<br />EAST PASCO MEDICINE ENTER <br />NUCLEAR MEDICINE <br />LOG NO. H-425-0 / C N NO. NON-REVIEWABLE <br />DECEMBER 21, 1992 <br /> <br />ARCHITECTURAL <br /> <br />The original const uction document review letter was dated <br />November 2, 1992. he response dated October 26, 1992- to the <br />original review sat' sfies the requirements of this office with <br />the following except on(s). <br /> <br />Sheet A4.1: <br /> <br />A-2 <br /> <br />Duct shaft cannot run in stair B. <br />shaft out f stair. <br /> <br />Relocate duct and <br /> <br />Horizontal portion of duct shaft must be of <br />constructi n tested for horizontal application. Test <br />lab. design number noted is for vertical application <br />only. Pro ide test lab design number for horizontal <br />applicatio also. Provide detail of intersection of <br />horizontal and vertical. Coordinate Sheet A4-1 plan <br />with Sheet MP~l plan of shaft enclosure. <br /> <br />DHP/sl <br /> <br />MECHANICAL <br /> <br />No comments. <br /> <br />FIRE PROTECTION <br /> <br />No comments. <br /> <br />ELECTRICAL <br /> <br />Approved without comm nt. <br /> <br />MFC:TLM/sl <br /> <br />Page 1 of 1 <br />