DESCRIPTION <br />The Fike Intelligent Beat detector (P/N 60-1039 & 60-1040) is a fixed <br />temperature/rate-of-rise detector thatt can be programmed for a set -point range <br />of 135-170°F for ordinary detection, or 175-190°F for intermediate detection. <br />Detectors in rite intermediate range may be programmed for either fixed or <br />4 <br />15°F rate -of -rise application. The detector is designed with tri-color LEDs to •�' <br />i <br />indicate detector status. A remote LED annunciator (P/N 02-3868) is available <br />as an accessory. It can be configured to follow the sensor LED operation or be <br />independently controlled. 'I:Ine isolator version (P/N 60-1040) pro -,tides complete <br />short circuit isolation for. N.FPA 72, Style 7 wiring if used with an isolator. base. <br />The detector is compatible with Fike's CyberCat and Cheetah Xii intelligent control panels. Its operating parameters are. Y x <br />configured using the panel's programming software and are stored within non-volatile RATNI. in the detector. This on -board <br />intelligence allows each detector to communicate its status directly to other devices connected to the panel. This peer. - <br />to -peer digital protocol results in less information that needs to be sent between the detector and the host control panel, <br />resulting in faster, more reliable communication. <br />SPECIFICATIONS <br />Normal Operating Voltage: <br />15 to 30 VDC <br />Standby Current: <br />215 µ , max. @ 24 VDC (continuous broadcasts) <br />LED Current: <br />2 mA max. @ 24 VDC (LEDs on) <br />Operating Humidity Range: <br />10% to 93% Relative Humidity Non -condensing <br />Installation Temperatures:. <br />-4°F to 100°F (-20°C to 38°C); 135°F-174°F setpoint <br />-4°F to 150°F (-20°C to 66°C); 175°F-190°1,' setpoint <br />Fixed'remperature Rating: <br />135°F (570C)190°F (88°C); programmable <br />Rate. of Rise Detection: <br />Responds to greater than 15°F/min.(8°C/mm); programmable <br />Spacing for Thermal Detectors: <br />Detectors set between 135' to 1550F or 175' to 190oF : 50 ft (15.24 m) spacing <br />Detectors set between 160' to 170°F: 15 ft. (4.57 M) spacing <br />Height: <br />2.1 inches (51 mm)in 63-1054 base <br />Diameter: <br />6.1 inches (155 mm) installed in 63-1054 base <br />4.1 inches (104 mm) installed in 63-1055 base <br />Weight: <br />4.8 ounces (137 g) <br />Form No. P.1.90.01-4 I <br />704 S.W. 10th Street • P.O. Box 610 • Blue Springs, Missouri 64013-0610 U.S.A. (816) 229-3405 - www.fike.com <br />