ILIE00 IIVG- <br />TILLIT TESTING A ENGINEERING COMPANY <br />WAT TF.R A. TTLLTT JR., P.E. - tiller aElsnm <br />ILPR a\o-Nbl47 <br />4a <br />PI. C,t.Idueuxe NC. 001167I9 <br />PRODUCT EVALUATIOF_PORT <br />REPORT NO.: 20-0728.01 <br />DATE: July 28, 2020 <br />PRODUCT'CATEGORY: Shutters <br />PRODUCT SUBCATEGORY: Storm Panels <br />PRODUCT NAME: 20 GAGE GALVANIZED ;STEEL STORM PANEL <br />MANUFACTURER: Global Protection Products LLC. <br />4800 S.W. 51 Street <br />Davie, Florida33314 <br />1 PURPOSE OF EVALUATION; <br />This is a Product Evaluation Report issued by Walter A. Tillit, Jr., P.E. (System <br />ID # 1906) to the Glabel Protection Products, LLC, Rule Chapter No. <br />61G20-3, Method 1 D of the Florida Department of Business and <br />Professional Regulation. <br />This product is being issued an Evaluation Report as described herein, and has <br />been verified for compliance in accordance with the 2020 Seventh Edition of the <br />Florida Building Code, and to verify that the product is for the purpose Intended <br />at least equivalent to that required by the Code. <br />This Product Evaluation Report shall be subject to review and revision in case of <br />a Building Code change that may affect Its limitations and conditions <br />2 EVIDENCE SUBMITTED` <br />2.1. PRODUCT EVALUATION DOCU_MENT4P,E.DJ; <br />Drawing No. 20-176, titled "20 (SAGE GALVANIZED STEEL STORM PANEL", <br />sheets 1 thru26of 26 prepared by Tilteco, Inc.; signed and sealed by Walter A. <br />Tillit, Jr., P.E.; dated 07128/2020, This drawing is an integral partiifll�f�s <br />Evaluation Report. ```tIk�A <br />f� - • Z NO, 44167 <br />y,��FSSt OA.10 P•.0 <br />6355 N.W. 36th Street, Suite 305, Miami, Florida 33166 - Phone: (305) 871-1530 �P6Trs,,6i$, <br />PRODUCT F.V r.;UATION AEPOlt',E N(I III-ITT28.01 2 <br />2.2. TEST REPENTS; <br />Largemissile <br />m sslle Impactandfatigue load tests were performed under Protocols TAS <br />201, 203 as per section 1626 of the Florida Building Code. Uniform static loads <br />as per TAS 202 Protocol. Test reports prepared by Hurricane Engineering & <br />Testing, inc., Reports # 96-569 dated 08/09/1996 #96-570 dated 09/1811996 <br />#96-T30 dated 09720/1996, all three signed and sealed by Hector M. Medina, <br />P.E., Fenestration Testing Laboratory, Inc, reports # 2032 dated 04/16/1998 and <br /># 2126 dated 10/0611998 witnessed by Gilbert Diamond, III and Report No. <br />0219.01-09, dated March 4, 2009, signed and sealed by Edmundo Largaespada, <br />P.E. and Henry Hattem, P.E. <br />Tensile test report No. 9CM-197 by QC Metallurgical, Inc„ dated March 13, 2009, <br />signed and sealed by Frank Grate, P.E. <br />2,3. STRUCTURAL,ENGINEERINGCALCULATIONS: <br />On 20 Gage Galvanized Steel Storm Panel for maximum panel length vs. design <br />wind load, as well as maximum anchor Spacing vs. design wind load and panel <br />length based on rational and comparative analysis, and in accordance with <br />section 1616 of the Florida Building Code. Calculations prepared by Tilteco, Inc., <br />dated 11/03/08 and 03/12/15, signed and sealed by Walter A. Tillit, Jr., RE, <br />S MISSILE IMPACT RESISTANCE: <br />Large missile Impact under section 1626 of the Florida Building Cads, as per <br />TAS 201 Protocol. <br />4.1M1f ND LOADS RESISTANCE: <br />20 Gage Galvanized Steel Storm Panel has been verified to sustain wind <br />pressures. Maximum panel length shall be as indicated on sheets 8, 10, 14, 15, <br />16, % 25 and 26 of 26 of Product Evaluation Document (P.E.D.), drawing No. <br />20-176. Maximum Anchor Spacing shall be as Indicated on sheets 8 9 10 11 <br />P g <br />14, 15, 17, 18, 19,20 25 and 26 of 26, of Product Evaluation Document (P.E.D.), <br />drawing No. 20-176. <br />5. INSTALLATION: <br />Installation shall be performed strictly in accordance with details indicated on <br />sheets 3 thru 7, 10 thru 20, 23, 24 and 26 of 26, of Product Evaluation Document <br />(P.E.D.), drawing No. 20-176. Minimum separation to glass shall be as <br />indicated on sheets 8, 14, 16, 