCE WITH THE -DESIGN <br />SPECIFICATION FOR LIGHT METAL PLATE CONNECTED WOOD TRUSSES" BY THE <br />ANSI/TPI 1-2002, BCSI 1 - 03 <br />4.4.8. <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES <br />SHALL BE PROVIDED AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />4.4.9. <br />ALL EXTERIOR FRAME WALLS SHALL BE STUCCO FINISHI- 7/8"STUCCO FINISH PER <br />ASTM C. 926, APPLY 3 LAYERS W/ TOTAL THICKNESS 7/8. OVER METAL LATH. FIRST <br />2 LAYERS 3t8"THICK EACH. 3RD LAYER 1/8"THICK <br />4.4.10. <br />INSTALLATION OF EXTERIOR LATHING & FRAMING SHALL COMPLY TO ASTM C 1063 <br />PER FLORIDA RESIDENTIAL CODE R703.6.2 <br />4.5. <br />FASTENERS AND TIE DOWNS: <br />4.5.1. <br />FASTENERS AND TIE DOWNS SHALL CONSIST OF BUT ARE NOT LIMITED TO: <br />SHAPES, ANGLES, CHANNELS: ASTM A36136M 01 Fy = 36 Ks! <br />ROUND METAL PIPE: ASTM A53-01, GRADE B Fy = 35 Ks! <br />SQUARE METAL TUBING: ASTM A500-03a, GRADE B Fy = 46KsI <br />HIGH STRENGTH BOLTS: ASTM A325-94 <br />MACHINE BOLTS: GALVANIZED ASTM A307-03 <br />4.5.2. <br />SHEET MET.AJ_ ACCESSORIES SHALL CONFORM TO: Fy = 33KsIWITH G90 <br />GALVANIZED COATING IN ACCORDANCE WITH ASTM A525-87. <br />4.5.3. <br />NAILS SHALL CONSIST OF: COMMON WIRE NAILS WITH MINIMUM DIAMETER AS <br />FOLLOWS: 8d = 0.131', 10d = 0.148", 12d = 0.148", 16d = 0.162". <br />4.5.4. <br />ALL FASTENERS AND TIE DOWNS EMBEDDED IN CONCRETE OR USED IN AN EXTERIOR <br />APPLICATION ARE TO RECEIVE AN ANTI -CORROSIVE COATING BY MANUFACTURER <br />PRIOR TO INSTALLATION. <br />4.5.5. <br />ALL FASTENERS AND TIE DOWNS ARE TO PROVIDE THE UPLIFT CAPACITY CALLED <br />FOR IN THE PLANS ARE A MINIMUM. <br />4.5.6. <br />ALL FASTENER TIE DOWNS, BEAM HANGERS, JOIST HANGERS, AND FLOOR TRUSS <br />STRAPPING ARE TO BE INSTALLED IN ACCORDANCE WITH THE PLANS AND <br />SPECIFICATIONS. <br />4.5.7. <br />CONCRETE EMBEDDEDXBOLTS USED FOR UPLIFT ARE TO BE WET SET PRIOR TO <br />INITIAL SET OF THE CONCRETE, SPACING AND ALIGNMENT ARE TO BE IN ACCORDANCE <br />WITH THE DESIGN PLANS, U.N.O. ALTERNATES TO 7 BOLTS ARE NOTED ON PLANS. <br />4.5.8. <br />CONCRETE EMBEDDED TIE DOWNS USED FOR TRUSS AND WALL UPLIFT ARE TO BE <br />PLACED AROUND EMBEDDED REINFORCING PRIOR TO OR WHILE PLACING GROUT. <br />4.6. <br />MICRO -LAM <br />LUMBER: <br />4.6.1. <br />MICRO -LAM STRESS GRADES SHALL PROVIDE THE FOLLOWING MINIMUM PROPERTIES: <br />E 2,000,000 PSI <br />Fb 2,950 PSI <br />Ft 1,850 PSI <br />Fc 500 PSI (PERPENDICULAR) <br />Fc 2,700 (PARALLEL) <br />4.7. <br />STEEL: <br />Fv 285 PSI <br />4.7.1. <br />INSTALLATION OF ALL STEEL TO BE PERFORMED BY AN EXPERIENCED, QUALIFIED <br />STEEL ERECTOR. <br />4.7.2. <br />FABRICATE AND ERECT ALL STRUCTURAL STEEL IN ACCORDANCE WITH A.I.S.C. <br />"SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL <br />STEEL FOR BUILDINGS'. <br />4.7.3. <br />STRUCTURAL