Laserfiche WebLink
<br />EAST PASCO MEDICAL CE ER <br />11-BED ADDITION TO SKI LED NURSING UNIT <br />LOG NO. H-425-J j C N NO. 6518 <br />JUNE 12, 1992 <br /> <br />ARCHITECTURAL <br /> <br />Approved without comm nt. <br /> <br />DHPjsl <br /> <br />MECHANICAL <br /> <br />Approved without comm nt. <br /> <br />JPMjsl <br /> <br />FIRE PROTECTION <br /> <br />B. Remot area is shown as more than 1,600 square <br />feet. Show 1,500 square foot area. <br /> <br /> <br />ction document review letter was dated <br />esponse dated April 2, 1Q92 to the original <br />requirements of this office with the <br /> <br />The original constr <br />March 20, 1992. The <br />review satisfies t <br />following exception( <br /> <br />FP-1 <br /> <br />Revise <br />data: <br /> <br />calculations to include the following <br /> <br />A. <br /> <br />er sprinkler is SxL, where S=14 feet and L= <br />t or 168 square feet. <br /> <br />L of most demand is not in the designated <br />area. <br /> <br />mote area is defined as a rectangular area <br />e walls), which is the hydraulically most <br />ing area. <br /> <br />C. For 1 8 square foot single head coverage, 16.8 gpm <br />at 9 psi is required. Ten heads will cover the <br />area. <br /> <br />D. <br /> <br /> <br />FP-1 (A). <br /> <br />Locat <br />area. <br /> <br />the most demanding hydraulically remote <br /> <br />Page 1 of 2 <br />