25 and 26 of 26, of Product Evaluation Document <br />(P.E.D.), drawing No. 20-176. <br />iA Iu1111AIINr1�NFy Ai <br />NLN AA, <br />\tit ��L� ..., �/f✓YI,/ <br />s6 <br />7 STATE OF s <br />ih FtOR•- M <br />SJONAO� vs <br />FlAllfllll"Hk51N <br />GENERAL' 8.3) IN CASE THAT PRECAST SMW. OR PRECAST CONCRETE PANELS, STUCCO OR WOOD BOARDS BE FOUND ON THE <br />(SLID-- 0 -- DUONG WAL ANCHORS SHALL BE LONG ENOUGH TO REACH THE MAIN STRUCTURE BEHIND SUCH PANELS. <br />I. STORM PANEL SHOWN ON THIS PRODUCT EVALUATION DOCUMENT (P.E.D.) RAS BEEN VERIFIED FOR COMPLIANCE IN ANCHORAGE SHALL BE AS MENTIONED IN 13A) AND IN 8.2). <br />ACCORDANCE WITH THE 2020 (70, EDITON) OF THE FLORIDA BUILDING CODE (C) TO 02MM WM NWN SPECIFIC Da,,,4M 055 IMMI•; <br />WIND LOADS WALL DETERMINED PER SECTION OF THE ABOVE - 1/40 TAPCON ANCHORS, AS MANUFACTURED BY I.T.W. BUIICOL INC. <br />CODE, <br />FOR UI _ #14-10 PANELMATE FEMALE D AND PANEU ATF PLUS ANCHORS, AS MANUFACTURED BY ELCO CONSTRUCTION PRODUCTS, <br />FOR A WIND SPEED t6 RI WHERE 714 <br />THESE SHUTTERS WILL BE <br />0, THE ILL BE IN AND <br />FOR A ORECTgNN.TiY EDGIER Kdo-0.65. USING ASCE 7-15 ARID SWJ.L NOT EXCEED TINE. MAXIMUM (RICO.) - 1/4'0 TAG SCREWS PER N.O.S. <br />CTOR Kd USING ASICTTOFI 6AMAXIMUM <br />- <br />DESIGN PRESSURE RATINGS. INDICATED ON SHEETS 7 THR) 12, 14, 15. 16, 19 At 20, - 7/160 x 5/8` WOOD BUSHING AS DISTRIBUTED BY ALL PIRA SCREW, BOLT & SPECIALTY CO. <br />S ORDER FIRST <br />PER ASCE 7-16 C. 1) MINIMUM THREADED PENETRATION INTO WOOD OF TAPCON ANCHDRS, SNAIL BE 1 1/2' AND 2' FOR ELCO PMELMIiTE PLUS <br />VERIFY THE ABOVE COHESION, ULTIMATE DESIGN LINO LOADS THEM <br />SHALL RE FIRST REDUCED1 TO RSA. DESIGN WINO LOADA BY <br />MULTIPLYING THEM DY 0.7 ESN ORDER TO <br />AND PAHEIAIMA FEMALE ID. <br />IN <br />COMPARE THESE W/ MAX.W(A5.0} DESIGN PRESSURE RATIOS INDICATED ON SHEETS 7 THRU t?, ia, 75, 18, 19 & 20. <br />IN ORDER TO VERIFY THAT ANCOORS ON THIS P.E.D. AS TESTED WERE NOT OVER STRESSED, A 33X INCREASE IN ALLOWABLE C.2) MINIMUM THREADED PENETRATION OF LAG SCREW. INTO THE W000 FRAME UNIT SHALL BE 1 1/2'. NO THREADED <br />PENETRATION INTO STUCCO SHALL BE CONSIDERED AS PART OF THE RMSNT THREADED PENETRATION. <br />STRESS FOR WIND LOADS WAS jlLjt , USED IN THEIR ANALYSIS. FASTENERS SPACING TO WOOD HAS BEEN DETERMINED W <br />ACCORDANCE WITH AIDS. 2018. C.3) MINIMUM EOOE DISTANCE OF LAG SCREWS, INTO WOOD SHALL BE AS INDICATED IN TWS DRAWING <br />STORM PANEL'S ADEOUALY FOR IMPACT AND 'WIND RESISTANCE HAS BEEN VERIFIED IN ACCORDANCE WITH SECTION 1628 OF <br />THE ABOVE MENTIONED CODE AS PER HURRICANE ENGINEERING & TESTING INC. REPORTS 96-569. 96-570 & 96-TM AND C.4) MINIMUM PENETRATION OF WOOD BUSHING SHALL BE 5/8'. 1/4- 0-20 SCREWS USED SHAM. BE 1 1/2- LONG MINIMUM <br />FENESTRATION TESTING LAB. WNC REPORTS #2032 & #2126 . AS PROTOCOLS TAS-201, TAS-202 AND TAS-203. SHOULD STUCCO OUST, AND 1' MINIMUM FOR WALLS WITH NO STUCCO. <br />AS WELL AMENDAR C'AN TEST EAR OF SOUTH FLORIDA REPORT )0218.07-09, AS PER TAS 201, TAS 202 AND <br />TAS 203 STANDARDS. C.5) IN CASE THEY PRECAST STONE, OR PRECAST CONCRETE PANELS, STUCCO OR WOW BOARDS IA FOUND ON THE EXISTING <br />NLW EXTRA WAIL„ MOORS SHALL BE LONG ENOUGH TO .REACH THE MAIN STRUCTURE SEHND SUCH PANELS, <br />2. ALL ALUMINOM ZXTRUSDNS TO DE 6063-TES ALOE AM TEMPER. (tNBSSs OTHERWISE NOTED). SEE SHEET 2, ANCHORAGE SYALi, BE AS MENFINNED IN CA), C.2) & C4) <br />3. ALL ALUMINUM SHEET METAL USED AT CLOSURES SHAY HAVE 3105-1,114 ALLOY. (0) ANCHORS SMLL BE INSTALLED FOLLOWING ALL OF THE. RECOMMENDATIONS AND SPEOVFFGATTONS OF THE ANCHOR'S MANUFACTURER. <br />a. ALL STEEL SHEET META. PANELS SNAIL HAVE STRUCTURAL STEEL ASTM A-B93 GRADE 50 MINIMUM. G-60 <br />GALVANIZED STEEL DESIGNATOR W/FY- SB.s bl (AFTER RETIED). A 8. PANELS MAY M BE INSTALLED HORIZONTALLY FOLLOWING INSTAL{ATWN DETAILS SHOWNON SECTION 3 THROUGH 10 (SHEETS 4 <br />ROLLED). <br />THROUGH 6) EXCEPT THAT WADERS (3) SHALL NOT BE USED. <br />®& <br />S. ALL SCREWS TO BE STAINLESS STEEL 304 OR 316 AIS1 SERIES OR CORROSION RESISTANT COATED CARBON STEEL AS PER <br />DIN 50018 W/ 50 W YIELD STRENGTH AND 90 Inn TENS" STRENGTH & SHALL COMPLY W/ FLORIDA BIDDING CODE 9. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR To VERIFY THE SOUNDNESS OF THE STRUCTURE Wt$$ SHVITER S TO � <br />SECTION 241 3.3.4. ATTACHED TO INSURE PROPER ANCHORAGE THE SHUTTER SHALL ONLY BE ATTACHED TO CONCRETE, BLOCK OR WOW FRAME <br />BLLLDINGS. <br />S. BOLTS TO BE AST" A-307 GALVANRED STEEL, OR ASI 304 SERIES STAINLESS STEE" WITH 36 Kai MINIMUM YIELD <br />STRENOM. 10. EACH REGULAR STORM PANEL WITH LENGTHS OVER 8'-B THROUGH 12'-4-, AS PER SECTIONS 6, B. 9 & 10 AND ALTDOWTVE'S 6W, <br />7. ANCHORS TO WALL. SMALL RE AS FOLLOWS: 8W & IOW ON SHEETS 5, 6 & 12 RESPECTIVELY, SHALL HAVE A LEGIBLE AND READLY VISIBLE MARKING INSTRUCTING OWNER OR <br />TENANT TO SECURE PANELS WITH APPUCMS E REINFORCEMENT DURING PERIODS OF HURRICANE WARNING. <br />(A) 11. THE INSTALLATION CONTRACTOR IS 'TO SEAL/CAULK ALL SHUTTER COMPONENT EDGES WHICH REMAIN IN CONTINUOUS CONTACT WITH <br />- i/4"tl TAPtAN' ANCHORS AS MANUFACTURED BY LT.W, EUUXX. INC. (Min. rC-3192 p.s.i.) THE BUILDING TO PREVENT WINO/RNN INTRUSION, <br />- I/{' tl A J/r CALK -IN ANCHORS, AS MANUFACTURED BY DEWA.T INC (MIN, 1*g 300, p-Q <br />- 1/4'tl „ 3/4' SOUO-SET ANCHORS, AS DISMOUiEO BY ALL POINT SCREW, BOLT & SPECIALTY CO. 12. STORM PANEL INSTALLATION SHALL COMPLY WITH SPECS INDICATED IN THIS DRAWING PLUS ANY BUILDING AND ZONNNO r*CU ATKONS <br />(Min. rc-3000 P.4-L) PROVIDED Ifr THE JUMSOCBON WHERE PERMIT 15 APPLIED TO. <br />- /14-10 PMNELMATE FEMALE D & PAWUAATE PLUS ANCHORS. AS MANUFACTURED BY ELCO CONSTRUCTION PRODUCTS. <br />(MIN. t'C-3350 p,..Q 13. (C ) CT EVALUATION (P.E.D.) THIS ENGINEER <br />I M AND DOES NOT PROVIDE INFORMATION <br />F1�SAPRODI <br />SITE SPECIFIC SITEImo <br />- 1/4.0 Cr TAP -CRAP ANCHORS, AS MANUFACTURED BY TRU-FAST CORPORATION (T'c-3600 Pa.L) <br />XI) MINIMUM EMBEDMENT OF TAPCON ANCHORS INTO POURED CONCRETE SHALL BE 1 3/4': 2' FOR PANEMATE FEMALE W CONTRACTOR TO RE RESPONSIBLE FOR THE SELECTION. PURCHASE AND INSTALLATION INCLUDING LIFE SAFETY OF THIS PRODUCT <br />BASED ON THIS P.E.D. PROVIpED HE/SHE DOES NOT DEVIATE FROM THE CONDITIONS DETAILED ON THIS DOCIAENT. <br />,a NO PAWMALTE PLUS AND 1 1/4- FOR CF TAP --MP ANCHORS, CONSTRUCTION SAFETY AT SITE S THE CONTRACTOR'S RESPONSSI ITY. <br />A2) CALK-N & SOUD-SET ANCHORS SOW. BE EMBEDDED 7/6• INTO THE POURED CONCRETE. NO E14BEGMEW INTO (c) THIS PRODUCT EVALUATION DOCUMENT WILL BE CONSIDERED INVALID IF MODIFIED. <br />STUCCO SMALL BE PERMITTED. 1/4" ­20 SCREWS USED STALL BE 1 1/2" LONG MINIMUM SHOULD STUCCO OUST. <br />No I" MINIMUMFOR WADS WON NO STUCCO. AND MAY BE HEADED SCREWS OR ALL THREADED SCREWS WED HEAD. (d) SITE SPECIFIC PR(MF„CTS SHALL BE PREPARED BY A FLORIDA REGISTERED ENGINEER OR ARCHITECT WHICH WILL BECOME THE <br />BUT WITH WING NUTS. ENQII ER OF RECORD (E.O,R) FOR THE PROJECT AND WHO WILL BE RESPONSIBLE FOR THE <br />PROPER USE OF THE P.E.D. ENGINEER OF RECORD. ACTING AS A DELEGATED ENGINEER TO THE <br />A-3)IN CASE THAT PRECAST STONE, PRECAST CONCRETE PANEM PAVERS, STUCCO OR WOOD BOARDS BE FOUND ON THE P.E.O. ENGINEER, SHALL SUBMIT i0 1T+S LATTER THE SITE SPECIFIC ORAWIM FOR RENEW. <br />DISTINC WALL OR FLOOR ANCHORS SHALL BE LORD ENOUGH TO REACH THE MAIN STRUCTURE BEHIND SUCH <br />PANELS. AWJ071GE SHALL BE AS MENTIONED IN Am) AND IN A.2). (e) THIS P.E.D. SHALL BEAR THE DATE AND MORAL SEAL AND SIGNATURE OF THE PROFESSIONAL <br />ENGINEER OF RECORD THAT PREPARED IT. <br />(B) t0 EXRi7NG tS1dPX€TE rxx WALL AM <br />,CAD• 14. SHUTTER MANUFACTURER'S LABEL SHALL RE LOCATED ON A READILY VISIBLE LOCATION AT STORM <br />1/4• tl TALON ANCHORS AS MANUFACTURED BT L T. W. SURLDEX, INC. <br />PANEL SHUTTER N ACCORDANCE WITH SECTION 1J09.9.3 OF FLORIDA BALDING CODE 01� LABEL <br />I/4' ♦ 7/6- CALK -IN ANCHORS, AS MANUFACTURED BY OEWALT INC (MIN. f cam=}5W Pa.iJ SFMTL BE PLACED FOR EVERY OPENING, LABELING TO COMPLY WITH SECTION T70893 OF THE <br />1/46 X 3/4. SOUL -SET ANCHORS. AS DISTRIBUTED BY ALL POINT SCREW, BOLT e, SPECIALTY Co. FLORIDA BUILDING CODE, <br />(MN. Fc-1500 P.Sa.) <br />- 014-10 PANE WTE PEMA11 ID AND PANELMATE PLUS ANCHM. AS MANUFACTURED BY ELCO CONSTRUCTION THS DRAWING SHALL L ONLY 9E USED 70 <br />PRODUCTS (MIN. e-207T P.I,N.) N1+tki HhNNTryH �TA>AL PERMITS IN THE STATE OF FL©WON <br />- 1/4• 0 OF TAP ANCHORS., MANUFACTURED BY A• l'11 AH <br />-GRIP AS TRV-'FAST CORPORATION aM•tti�•R <br />A <br />•'�,, ••.