STEEL: ASTM A36/36M 01. <br />4.7.4. <br />STEEL TUBING: ASTM A500-03a, GRADE B. <br />4.7.5. <br />WELDED CONNECTIONS: E70XX ELECTRODES, MINIMUM SIZE FILLET WELDS 3/16", AWS <br />CERTIFIED WELDERS. CERTIFICATION PAPERS TO BE SUBMITTED UPON REQUEST. <br />4.7.6. <br />WHERE STEEL BEAMS ARE CONTINUOUS OVER COLUMNS, PROVIDE WEB STIFFENER <br />PLATES ON EACH SIDE OF THE WEB, OF A THICKNESS EQUAL TO BEAM FLANGE <br />THICKNESS, LOCATED AT THE CENTER LINE OF THE TUBE COLUMN. <br />4.T 7. <br />THE STEEL FRAME IS"NON-SELF SUPPORTING". ADEQUATE TEMPORARY SUPPORT <br />SHALL BE PROVIDED BY THE CONTRACTOR UNTIL REQUIRED CONNECTIONS OR <br />4.3. <br />SOIL: <br />ELEMENTS ARE IN PLACE. <br />4,8A. <br />MINIMUM SOIL BEARING PRESSURE CAPACITY OF 2000 PSF. <br />FOUNDATIONS HAVE BEEN DESIGNED WITH THE MIN. CAPACITY OF 2000 PSF <br />4.8.2. <br />ALL SOIL IS TO BE CLEAN & POISONED FOR TERMITES PER FRC 2007 W1 2009 REVISIONS, RESIDENTIAL SECTIONS <br />R320.1, R320.2, R320.3, & R704. <br />4.8.3. <br />SOIL IS TO BE COMPACTED TO 95% MODIFIED PROCTOR AS DEFINED BY ASTM D 1557-00 <br />TERMITE PROTECTION - <br />PLANS MUST SPECIFY TYPE OF TERMITE TREATMENT <br />Soil Chemical Barrier Method <br />Other treatment - Must specify proposed method and submit documentation, which <br />substantiates the proposed method, is an approved termite prolection system or method. <br />IF CHEMICAL SOIL TERMITE TREATMENT IS USED <br />1 FIRC 105.11 - "A permanent sign which identifies the termite treatment provider <br />and need for re -inspection and"atment contract renewal shall be provided. <br />The sign shall be posted near the water heater or electric panel" <br />2. Condensate and roof downspouts shall discharge at least <br />T�0' away from the building side walls. <br />3. Irrigation/sTrinkler sN ftbrns includi I risers and <br />spray heal � shall n be installed WA V-0" of the building side wall. <br />4. FIRC R704- To provide for inspection for termite infestation between <br />wall covering and final earth grade shall not be less than 6 inches. <br />Exception: Paint or decorative comentilious finish less than 518" <br />thick adhered directly to the foundation wall. <br />5. FRC R320.1.1 - Initial treatment shall be done after all excavation <br />and backfill is complete. <br />6. FIRC R320.1.2 - Soil disturbed after the initial treatment shall be retreated <br />including spaces boxed or formed. <br />7. FIRC R320.1.3 - Boxed areas in concrete floors for subsequent installation of traps <br />etc., shall be made with permanent metal or plastic forms. Permanent forms must be <br />of a size and depth that will eliminate the disturbance of soil after the initial treatment. <br />8. FRC R320.1.4 - Minimum 6 mil vapor retarder must be installed to protect against <br />rainfall dilution. If MVill occurs b9bre