Laserfiche WebLink
External Lighting Compliance <br />Description Category Tradable? Allowance Area or Length ELPA CLP <br />(W/Unit) or No. of Units (W) (W) <br />(Sgft or ft) <br />None <br />Project: ZEPHYR COMMONS <br />Title: ZEPHYR COMMONS OUTPARCEL 4 <br />Type: Office <br />(WEA File: FL TAMPA INTERNATIONAL AP.tm3) <br />Lighting Controls Compliance <br />Acronym Ashrae Description Area Design Min Compliance <br />ID (sq.ft) CP CP <br />MAIN 16 Office -Open Plan 7,000 3 3 PASSES <br />PASSES <br />Project: ZEPHYR COMMONS <br />Title: ZEPHYR COMMONS OUTPARCEL 4 <br />Type: Office <br />(WEA File: FL_TAMPA_INTERNATIONAL AP.tm3) <br />System Report Compliance <br />5-TON 5-Ton Rooftop Unit Constant Volume Air Cooled <br />No. of Units <br />RTU Single Package System < <br />65000 Rtu/hr <br />5 <br />Component Category Capacity Design Eff Design IPLV <br />Comp- <br />Eff Criteria IPLV Criteria <br />liance <br />Cooling System Air Conditioners Air 63000 16.10 14.00 <br />PASSES <br />Cooled Single Pkg < <br />6500013tu/h Cooling <br />Capacity <br />Heating System Electric Furnace 22100 1.00 1.00 <br />PASSES <br />Air Handling Air Handler (Supply) - 2000 0.50 0.82 <br />Not Required <br />System -Supply Constant Volume <br />PASSES <br />EnergyGauge Summit® Fla/Com-2020. Effective Date: Dec 31, 2020 <br />Florida Building Code, Seventh Edition (2020) - Energy Conservation C402.1.1: ASHRAE Energy Cost Budget Option <br />5/19/2022 Page 6 of 24 <br />