•, <br />• .BUILDING CODE HI h Yetec.. HuMcone Zor1e <br />0.1) MINIMUM EMBEDMENT OF TAPCON ANCHORS, ELCO PANELAUTES AND CF TAP-GFBP ANCHOR. INTO THEFLORIDAE� <br />BLOCK UNIT SHALL BE 1 1/4'. °2°30 TMT�• 01Q. <br />1L• <br />20 GAGE GALVANIZED STEEL STORM PANEL tln,EEN Err. <br />i <br />8.2) CALK-N & SOLID -SET ANCHORS SHAD. BE EMBEDDED 7/a' INTO THE CONCRETE 87.DCK UNIT. NO EMEGONo. 4 167 Z <br />INTO STUCCO SWYL. BE PERMITTED. 1/4• F20 SCREWS USED sHA, BE 1 1/2" LORD MINIMUM SNOU GLOBAL PROTECTION PRODUCTS, I.L.C. C1 DAILSetD <br />EXIST. MD I" MINIMUM FOR WAILS WITH NO STUCCO, q <br />F' I L E C 0,... <br />�9 STAT OF .III S.M. a, amEfT <br />IMAT ENGINEEWO c6MPANY WE. R <br />'! 't' '• OR ON aw G. M.. eon tR"M, 4AmdA n Aw PKNE, tle+%GT-T5,5, FAx: t6a,)HIn9-am 20-176 <br />ar ., w"" : mu. -vam ,cMa aN-,.> <br />Rs <br />%�,. ,a ..4 Aw .. wr.NA R" DAIMON HP <br />y�iip�/QNA rG sEAyswNATuIDAre a <br />NN WALTOe mizx�s�`ii �, I rm re <br />INTO EXISTING <br />INSTALLATION DETAILS <br />POURED <br />FOR REQ,U AR PANELS <br />CONCRETE OR CONCRETE <br />(3) <br />BLOCK STRUCTURES(M SCHEDULE D <br />COMPETE ANCHORS <br />(SEE SCHCOULE GNPOURM <br />MYE, 6 iTpttO{MFN 9) <br />GONLIE.W AIiCYKMLS <br />SHEETS a Twwo ScHEMU N <br />9) G. <br />CONCRETE ANCHORS <br />! �ifINLLWptl <br />SHEZTS a nwtxwH e} <br />CONCRETE�/4�JOUSTING f�� <br />W7 i <br />'ODNCR£i <br />EXSTRIO POURED <br />II£WNiE6.l%4" <br />j I <br />i9 <br />orl <br />�1. <br />/�2C. � <br />1 4- <br />,14,`.y <br />a <br />ii4 <br />E77OSTAIG POURED ED CONCRETE <br />REQUIRED. <br />1 2 6 <br />I <br />i <br />E <br />EoxmnmfP0E1RE0 ! <br />t <br />EACONCRETE <br />� <br />� <br />� <br />~ �`ti + 1 <br />T ���I j���i:• 14 <br />OFAY <br />i <br />1 <br />'`'� <br />I BEZ %aIFOIAC <br />TO NABS. 1 <br />I <br />�,�,i <br />SRq G E14RF BRIO I <br />Wr UC <br />Sam I <br />-gnWl lrn TWM6 <br />tD Lush. <br />1 4x�,L <br />I <br />SEE atN@46. <br />Ew eIMAT a <br />i,-•_.,, ,at <br />A�� 1 <br />ETa3APC <br />R F'4 <br />FNRotNNB i <br />m a <br />"MW aei I <br />I <br />I <br />�..I`•',\ , "�\ -r! <br />N6RY 6"RMGe NNA\ <br />ETNRPOURDa E` <br />; <br />NUT • <br />F"Iw�o°c <br />N'"-' i -TC12IWRROtfY YOSOR <br />"OR <br />C <br />CONCRETE <br />'UQR <br />.6 <br />%9RTE (, <br />BOCK <br />WOUIREO. /°,• <br />EVERY sm e <br />i 12 1/r Oc e <br />1 <br />9 <br />�;,, - <br />OONCRk.TE BLOCK ! `' <br />CONCRETE BLOCK I. .q __...... ........_ <br />REQUIRED ^+ <br />t , <br />REflwRED. �{ 11Y <br />... <br />CONCRETE ANCHORS F: <br />(� <br />_'C"i O <br />R EOUMRRD. <br />00NCRElE ANRgRS <br />I — iTIL CD+oTIaPO <br />•`-E-D= <br />CONMAEM ANC 1 4 <br />/6�"0M <br />' SIT s �' { .-. 4 0 <br />BYL • Q0. C <br />,OIGCIIND M/ SHAD <br />Psl�r rEve.. On 11aA <br />(5FY SGiWIE OR`"`� <br />(9E{ 9piEWE QN-'- +\ tsM. <br />R TILn <br />(;FE 5CMdAE DN'm R+• Oa,d. eu.. OEM' 9.{ <br />SHEETS a THROUGH 9) <br />SlEFTS 8 THROWN 9) <br />SHEETS 6 MROUGH 9) <br />SHEER 6 THROA. 9)WALL <br />crP..w <br />SCALE 3A-1- <br />3ti,ti[tS.3,.AE!(Xii.AE>oi <br />/{�ELING�`R' ���)yT���E/� <br />SCALE 3/8-1' <br />p���� <br />dt7[3fT6i. - -PUNT <br />STANCE 3!e-, <br />�E,NEe ,E�• T �1Nr����L•��y <br />i4%6L LlI LI. CNA'r4_'�,E.. wlv6l.LYAi <br />5CAE 3/8-1 <br />I <br />1 <br />C.D. - EDGE DISTANCE <br />(SEE SCHEDULE ON <br />'IINTR Mn 04 <br />ro <br />i <br />SHEETS 6 & 9) <br />51AIs <br />i <br />1 $ <br />I <br />� <br />C. <br />Lw.e. <br />a i <br />Noo <br />FYyiy4 <br />TOP & BOTTOM MOUNTINGS CAN BE <br />COMBINED <br />ILT-11— <br />N+'ANA�EIi A' .. <br />IN INSYAU.At)ON. ANY WAY TO SUIT ANY <br />w . <br />3/4 <br />$ _ _ <br />FIERIER BUILDING LADE M h YetQct Nu cone ZonG). <br />e�9ATEPOUR,LD, <br />L--'----ED—_ - <br />' <br />> <br />C• I = <br />OSO$B TaiEo, INC.rPREoumED. . <br />20 GAGE GALVANIZED STEEL STORM PANEL or., <br />�E6i1+RaOatON <br />DRIWT <br />y r{c' DpipY, '• - <br />STjM/I026 <br />IL Ei►O rrEe. GLOBAL PROTECTION PRODUCT'S, U.C. CAM. <br />4600 S.W, 51 STREET <br />.