vapor retarder placement, <br />retreatment is requi . <br />9. FRC L320.ml 65 ee rgDur nd mortar along the foundation perimeter <br />re v;= <br />re on r soi <br />must , treatment. <br />10. FIRC R320.1.6 - Soil treatment must be applied under all exterior concrete <br />or grade within V-0" of the structure sidewalls. <br />11. FRC R320.1.6 - An exterior vertical chemical border must be installed after <br />construction is complete, including landscaping and irrigation. Any soil disturbed <br />after the vertical baffler is applied, shall be hAFeated, <br />12. FIRC R320.1 - All buildings are required to have pre -construction treatment. <br />13. FIRC R320.1 - A certificate of compliance must be issued to the building department <br />b i licensed post control company before a certificate of occupancy will b6 issued. <br />Tgeacertificate of compliance shall state: "The building has received a complete <br />treatment for the prevention of subterranean termites. The treatment is in <br />accordance with the rules and laws of the Florida Department of Agriculture <br />and Consumer Services". <br />14. FRC R320.3 - After all work is completed, loose wood and fill must be removed <br />from below and within I-V of the building. This includes all grade stakes, <br />tub trap boxes, forms, shoring or other cellulose containing material. <br />NOTE: BORATE APPLIED TO ALL FRAME MEMBERS WITHIN 24" A.F.F. <br />1) METHOD OF TREATMENT SHALL BE APPROVED BY THE GOVERNING JURISDICTION -LIQUID <br />BORATE OR BOR-A-COR" PRODUCT METHODS MUST BE DETERMINED AT PERMIT STAGE. <br />2) PRESSURE TREATED LUMBER THAT HAS BEEN CUT OR DRILLED THAT EXPOSES UNTREATED <br />PORTIONS OF WOOD ARE REQUIRED TO BE FIELD TREATED TO PREVENT INSECT INFESTATION. <br />ATTENTION: CHEMICAL CHANGES IN PRESSURE TREATED WOODS <br />AS OF DECEMBER 31ST, 2003, CHROMATED COPPER ARSENATE (CCA-C) WILL NO LONGER BE PRODUCED FOR RESIDENTIAL OR GENERAL <br />CONSUMER USE. SEVERAL NEW PRESSURE TREATED WOOD ALTERNATIVES HAVE BEEN CREATED TO REPLACE CCA-C. MANY OF THE NEW <br />PRESSURE TREATED WOODS USE CHEMICALS THAT ARE CORROSIVE TO STEEL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TYPE <br />OF WOOD TREATMENT AND TO SELECT APPROPRIATE CONNECTORS THAT RESIST CORROSION. FOR EXAMPLE, ACQ-C,ACQ-D, CBA-A, ORCA-B <br />REQUIRE HOT -DIPPED GALVANIZED OR STAINLESS STEEL FASTENERS. DOT SODIUM BORATE (SBX) DOES NOT. <br />REQUIRED SAFETY GLAZING IN HAZARDOUS LOCATIONS <br />(RE: FRC R308.4) <br />R308.3 HUMAN IMPACT LOADS. INDIVIDUAL GLAZED AREAS INCLUDING GLASS MIRRORS IN HAZARDOUS LOCATIONS SUCH AS THOSE <br />INDICATED AS DEFINED IN SECTION R308.4 SHALL PASS THE TEST REQUIREMENTS OF CPSC 16 CFR, PART 1201 CRITERIA FOR <br />CATEGORY I OR CATEGORY 11 AS INDICATED IN TABLE R308.3 <br />EXCEPTIONS: <br />1. POLISHED WIRED GLASS FOR