<br />EAST PASCO MEDICAL CE TER <br />11-BED ADDITION TO SK LLED NURSING UNIT <br />LOG NO. H-425-J j CON NO. 6518 <br />DECEMBER 21, 1992 <br /> <br />FP-9 <br /> <br />Provide sp inkler layout in stores area on Sheet FP-3, <br />showing ho Stairs-1 is sprinklered. <br /> <br />FP-10 <br /> <br />Revise rem layout <br />area to gree with the <br />rectangular format. <br /> <br />shown in <br />NFPA-13 <br /> <br />the loading dock <br />(1989) standard <br /> <br />FP-11 <br /> <br />It is reco mended the anti-freeze system be limited to <br />the 40 gall n capacity detailed in NFPA-13 (1989). The <br />enclosed r ms in the dock area can be sprinklered with <br />a conventio al wet pipe system. <br /> <br />FP-12 <br /> <br />Revise the loading dock remote area calculations to <br />provide a inimum of 26 psi water pressure to cover an <br />area of 143 square feet with 0.20 gallons per minute. <br /> <br />FP-13 <br /> <br />Provide a detail of the required anti-freeze piping <br />system mixi g arrangement. <br /> <br />JPMjsl <br /> <br />ELECTRICAL <br /> <br />New Comments: <br /> <br />E-6 <br /> <br />Sheet E-2: <br /> <br />A. The s bmitted narrative indicates no changes to <br />Sheet E-2. However, Sheet E-2 indicates several <br />No. 7 hanges. Review and advise. <br /> <br />B. Revie the receptacle in Room 103. Remove from <br />the l'fe safety branch if not in compliance with <br />NFPA-7 Chapter 517-32. <br /> <br />MFC:TMjsl <br /> <br />Page 3 of 3 <br />