__>..___ <br />?, �fn•'.....`.. <br />it,A As j <br />e, LgUNMROD ANY DAME, R =14 <br />3f6-1' <br />NAB E <br />Ns.1 a". $ A,W N. XNW PIKNE': (F6B}GI9-Ja4a FAR, (96a)VIII-4 a zD-176 <br />Er-,R. , �— <br />SCALE <br />.E <br />«DTI M1AiNAs ,W w: r aw DRARNNC Nn <br />EATER A. law N,N., P.E 4a er-,,, _ <br />BAIMA 467 9N[CT 4 DF 78 <br />PRODUCT VVALVATTON REPORT NO. 20-0728.01 <br />S MATERIAL CHARACTERISTICS AI11p SPEC1FiCAT10NS: <br />Shall be strictly in accordance with General Notes and Components indicated on <br />sheet 1, 2 and 22 of 26, of Product Evaluation Document (P.E.D.), drawing <br />No.20-176. Anchor specifications shall be as indicated on sheets 1, 7 and 21 of <br />26, of Product Evaluation Document (P,E.D.), drawing No. 20-175, <br />7 LIMITATIONS AND CONDITIONS OF USE,- <br />7.1. Shall be strictly in compliance with General Notes No. 1, 8 thru 14, indicated <br />on sheet 1 of 26 s well <br />a t as General Notes # 1 thru 4 and 11 thru 16, indicated <br />on sheet 21 of26 of Product Evaluation Document (P.E.D.), drawing No. 20.176 <br />prepared by Tilteco, Inc. and signed and sealed by Walter A. Tdlit, Jr„ P,E. <br />7.2. Product may be installed within HIGH VELOCITY HURRICANE ZONES as <br />defined on section 1620.2 of the Florida Building Code. <br />7.3. Product shall only be installed into poured concrete, concrete block, and <br />wood frame structures. <br />Product Evaluation Report prepared by Walter A. Tillit, Jr., P.E. (Florida License <br />No. 44167 President of Tilteco IncCA-00 7 ), , (Florida( O6 19), <br />Nl EN <br />44P ll++ t�C 2J <br />a �•,.• <br />Z _ s <br />M^, 44167 <br />_ s <br />?."`'•'7�7.,�`5a.n �. cTAT; nF ::_cr r <br />VVAT1LL <br />DA TILTECO ADMON RECORDS I P. E. REPORT-20 k GLOBAL PROTECTION PRODUCTS, LLC 1.20 GAGE <br />GALVANIZED STEEL STORM PANF14 DRWG 420,176 %REPORT 7r 2MT28.01 <br />2. • '�'N• ! ED IYP. <br />^T EDGE <br />1-STAB_ A <br />1 I L I EC0 Inac. <br />TILLIT TESTING S ENGINEERING COMPANY <br />WALTERA. TILLIT, a, P.E, tltew@ael.conPR7F lit,N44167UQ( <br />}LC.A, LT—Na 9006719 <br />REPORT NO,: 20-0727.02 <br />DATE: July 27, 2020 <br />PRODUCT CATEGORY: Shutters <br />PRODUCT SUB -CATEGORY: Storm Panels <br />PRODUCT NAME: 24 GAGE GALVANIZED STEEL STORM <br />PANEL <br />MANUFACTURER: Global Protection Products LLC <br />4800 S.W. 51 Street <br />Davie, Florida 33314 <br />1. PURPOSE OF EVALU TA ION: <br />This is Product Evaluation Repo issued by Walter A. Tillit, Jr., P.E. (System <br />iD # 1906) to the Global Protection Products, LLC, Rule Chapter No. <br />61 G20-3, Method 1D of the Florida Department of Busyness and <br />Professional Regulation. <br />This product Is being Issued an Evaluation Report as described herein, and has <br />been verified for compliance in accordance with the 2020 Seventh Edition of the <br />Florida Building Code, and to verify that the product is for the purpose intended <br />at least equivalent to that required by the Code. <br />This Product Evaluation Report shall be subject to review and revision in case of <br />a Building Code change that may affect its limitations and conditions <br />2. EVIDENCE SUBMITTED: <br />2.1. PRODUCT EVALUATION DOCUMENT (P E O 1 <br />Drawing No. 20-175, titled '24 GAGE GALVANIZED STEEL STORM PANEL', <br />Sheets 1 thru 18 of 18 prepared by Tilteco, Inc.; signed and sealed by Walter A. <br />Tillit, Jr., P.E,; dated 0712712020. This drawing is an inte (�T1D t rVi116 <br />Evaluation Report. �. R• <br />0`1 GEN,9, <br />167 <br />T— = <br />c STATE OF r <br />IV <br />6355 N.W. 36th Street, Suite 305, Miami, Florida 33166 -Pli (305) 871-1�13�#A.31T"AtiS 1-1531 <br />COMPONENTS FOR REGULAR tic LIFE SAFETY STORM PANELS <br />(ALE 1/2-1") <br />5,196' {TOTAL <br />msoo* (EPTECTNE <br />0.036' MIN. THICK <br />GALVANIZED STEEL <br />ASTN A-03 <br />DRAPE 50 MINIMUM <br />G-so GALv. <br />Du" <br />T =1111 t PANEL <br />PANELS EMI} LIP <br />W/ HaWED EA0['. ti....; <br />50.08- <br />\' <br />! w ISOMETRIC VIEW DETAIL -A <br />ROUNDED CORNER O ENDS. OF PANEL'S <br />ENO UP W/ HEMMED EDGE. <br />(N.TS) <br />® 2"X7"X1/4" <br />ALUMINUM ANGLE <br />0.344 <br />7.407'Y.063' .625' <br />__J <br />B57' <br />L - Nth .EIS' <br />KEY HOLE WASHER <br />.OBI` <br />0.N)3fi• (MIA) --I �a94' <br />GALVAN¢TS STEEL <br />.375'YtlM .6750 <br />KE <br />O63' NICKEL <br />.125-•- .iB75' �P^"�' WING NUT <br />ALTMMTN4LY� NUT W/OUT <br />WROL• WASHER W/ QW04AL <br />7/6'ex3/32' (SWUM <br />STEEL OR NICKEL PLATED STEW, <br />MEO_,,;y- '` .1 <br />DETAIL � / <br />r - <br />i <br />.093' i <br />2,125, 2060- <br />r17kn,, At Y30' i/ , <br />1, . <br />Q END STORM PANEL <br />1 41 .125' <br />1.1251 '1•;.S.. SM METED S.S. SEW RNE(rD � Fr��r'...� <br />r- TO ANGLE O 7D ANfYE G I <br />12 I{2' Mc 12 ,/2. O.c <br />_-_ <br />1.500" iS00' <br />OET�AIL , .9 t' L 125 k EFN. 1 j <br />{ C <br />t j <br />GJ <br />U 'h" HEADER UJ "U" HLOER (_!9 ANGLE (F,� ANGLE WITH STUD @ ANGLE WITH <br />ORSTRD POURED i <br />BLOCK <br />REQUIRED. <br />9) <br />REVERSE STUD <br />� 7yp i0P EDGE 374 .OES; ow - M <br />..-.350• 125f 4'a-20. 3W SUM <br />)-- .a7O".856' i » .6t0- l,„^)- .,3& E 0 12 1/2'EVIR) 0 <br />' ANGLE G 1RI T/2' TO <br />91" i i1:662" 1.671 <br />•--R.7E5" ..:off• ...4 L_ �.._�_� <br />2.000'- ' ' TTP.) <br />"F" TRACK jyf(= R 3,/$" "F' TRACK Q) ME PLATED <br />.344"0 4T41ATilENMN,AA VATH STUD <br />�� � A Tit. . <br />�t ND. 44167 <br />,315" <br />T``" # � *' ;, •# ' * S FLORIDA BUILDING CODE (High VelNtGity HUMCOM Zone <br />isDuo <br />KEY HOLE/.40 <br />� STATE QP \ omp Two 20 GAGE GALYARIZED STEEL STORM PANELFR <br />AT PANEL ry' P %0' " T eT A PROTECTION PRODUCTS, LLC. e' DAE <br />AAIR]JA4A4TE f <br />i <br />-•-_---� <br />CONCRETE <br />REDNR®. Bl t..,..f r <br />4j2• <br />AP-6Y6P <br />CONCRETE ANCHORS <br />'`�- . <br />T} ES ON <br />ISEE � <br />SHEEN, a ?iRrnIGH 9) <br />SCALE 3/0 <br />%' T)PELNINGIXISRND * <br />NEW i" WIDE x VARES x 1/8' <br />STUCCO/ <br />THICK ALUM TUBE OR T" x� <br />-V'1 <br />EXISTNNO <br />--- WOOD BAND <br />P.T. WOOD PLATE SPACER <br />t <br />G NEW I- WIDE x VARIES x 1/a• <br />- AU M, TUBE OR i- x VARIES <br />..T. W006 PlA7E SPACER <br />1 BEHIND TRI6c <br />r. <br />}( <br />CONCRETE R5 <br />I <br />--'� <br />(SEE SCHEDULE OR ,. <br />&1EE1, ! TTINOIIGH 9)� <br />; <br />R COOL <br />1 + K <br />C,,. <br />EXISTING d <br />,N1C <br />9WCpl tkT1OI); <br />b <br />( EeGa t tf2' Min. <br />cow <br />ETE SLOGS f <br />AMi FtWTA tROHT ld <br />dl CINDER TSPH <br />REOU TXW <br />ate. <br />SEC OTI N X-X <br />DETAIL EQ8 SPPAM <br />0710114 TRACKS AD <br />SCALE 3/8-1- <br />REQUIRED AT TOP OR TO M=MM BANDS <br />F. & U DO CLOSIM DETAINS FOR INUAU.ATiON IN POURED CQFIOiEiE, <br />NK STRUCTURES QQN= i = OR HOOD <br />YAUD FOR TENDRIL UFE SAfEIY AND E-Z8" STORM PM SYSTEM <br />...4•. a�Rem ras') XaJ <br />MO <br />, <br />G a iR• Is �_7,,O� <br />1 1 tt a"°AwtipE � I Ra'a <br />w 1:ti:°,NaE1 n ASP,' <br />r. <br />I 2 1/Y SCALE 3/TS-1 <br />I 4A»oni i � I -i �• Eoti-s+IP�m�n. , uii O <br />N I A wmM tl �ae ' aV.' '•. <br />I , <br />i ,e ,n64 <br />1 Y � aEas <br />0 <br />I f i iiW�4P'` Aalnm <br />CAS <br />� II 1wPE" <br />i SCALEa/{6�Ji CASE D (eLAN) <br />SCALE 3/18-1- <br />T- /4� i ^"" -'; ""'- <br />1'1G,e-+ \'�,, � Ze'�.. �\''s4 -•'\.'