Laserfiche WebLink
-GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to centered line of the box to be: 16" <br />AFF (general) <br />kitchen 44" AFF <br />bathroom 39" AFF <br />laundry room 36" AFF <br />exterior waterproof 12" AFF <br />garage general purpose 42" AFF <br />range 2" AFF <br />2. All trim plates & devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance <br />with the national electric code, latest edition, by a licensed electrical contractor who shall be <br />responsible for the installation & sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R313.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination tyke installed to provide protection <br />of the branch circuits in all dwelling units per NFPA 70 and the 2008 NEC. <br />7. Provide Tamper Resistant Receptacles as required by the 2008 NEC, 406.11 <br />8. R313.2 1 carbon monoxide protection: carbon monoxide alarms or detectors shall be installed <br />in all dwelling units in accordance with NFPA 70. Such devices shall be listed by the <br />appropriate standard, either ANSI/UL 2034, standard for single and multiple station co alarms <br />or UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R313.2.2 3 combination alarms: combination smoke/carbon monoxide alarms shall be <br />permitted if each meets the applicable UL standard. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source <br />- and shall be equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and <br />soffits is not acceptable. <br />13. All doors and windows providing direct access from the home to the pool shall be equipped <br />with an exit alarm complying with UL 2017 that has a minimum sound pressure rating of 85 <br />DBA at 10 feet, and either hardwired or of the plug-in type. The exit alarm shall produce a <br />continuous audible warning when the door or window are opened.. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where <br />installed within 6' if the outside edge of a sink. This would include the receptacle installed for a <br />washing machine. Receptacles outlests shall not be required on a wall directly behind a range <br />or sink to fulfill the requirement for an outlet every 24". The width of the sink or range is not to <br />be included in the spacing of the outlets unless the distance from the sink or range is greater <br />the 12" for straight counter tops and 18" for sinks and ranges installed in corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />LI <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />4- <br />CEILING MOUNTED INCANDESCENT LIGHT FIXTURE <br />WALL MOUNTED INCANDESCENT LIGHT FIXTURE <br />O; <br />RECESSED INCANDESCENT LIGHT FIXTURE <br />4-P.C. <br />LIGHT FIXTURE WITH PULL CHAIN <br />TRACK LIGHT <br />C <br />FLOURESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />rD <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />El <br />PUSHBUTTON SWITCH (OPTIONAL) <br />SD <br />SMOKE DETECTOR <br />CM SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />f a TELEPHONE (OPTIONAL) <br />© TELEVISION (OPTIONAL) <br />2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O THERMOSTAT <br />IMM ELECTRIC METER <br />jow ELECTRIC PANEL <br />DISCONNECT SWITCH <br />SPEAKER (OPTIONAL) <br />ROUGH -IN FOR OPT. CEILING FAN <br />v J <br />CEILING MOUNTED INCANDESCENT LIGHT FIXTURE W/ <br />G J ROUGH -IN FOR OPT. CEILING FAN <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />UNIT 1501 <br />FAIR HOUSING ACT REQUIREMENTS: <br />OPERABLE PARTS OF THE CONTROLS FOR LIGHT SWITCHES, ELECTRICAL <br />OUTLETS, THERMOSTATS AND OTHER ENVIROMENTAL CONTROLS MUST BE <br />LOCATED NO HIGHER THAN 48", AND NO LOWER THAN 15", ABOVE THE FLOOR. <br />IF THE REACH IS OVER AN OBSTRUCTION (FOR EXAMPLE, AN OVERHANGING <br />SHELF) BETWEEN 20 AND 25 INCHES IN DEPTH, THE MAXIMUM HEIGHT IS <br />REDUCED TO 44" FOR FORWARD APPROACH; OR 46" FOR SIDE APPROACH <br />PROVIDED THE OBSTRUCTION (FOR EAXMPLE, A KITCHEN BASE CABINET) IS <br />NOT MORE THAN 24 " IN DEPTH. OBSTRUCTIONS SHOULD NOT EXTEND MORE <br />THAN 25" FROM THE WALL BENEATH A CONTROL. <br />NIT 1399 <br />SMOKE DETECTORS <br />SMOKE DETECTORS SHALL BE IN ALL SLEEPING AREAS, SHALL <br />BE INTERCONNECTED, SHALL BE WITHIN 1' TO 3' OF PEAK, AND <br />SHALL BE 3' FROM THE SUPPLY OR AIR STREAM, AND EQUIPPED <br />WITH BATTERY BACK-UP. ALL SMOKE DETECTORS TO BE <br />ARC -FAULT PROTECTED. <br />NIT 1398 <br />SYMETRICAL <br />ELECTRICAL PLAN <br />SCALE: 3/ 16"=1'-0" <br />N <br />C <br />CD <br />o <br />A <br />U <br />It <br />� <br />_ 0 <br />vi C I— <br />v N <br />ra '0 <br />p <br />EMco <br />0 � CO <br />U N <br />O <br />W C\l <br />0 EO <br />Ln <br />V) <br />00 <br />m l0 U <br />- <br />0) 0 <br />N <br />C <br />ra <br />M <br />c' ` <br />E <br />O 2 <br />�C N 0 <br />= N <br />U <br />s 0.0 00 <br />o a <br />oft <br />CO <br />Ln <br />o <br />rn � <br />0 <br />A0 <br />N °.-BDo: <br />P <br />W <br />_ o <br />M <br />N <br />0 <br />N <br />Z <br />ZW T <br />y MO'0 O <br />LU <br />°° <br />Z <br />LL N <br />o*v N <br />a <br />L� <br />W <br />mJ� <br />W � <br />Z0) 0W <br />C m oN 04 <br />a ¢rn <br />mZ <br />t9 N° 1 r � <br />Z <br />m w <br />r <br />Un W Q o <br />m <br />a� <br />O <br />U <br />To the best of the engineer's knowledge and <br />understanding, the structural plans and <br />specifications comply with the 2007 Florida <br />Building Code, Residential with 2009 revisions <br />signed and sealed for the structural portion of this <br />drawing. <br />O <br />N M <br />r <br />U LO � <br />> N CD <br />Q �(MO <br />,--I <br />Q ' i ru <br />LL <br />ZQ <br />ro <br />� <br />N <br />Z 4-J <br />LULU <br />JL0� <br />L V <br />Q <br />Z <br />Z <br />J <br />oZ <br />wLLO <br />wcoZ IL <br />— E W <br />�o�zoo <br />ZZ Q <br />' <br />Z } OU 2: CL Q <br />_ - w ~ Z <br />U <br />O <br />O 4 o � o <br />UMO�wN <br />t—a-Z <br />z <br />c J <br />� <br />N <br />lfl <br />Ln <br />�✓ <br />rl <br />E <br />O <br />J <br />I..L <br />Q <br />W A OO Q <br />a <br />v0 <br />0a <br />`5 <br />z <br />ULUimOZwOo <br />VQ1'1 <br />ZOwZo <br />2�Zz <br />101— <br />OOJ <br />LU WO OZ <br />U <br />J <br />J <br />o0LU <br />.N Q <br />S2>90- <br />W�O2OQ <br />Uj <br />�� <br />U <br />Q0o <br />a � LL n <br />Q <br />Lj <br />Ii <br />-J W <br />Yw <br />a¢ <br />z <br />M <br />U <br />W <br />� <br />g J <br />Z <br />0 <br />a W <br />SCALE <br />AS NOTED <br />PLOT DATE : 01 / 21 / 2011 <br />VERSION NO. <br />1000 <br />JOB NO: 11-0055-60 <br />SHEET NO. <br />8 <br />