Laserfiche WebLink
Quantity System Type & Description <br />Fans: <br />AC-5 Fan Supply, Constant Volume, 335 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade <br />AC-6 (Single Zone): <br />Cooling: 1 each - VRF Zone Fan Unit, Capacity = 18 kBtu/h, No Economizer, Economizer exception: None <br />No minimum efficiency requirement applies <br />Fan System: AC-6 Fan I BREAKROOM -- Compliance (Motor nameplate HP method) : Passes <br />Fans: <br />AC-6 Fan Supply, Constant Volume, 812 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade <br />AC-7 (Single Zone): <br />Cooling: 1 each - VRF Zone Fan Unit, Capacity = 24 kBtu/h, No Economizer, Economizer exception: None <br />No minimum efficiency requirement applies <br />Fan System: ACU-7 FAN I DENTAL EXAM UBER 1 -- Compliance (Motor nameplate HP method) : Passes <br />Fans: <br />ACU7 FAN Supply, Constant Volume, 883 CFM, 0.2 motor nameplate hp, 0.0 fan efficiency grade <br />AC-8 (Single Zone): <br />Cooling: 1 each - VRF Zone Fan Unit, Capacity = 24 kBtu/h, No Economizer, Economizer exception: None <br />No minimum efficiency requirement applies <br />Fan System: ACU-8 FAN I DENTAL EXAM UBER 2 -- Compliance (Motor nameplate HP method) : Passes <br />Fans: <br />ACU8 FAN Supply, Constant Volume, 883 CFM, 0.2 motor nameplate hp, 0.0 fan efficiency grade <br />AC-9 (Single Zone): <br />Cooling: 1 each - VRF Zone Fan Unit, Capacity = 12 kBtu/h, No Economizer, Economizer exception: None <br />No minimum efficiency requirement applies <br />Fan System: AC-9 Fan I MED EXAM UBER 2 -- Compliance (Motor nameplate HP method) : Passes <br />Fans: <br />AC-9 Fan Supply, Constant Volume, 371 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade <br />AC-10 (Single Zone): <br />Cooling: 1 each - VRF Zone Fan Unit, Capacity = <br />No minimum efficiency requirement applies <br />Fan System: ACU-10 FAN I MED EXAM UBER 1 <br />15 kBtu/h, No Economizer, Economizer exception: None <br />-- Compliance (Motor nameplate HP method) : Passes <br />Fans: <br />FAN ACU10 Supply, Constant Volume, 494 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade <br />AC-11 (Single Zone): <br />Cooling: 1 each - VRF Zone Fan Unit, Capacity = 18 kBtu/h, No Economizer, Economizer exception: None <br />No minimum efficiency requirement applies <br />Fan System: ACU-11 FAN I EXAM WORK AREA -- Compliance (Motor nameplate HP method) : Passes <br />Fans: <br />ACU11 FAN Supply, Constant Volume, 600 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade <br />DOAS-1 (Multiple -Zone): <br />Heating: 1 each - Central Furnace, Electric, Capacity = 68 kBtu/h <br />No minimum efficiency requirement applies <br />Cooling: 1 each - Single Package DX Unit, Capacity = 66 kBtu/h, Air -Cooled Condenser, Air Economizer <br />Proposed Efficiency = 14.90 EER, Required Efficiency: 11.20 EER + 12.8 IEER <br />Fan System: DOAS-1 Building Outside Air -- Compliance (Motor nameplate HP method) : Passes <br />Fans: <br />DOAS-1 Supply, Constant Volume, 1260 CFM, 1.0 motor nameplate hp, 0.0 fan efficiency grade <br />DOAS1 EXH Exhaust, Constant Volume, 1050 CFM, 1.0 motor nameplate hp, 0.0 fan efficiency grade <br />Project Title: BLOX - Zephyrhills <br />Report date: 11/23/20 <br />Data filename: P:\CLNT\Retail G\07 Project Manual\COMcheck\Zephyrhills COMCheck-2020.11.13.cck Page 9 of 37 <br />