Laserfiche WebLink
Test Laboratory: Hurricane Test Laboratory, Inc. (HTL) & Architectural Testing, Inc. (ATI). <br />Note that HTL is now known as Intertek Architectural Testing, Inc.) <br />Test report numbers: <br />HTL reports 0049-1106-00, 0049-0406-01 & 0049-0202-05; ATI reports B8873.01-550- <br />18. Note: All HVHZ test reports have been signed & sealed by a Florida PE. <br />General report notes & system limitations: <br />l . All size & installation conditions shown in this report, the referenced drawing No. 1790 <br />and Addendum "A" are based off the referenced test reports and/or engineering analysis <br />in accordance with the Florida Building Code. <br />2. Curtain wall shall be constructed in accordance with the descriptions in this report, and <br />the manufacturer's state approved quality assurance entity specifications. <br />3. This product is approved for use in & outside of the High Velocity Hurricane Zones <br />(HVHZ). <br />4. Job required design wind pressure shall be calculated in accordance with the Florida <br />Building Code Chapter 16 and ASCE 7 Minimum Design Loads for Buildings and Other <br />Structures (0.85 directionality factor may apply per the current ASCE 7 standard). <br />5. This curtain wall is small missile impact rated and may not be installed at elevations <br />below 30 ft. above grade or at any code designated large missile impact location without <br />an approved shutter. <br />6. Dry glazing gaskets are in accordance with ASTM C864 <br />7. When applicable, all safety glass requirements must be met per FBC chapter 24. <br />(ATI) Architectural Testing, Inc. <br />APR 0 8 2016 <br />Warre . Schaefer, P.E. <br />Flo ' P.E. #44135 <br />