USE IN FIRE DOORS AND OTHER FIRE RESISTANT LOCATIONS SHALL COMPANY WITH ANSI <br />Z97.1 <br />2. LOUVERED WINDOWS AND JALOUSIES SHALL COMPANY WITH SECTION R308.2 <br />R308.4 HAZARDOUS LOCATIONS. <br />THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSE OF GLAZING: <br />1. GLAZING IN SWINGING DOORS EXCEPT JALOUSIES. <br />2. GLAZING IN FIXED AND SLIDING PANELS OF SLIDING DOOR ASSEMBLIES AND PANELS IN SLIDING AND BIFOLD CLOSET DOOR <br />ASSEMBLIES. <br />3. GLAZING IN STORM DOORS. <br />4. GLAZING IN ALL UNFRAMED SWINGING DOORS. <br />5. GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS, AND SHOWERS. <br />GLAZING IN ANY PART OF A BUILDING WALL ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE <br />GLAZING IS LESS THAN 60 INCHES (1524MM) MEASURED VERTICALLY ABOVE ANY STANDING OR WALKING SURFACE. <br />6. GLAZING, IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT TO A DOOR WHERE THE NEAREST VERTICAL EDGE IS <br />WITHIN A 244NCH(610MM) ARC OF THE DOOR IN A CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES <br />(1524MM) ABOVE THE FLOOR OR WALKING SURFACE. <br />7. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS DESCRIBED IN ITEMS 5 AND 6 <br />ABOVE, THAT MEETS ALL OF THE FOLLOWING CONDITIONS: <br />7.1 EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 SQUARE FEET (0.836 M2). <br />7.2 BOTTOM EDGE LESS THAN 18 INCHES (457 MM) ABOVE THE FLOOR. <br />7.3 TOP EDGE GREATER THAN 36 INCHES (914 MM) ABOVE THE FLOOR. <br />7.4 ONE OR MORE WALKING SURFACES WITHIN 36 INCHES (914 MM) HORIZONTALLY OF THE <br />GLAZING. <br />8. ALL GLAZING IN RAILINGS REGARDLESS OF AN AREA OR HEIGHT ABOVE WALKING SURFACE. INCLUDED ARE STRUCTURAL <br />BALUSTER PANELS AND NONSTRUCTURAL IN FILL -PANELS. <br />9. G122-ING IN WALLS AND FENCES ENCLOSING INDOOR AND OUTDOOR SWIMMING POOLS, HOT TUBS AND SPAS WHERE THE <br />BOTTOM EDGE OF THE GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A WALKING SURFACE AND WITHIN 60 INCHES (1524 <br />MM) HORIZONTALLY OF THE WATER'S EDGE. THIS SHALL APPLY TO SINGLE GLAZING AND ALL PANES IN MULTIPLE GLAZING. <br />10. GLAZING ADJACENT TO STAIRWAYS, LANDINGS, AND RAMPS WITHIN 36 INCHES (914 MM) HORIZONTALLY OF A WALKING <br />SURFACE WHEN THE EXPOSED SURFACE OF THE GLASS IS LESS THAN 60 INCHES (1524 MM) ABOVE THE PLANE OF THE <br />ADJACENT WALKING SURFACE. <br />11. GLAZING ADJACENT TO STAIRWAYS WITHIN 60 INCHES (1524 MM) HORIZONTALLY OF THE BOTTOM TREAD OF A STAIRWAY IN <br />ANY DIRECTION WHEN THE EXPOSED SURFACE OF THE GLASS IS LESS THAN 60 INCHES (1524 MM) ABOVE THE NOSE OF THE <br />TREAD. <br />I EXCEPTION: THE FOLLOWING PRODUCTS, MATERIALS AND USES ARE EXEMPT FROM THE ABOVE HAZARDOUS LOCATIONS: <br />1. OPENINGS IN DOORS THROUGH WHICH A 3-INCH(76 MM) SPHERE IS UNABLE TO PASS. <br />2. DECORATIVE GLASS IN ITEMS 1, 6 OR 7. <br />3. GLAZING