\^`'. � R�wE�,0an0, ��4..tai (ami <br />U. Qui.,`y9IiMA4UlITJ161 <br />11 -1 <br />SCALE 3/B-t' <br />E.D. " EDGE DISTANCE: <br />(SEE SCHOULE ON j r"iJfi0Y7 S 1,ASE F �pLANl <br />SHEETS 6 & 9) - SCALE 3/iNt' <br />TOP & BOTTOM MOUNTINGS CAN BE <br />COMBINED IN ANY WAY TO SUIT ANY EASE E (PLANS <br />INSTALLATION. -. SCALE 3/16-t' <br />PRODUCT EVAIXATION REPORT NO 20-0717 02 2 <br />23. TEST Rli <br />Large missile impact load tests were performed under SSTD 12.99 standard as <br />per section 1609.1.2 of the Florida Building Code. Uniform static loads as per <br />Section 1709.8.3 r A - , per ASTM E 330. Test reports prepared by American Testing <br />Lab of South Florida, Report # 0814.01-01 dated 03111/02,witnessed by William <br />R. Mehner, P.E., Boriz Moroz, P.E, and Henry Hattem, P.E. and Report No. <br />0219.01-09, dated February 26, 2009, signed and seated by Edmundo <br />Largaespada, P.E. and Henry Hattem, P.E. Large missile impact and cyclic <br />loadings per Protocols TAS 201 & 203 as per section 1609.1.2 of the Florida <br />Building Code. Test Report prepared by American Testing Lab of South Florida, <br />Report No. 1123,01-10, dated November 23, 2010, signed and sealed by Julio E. <br />Gonzalez, P.E. <br />Tensile test report No. 9CM-1 po 98 by QC Metallurgical, Inc., dated March 13.2009, <br />signed and sealed by Frank Grate, P.E, as per ASTM E-8 and Tensile Test as <br />per QC Metallurgical Report No. 1 OKM-1318, dated December 1, 2010 signed <br />and sealed by Jerry Jaciofano, P.E. as per ASTM E-8. <br />2.3. STRUCTURAL ENGINEERING CALCULATIONS: <br />On 24 Gage galvanized Steel Stoma Panel for maximum panel length vs, design <br />wind load, as well as maximum anchor spacing vs. design wind bad and panel <br />length based on rational and comparative analysis, and in -accordance with <br />,p y , <br />section 1604 of the Florida Building Code. C I <br />g , e a culations repared kiy Tilteco; <br />P <br />inc,, dated 12/1 B110 and 08127113 (for this revision), signed and sealed by Walter <br />A. Tillit, Jr., P.E. <br />3. MISSILE IMPACT RESISTANCE: <br />Large missile impact under section 1609,1.2 of the Florida Building Code, as per <br />SSTD 12-99 Standard and TAS 201. <br />4. HAND LOAN RESISTANCE: <br />24 Gage Galvanized Steel Storm Panel has been verified to sustain wind <br />pressures. Maximum panel length shall be as indicated on sheets 3, 9, 10, 11, <br />12 and 17 of 18 of Product Evaluation Document (P.E.D.), drawing No. 20.175- <br />Maximum Anchor Spacing shall be as indicated on sheets 5, 9, 10, 11,13 thru 16 <br />and 18 of 18, of Product Evaluation Document (P,E.D.), drawing No. 20-175.. <br />24 Gage Galvanized Steel Storm Panel has been verified for code compliance to <br />work as a non -porous storm shutter assembly, as per SSTD 12-99 Standard. <br />a�yN� yf�Q1AgTt((Jt% <br />''�t;ENS" �?) <br />ti 67 <br />STATE OFQ <br />RM <br />4/*.`,1'9010'NIA 11iN, . <br />MAX. GAP <br />tf4" ' <br />PRODUCT EVALUATION ATPORT NO 20-072702 3 <br />5 INSTALLATION• <br />Installation shall be performed strictly in accordance with details indicated on <br />sheets 3 thru 8, 12 thru 18 of 18, of Product Evaluation Document (P.E.D.), <br />drawing No. 20-175. Minimum separation to glass shall be as indicated on <br />sheets 3, 6, 13, 14, 16, 16 and 18 of 18, of Product Evaluation Document <br />(P,E.D.); drawing No. 20.175. <br />S. MATE_RiAL CHARACTERISTICS AND SPECIFICATIONS' <br />Shall be strictly in accordance with General Notes and Components indicated on <br />sheet 1 and 2 of 18, of Product Evaluation Document (P,E.D.), drawing No, <br />20.175. <br />Anchor specifications shall be as indicated on sheet 1 of 18, of Product <br />Evaluation Document (P.E.D.), drawing No. 20-175. <br />7. LIMITATIONS.AND CONDITIONS OF USE: <br />7.1. Shalt be strictly in compliance with General Notes No. 1, 8 thru 14, indicated <br />on sheet 1 of 18 of Product Evaluation Document (P.E.D.), drawing No. 20-175 <br />b Tilteco Inc. n i <br />prepared y a d sgned and sealed by Waller A. Tillit, Jr., P;E. <br />7.2. Product shall not be installed within HIGH VELOCITY HURRICANE ZONES <br />as defined on section 1620.2 of the Florida Building Code. <br />7.3. Product shall only be installed into poured concrete, concrete block, and <br />wood frame structures. <br />Product Evaluation Report prepared by Walter A. Tiilit, Jr., P.E. (Florida License <br />No. 44167), President of Tilteco, Inc. (Florida CA-0006719). <br />WATILL <br />Dn TILTECO ADMON RECORDS k P. E. REPORT <br />GALVAfNIZED. STEEL STORM PANEL LDRWG#.20-17 <br />1/4, 2/4, 3/4. 