Laserfiche WebLink
<br />SPRIN'LER SYSTEM HYDRAULIC ANALYSIS <br /> <br />Page 3 <br /> <br />JOB TITLE: PASCO MEDIC L CENTER NEW STANDPIPE <br /> <br />NOTES: <br />(1) Calculations wele pe,fo,med by the HASS 5.5.0 computel ploglam <br />under license 428L203 g,anted by <br />Systems, I nc . <br />3 Ranchwood Dr., N.E. <br />anta, GA 30345 <br /> <br />(2) The system has be n balanced to p,ovide an average <br />imbalance at each node of 0.012 gpm and a maximum <br />imbalance at any ode of 0.071 gpm. <br /> <br /> <br />(3) Velocity pressule ale p,inted for information only, and are <br />not used in balan ing the system. Maximum water velocity in <br />any pipe is 5.1 f /sec. <br /> <br />(4) PIPE FITTINGS TAB E <br /> <br />Pipe Table Name: STANDARD.PIP <br /> <br />PAGE: A MATERIAL: S40 HWC: 120 <br />Diameter Equivalent Fitting Lengths in Feet <br />( in) E T L C B G A D <br /> Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv <br />8.071 18.00 35.00 13.00 45.00 12.00 4.00 35.00 27.00 <br />