Laserfiche WebLink
SpectrAlert Advance Specifications <br />General <br />SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or <br />double -gang back box. Two -wire products shall also mount to a single -gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall <br />be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. <br />Also, SpectrAlert Advance products, when used with the Sync•Circuit" Module accessory, shall be powered from a non -coded notification <br />appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification <br />appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between <br />16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full - <br />wave rectified unfiltered power supply. Strobes and horn strobes shall have field -selectable candela settings including 15, 15/75, 30, 75, 95, <br />110, 115, 135, 150, 177, and 185. <br />Strobe <br />The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service <br />The strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for <br />visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash <br />tube and associated lens/reflector system. <br />Horn Strobe Combination <br />The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for <br />fire protective service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with <br />Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light <br />shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch <br />between a temporal three pattern and a non -temporal (continuous) pattern. These options are set by a multiple position switch. On four -wire <br />products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non -coded <br />power supply. <br />Synchronization Module <br />The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module <br />shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns <br />on horn strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/8-inch back box. The module shall also <br />control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more <br />synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. <br />Standard Operating Temperature 32°F to 120°F (0°C to 49°C) <br />Humidity Range 10 to 93% non -condensing <br />Strobe Flash Rate 1 flash per second <br />Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR' <br />Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) <br />Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) <br />Input Terminal Wire Gauge 12 to 18 AWG <br />Wall -Mount Dimensions (including lens) 5.6-L x 4.7-W x 2.5-D (142 mm L x 119 mm W x 64 mm D) <br />Horn Dimensions 5.6"L x 4.7-W x 1.3-D (142 mm L x 119 mm W x 33 mm D) <br />Wall -Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS) 5.7-L x 4.8-W x 0.35-D (145 mm L x 122 mm W x 9 mm D) <br />Notes: <br />1. Full Wave Rectified (FWR) voltage is a non -regulated, time -varying power source that is used on some power supply and panel outputs. <br />2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. <br />