4/4, 5/5, 7/5, <br />1W/10, 2W/10, 3W/10, 4W/10. 6/5 <br />SW/10, 6W/11 A 7W/11 <br />„ANCHORS: FOR CONCRETE SEE SCHEDULE ON SHEETS 9 & 9 3' MAX <br />- FOR WOOD SEE SECTIONS ON SHEETS 10 & 11 11 MIN. <br />O / O <br />AS <br />` $OLTED PANELS W/ 1/{►-20x1" <br />5. M.s. BOLT W/ 7/6' X 3/32- <br />W'INFNUIS O FA OVERLAP <br />I , (SEE SECTIONS AS APPL"%-') <br />MAX---!1/4. 2/4, 3/4, 4/4, 5/5, 7/5, <br />MIN 1W/10, 2W/10. 3W/10, 4w/10, <br />5W/10, 6W/11 A 7W/11 <br />_,__ANCHORS: FOR CONCRETE SEE SCHEDULE ON SHEETS 9 <br />FOR WOOD SEE SECTIONS ON SHEETS 10 & 91 <br />REGULAR STORM PANELL$ t dE Q ELEVATION <br />N.T.S. <br />2.6T <br />(MaX Um-1 WTWLE VA en <br />1' MIN. <br />6/5 <br />1/4- Max. GAP <br />No <br />'.O•,••. <br />i�pF :• <br />hEF <br />44167 �. <br />-w. _ <br />DR1 <br />am TXTEw, INC. <br />IL. E C O InQ.IN <br />20 GAGE GALVANIZED STEEL STORM PANEL <br />'DIANN SIT <br />GLOBAL PROTECTION PRODUCTS, t1C.kTE <br />4aW SMa. 8/ STREET <br />NMaC cls4)6II4•-T5FLAW.,(6sajgll-6T6T <br />a7/e/2mo <br />TWA.F� 6>aN. 0:10 MIIeV,: RMYN <br />il <br />c"DO"19 <br />WATER A. TAUT &., P.C. <br />20-176 <br />TIPIYMND No: <br />.mss,s IMt war „�Mr, sat <br />/MtD <br />i' - <br />5"m 3 or 26 <br />INSTALLATION <br />INTO EXISTING POURED <br />DETAILS FOR REGULAR PANEUCD <br />do t1A <br />STRUCTURES <br />CONCRETE OR CONCRETE BLOCK <br />CONCRETE BLOCK <br />B LCK <br />F�m B1.IX:K <br />RDEROCONCCDEDl <br />CONCRETE MC"ORB <br />SG)IEDULE <br />1"- SHEET 9) <br />I <br />« REQ� <br />j <br />If ANONORS <br />NSCHQALE ON <br />[ :!TNT2T 9) <br />I <br />I Aek <br />(-- SCHFDUI <br />l SHEET 9) <br />C� \ i <br />I ; I 1 , <br />_ <br />S i I I ae I <br />O <br />t OTTS Z <br />YMFQ NUT G EACH -N TWO RUT G FApf W� 6 <br />n I ! <br />SDi <br />MAY OF 1* <br />l /.+: 1 -1 �7T tM .:fff✓. ! ir.'' I MAX <br />In <br />L- >E ARGOTS sTA 0 <br />�ETSR9) (Tiff st•NEOUIF ON <br />.� Bi3CK OR <br />REQUIROO <br />DIRECT MOUNTING <br />SCAM 3/e-1". <br />14' SS. 90L.Y <br />W2 WING NUT <br />D.G. <br />CO!lCIff�TE� OR <br />moo« REOURED <br />ilI1NSi <br />SCAB 3/)5-T' <br />E.D. - EDGE DISTANCE 1)RT�-FOR COMa93AtTrt){ OF sFCnDNS: <br />(SEE SCHEDULE ON O & BOTTOM MOUNTINGS CAN BE <br />SHEET 9) COMB)NED IN ANY WAY TO SUIT ANY <br />INSTALLATION. <br />f <br />FOR MAD 5T:U 41:CTTIN4S ON 5HEET 12 <br />f <br />REGULAR STORIst PANELS ELEVATION <br />SCALE 3/32•-1 <br />-_- i <br />1/4' MAX, GAP <br />I <br />2.67' <br />(AIR CVERLAP>+-11 WHOLE VRIEF) <br />z4 <br />CONCRETE ANCHORS <br />ON <br />SXF2T 9) i/{• MM <br />R KE aR <br />SECMNA-A�(VTA <br />SCALE 3/32--1- <br />r,ytiQ�•:'''�t'AENS *'? �,. <br />FLORIDA BUILDING CODE Hi h Velocity Hu cant Zone) <br />No <br />44167 ? <br />97A1I U=. W_ <br />20 GAGE GALVAN IND STEEL STORM PANELOPAW <br />F r. <br />S <br />ATE c � <br />IL ECOIrho. <br />GLOBAL PROTECTION PRODUCTS, U.C. <br />MAX. <br />20-176 <br />iNtWIFNB Nx <br />•, <br />• a A <br />MN Aj'S/ <br />,A"ANNF <br />RttiP . Z <br />•• '� at` <br />T LLIT CffM►ANY <br />nw�. , c,IN aT ,"I . r: , aw rn-wT <br />61�0 <br />4600 S.M. 51 W <br />are, n. 53514 <br />PROM: W4)BNT 1645. FAK (954)e6B-6797 <br />Nx ,",snn to . ,a,rar Nal <br />��INi4iil,^ M <br />MN.TCRa, U. J <br />Cll <br />Cll <br />0 <br />0 <br />N <br />IL <br />0 <br />co <br />}tl <br />V <br />^1 <br />a) <br />N <br />� <br />»V <br />M <br />U <br />-� <br />"ram <br />v) ♦ <br />0 <br />0 <br />0 <br />C5 <br />Co <br />0 <br />O <br />+� <br />C6 <br />LL <br />y— <br />0 <br />Co <br />> <br />-� <br />U) <br />E <br />0Co <br />O <br />CU <br />-i-+ <br />Q <br />Z <br />Z <br />W <br />J <br />( V 0 M <br />Cv 00 Ut V <br />® m IL a <br />C!i O <br />t " C5 m <br />7 <br />7 << <br />V r� <br />�3 .5 <br />%.) Q <br />(n <br />^Ii <br />W <br />_(D <br />U) <br />CU <br />CIO <br />(D <br />ICU <br />CLL <br />Vi <br />W <br />W <br />= <br />Q <br />Z <br />Z <br />Q <br />J <br />SHEET NO. <br />SH <br />1.0. <br />