IN SECTION R308.4, ITEM 6, WHEN THERE IS AN INTERVENING WALL OR OTHER PERMANENT BARRIER BETWEEN THE <br />DOOR AND THE GLAZING. <br />4. GLAZING IN SECTION R 308.4, ITEM 6, IN WALLS PERPENDICULAR TO THE PLANE OF THE DOOR IN A CLOSED POSITION OR <br />WHERE ACCESS THROUGH THE DOOR IS TO A CLOSET OR STORAGE AREA 3 FEET (914 MM) OR LESS IN DEPTH. GLAZING IN <br />THESE APPLICATIONS SHALL COMPANY WITH SECTION R308.4, ITEM 7. <br />5. GLAZING IN SECTION R308.4, ITEMS 7 AND 10, WHEN A PROTECTIVE BAR IS INSTALLED ON THESE ACCESSIBLE SIDE(S) OF <br />THE GLAZING 36 INCHES ± 2 INCHES (914 ± MM 51 MM) ABOVE THE FLOOR. THE BAR SHALL BE CAPABLE OF WITHSTANDING A <br />HORIZONTAL LOAD OF 50 POUNDS PER LINEAR FOOT KG/M) WITHOUT CONTACTING THE GLASS AND BE A MINIMUM OF 1 Y2 <br />INCHES (38 MM) IN HEIGHT. <br />6. OUTBOARD PANES IN INSULATING GLASS UNITS AND OTHER MULTIPLE GLAZED PANELS IN SECTION R308.4, ITEM 7, WHEN <br />THE BOTTOM EDGE OF THE GLASS IS 25 FEET (7620 MM) OR MORE ABOVE GRADE, A ROOF, WALKING SURFACES, OR OTHER <br />HORIZONTAL [WITHIN 45 DEGREES (0.79 RAD) OF HORIZONTAL] SURFACE ADJACENT TO THE GLASS EXTERIOR. <br />7. LOUVERED WINDOWS AND JALOUSIES COMPLYING WITH THE REQUIREMENTS OF SECTION <br />R308.2. <br />8. MIRRORS AND OTHER GLASS PANELS MOUNTED OR HUNG ON A SURFACE THAT PROVIDES A CONTINUOUS BACKING <br />SUPPORT. <br />9. SAFETY GLAZING IN SECTION R308.4, ITEMS 10 AND 11 IS NOT REQUIRED WHERE: <br />9.1 THE SIDE OF STAIRWAY, LANDING OR RAMP HAS A GUARDRAIL OR HANDRAIL, INCLUDING BALUSTERS OR <br />IN -FILL PANELS, COMPLYING WITH THE PREVISIONS OF SECTION 1012 AND 1607.7 OF THE FLORIDA BUILDING CODE, BUILDING; <br />AND <br />9.2 THE PLANE OF THE GLASS IS GREATER THEN IS INCHES (457 MM) FROM THE RAILING. <br />BUILDING DATA <br />WIND SPEED 120 MPH <br />WIND IMPORTANCE FACTOR - (1w) = 1.0 <br />WIND EXPOSURE - 'C' (FRC R301) <br />INTERNAL PRESSURE COEFFICIENT= +/- 0.18 ENCLOSED BLDG) <br />DESIGN WIND PRESSURE: <br />(COMPONENT AND CLADDING) WORSTCASE (10 SF - END ZONE) <br /># END ZONE IS ONLY WITHIN T-0" <br />OF ALL EXTERIOR BUILDING CORNERS <br />WINDOWS AND DOORS <br />CONSTRUCTION 120 MPH + 33.4 PSF 44.8 PSF (END) U.N.O. <br />TYPE: 513 + 33.4 PSF/ -36.2 PSF (INTERIOR) U.N.O. <br />GARAGE DOORS (V = 120 MPH) <br />SINGLE 90 +27.6 PSF / -31.2 PSF <br />DOUBLE 16x7 +26.4 PSF / -29.4 PSF <br />NOTE: <br />IT IS THE CONTRACTORS RESPONSIBILITY TO REVIEW ALL DRAWINGS BEFORE <br />CONSTRUCTION BEGINS. FLORIDA DESIGN SOLUTIONS, INC. IS RESPONSIBLE FOR THE <br />STRUCTURAL INTEGRITY OF THIS PROJECT ONLY. ANY DISCREPANCY BETWEEN FIELD <br />CONDITIONS, OTHER DESIGN PROFESSIONALS' SHOP DRAWINGS, CONTRACTORS' <br />BUILDING METHODS, AND THESE SIGNED AND SEALED DRAWINGS MUST BE BROUGHT TO <br />THE ATTENTION OF FLORIDA DESIGN SOLUTIONS, INC. PRIOR TO THE COMMENCEMENT OF <br />CONSTRUCTION. <br />NOTE: <br />GYPSUM BOARD MAY BE INSTALLED USING GWB54 NAILS TO SET IN PLACE. FIELD <br />FASTENING SHOULD BE TYPE"W" 1%" DRYWALL SCREWS AT 12" O.C. FOR CEILINGS AND 1Y811 <br />DRYWALL SCREWS AT 12" O.C. FOR WALLS. ALL ENDS AND EDGES OF WALLBAORD SHALL <br />OCCUR OVER AND BE SCREWED TO SUPPORTS. MAXIMUM SCREW SPACING AT ENDS <br />(EDGES IN VERTICAL APPLICATION) SHALL BE 6" O.C. AT EACH SUPPORT. MINIMUM SCREW/ <br />NAIL DISTANCEFROM EDGE SHALL BE %8". THIS SHALL APPLY TO BOTH CEILING AND WALL <br />INSTALLATION. DRYWALL SHIMS SHALL BE USED ONLY WHERE NECESSARY. OPENINGS <br />CUT FOR OUTLETS, SWITCHES, ETC, SHALL BE OF A TOLERANCE THAT CAN BE COVERED <br />ADEQUATELY WITH NORMAL SWITCH PLATES AND COVERS WITHOUT ADDITIONAL TAPING <br />OR CAULKING. DRYWALL SHALL NOT BE INSTALLED WITHOUT PROPER BACKING. <br />NOTE: <br />THE EOR HAS VERIFIED THAT HEM FIR WOOD STUDS AND FLAT MATERIAL CAN <br />BE SUBSTITUTED FOR SPRUCE PINE FIR LUMBER PROVIDED THE SAME <br />MATERIAL GRADE NUMBER IS USED. <br />ALL HEADERS, BEAMS, ETC ARE TO BE SYP #2 OR BETTER AND OR MICROLAM <br />AS INDICATED ON THE DRAWINGS AND CAN NOT BE REVISED. <br />C <br />U <br />0 <br />.5 <br />E CF) 0 <br />0 65 <br />0 N <br />0 <br />CM <br />m r, E <br />00 <br />C: <br />ni't <br />Q <br />.2 c,) <br />LL <br />(a <br />0 Ce) <br />CO <br />(D <br />0 <br />0 N 0 <br />CL 0 <br />0 Co <br />CX CD <br />0 <br />0 <br />0 <br />0 <br />A E <br />ff U <br />N -C -B -D �C <br />Cq <br />#A <br />4 - OQ <br />U_ <br />ow- <br />ry <br />EN <br />Tothe bestoftheen neerAWnoewledgeand <br />understanding, the structural plans and <br />specifications comply with the 2007 Florida <br />Building Code, Residential with 2009 revisions <br />signed and sealed for the structural portion of this <br />drawing. <br />V-4 <br />Ln <br />Z :Lj Cn <br />0 :3 1 <br />CD <br />�_4 V) <br />V) %D <br />> <br />a. <br />0 <br />z <br />LL <br />r4 <br />z <br />Z.0 <br />3 <br />W <br />LU <br />In a) <br />Ln <br />Ln <br />z <br />z <br />LLJ <br />0 <br />W z <br />LLJ LL <br />LL, LLI Z <br />0 z<0 <br />ffioo.w <br />Z�- U�< <br />0 <br />Z Z Z <br />Z <br />3.8 <br />8 0 15 W <br />2 LU 04 <br />0 z <br />CD <br />LU <br />CE Z. <br />LU <br />T-4 <br />5- <br />%D <br />r*4 <br />0 <br />ko <br />=T-1 <br />Ln <br />Z <br />Uj 0 (:"j <br />U r VI M <br />90zW <br />0 <br />z <br />z 5 UrL, 0 <br />CY -,am <br />Lu LLI in 0 <br />p <br />(y) <br />LL. <br />X <br />LLJ <br />T__I <br />C:) <br />z <br />? !g g 8 <br />0 LL Z <br />I.- YL 8 <br />5 OW 0 <br />LL <br />z <br />0 <br />CY) <br />r-q <br />LLi <br />iFt- <br />F- <br />LL <br />z <br />LU <br />> <br />z <br />z <br />0 <br />SCALE <br />AS NOTED <br />PLOT DATE: 07/08/2011 <br />VERSION NO. <br />1000 <br />JOB NO: 11-0958-0961 <br />SHEET NO. <br />S N <br />