Laserfiche WebLink
I Notification NAC 1 <br />2 Notification NAC 2 <br />1 Jnused <br />2 Unused <br />0.00000 0.66000 <br />O.00000_____ 0.36300 <br />NAC Standby: 0.00000 NACAIarm_1.02300 <br />Standby (amps) M"Alarm (amps) <br />Total <br />Total A <br />0.00000 0.00000 <br />0,00000 0.00000 <br />1/0 Standby: OA0000 I/O Alarm: 0.00000 <br />Panel Current: 0.13000 <br />0.22000 <br />P-Link Current: 0,01600 <br />0.02300 <br />SLC Device Current: 0.00676 <br />0.04276 <br />NAC Circuit Current: 0.00000 <br />1.02300 <br />1/0 Circuit Current: 0.00000 <br />C.00000 <br />SLC Loop Type: Class B <br />Total Standby y, " Total Alarm. <br />130 <br />Device Addresses Used amnam <br />Standby Hours: 24 Alarm Mins: <br />5 <br />Device Addresses Available: 100 <br />AH Required: 3.67 AH Required: <br />0.11 <br />Total Combined Standby & Alarm AmpHours Required: <br />3.78 <br />Safety Margin: <br />20% <br />Required Battery AmpHours: <br />4.54 <br />Battery AmpHours Provided: <br />Note: The cabinet will house two 8 AH or 18 AH batteries. The <br />charging circuit is rated for up to two 55 AH batteries. <br />Potter Electric Signal (C(2017 3 of AFC-100 Battery and Voltage Drop Calculation <br />