Laserfiche WebLink
<br />ZONE DESIGN COOLING LOAD SUMMARY <br />Location Tampa, Florida 02-02-93 <br />Prepared By ADVANCED TECH. DESIGN 6022890201 <br />Carrier Hourly Analysis Program Page 1 of 2 <br />************************************************************************ <br />CALCULATION DATA: <br />Zone Name: -~ _,RESIDENCE Calc Time: Jul 1700h <br />Job Name : RESID.LOAD FOR GENE CLEM Amb db/wb: 90.3/ 76.6 F <br />************************************************************************ <br />LOAD INFORMATION <br /> <br />LOAD COMPONENT <br /> <br />SENSIBLE <br />(BTU/hr) <br /> <br />LATENT <br />(BTU/hr) <br /> <br />------------------------------------------------------------ <br /> <br />SOLAR GAIN <br />GLASS TRANSMISSION <br />WALL TRANSMISSION <br />ROOF TRANSMISSION <br />PARTITION TRANSMISSION <br />LIGHTING ( 3,924 W TOTAL) <br />OTHER ELEC. ( 0 W TOTAL) <br />PEOPLE ( 4.00 PEOPLE TOTAL) <br />MISCELLANEOUS LOADS <br />COOLING INFILTRATION <br />PULLDOWN/WARM-UP <br />COOLI'NG SAFETY LdAD <br /> <br />11,414 <br />4,300 <br />3,604 <br />3,655 <br />890 <br />13,364 <br />o <br />1,119 <br />o <br />o <br />o <br />1,150 <br /> <br />o <br />o <br />o <br />o <br />o <br />o <br />o <br />1,080 <br />o <br />o <br />o <br />32 <br /> <br />------------------------------------------------------------ <br /> <br />SUB-TOTALS <br />NET VENTILATION LOAD ( <br />SUPPLY FAN LOAD (BHP= <br />WALL LOAD TO PLENUM <br />ROOF LOAD TO PLENUM <br />LIGHTING LOAD TO PLENUM <br /> <br />183 CFM) <br />0.2) <br /> <br />39,496 <br />3,021 <br />502 <br />o <br />o <br />o <br /> <br />1,112 <br />6,569 <br />o <br />o <br />o <br />o <br /> <br />------------------------------------------------------------ <br /> <br />TOTAL COOLING LOADS 43,019 7,681 <br />************************************************************************ <br />COIL SELECTION PARAMETERS: <br />COIL ENTERING AIR TEMP. (DB/WB) = 76.5/ 63.8 deg F <br />COIL LEAVING AIR TEMP. (DB/WB) = 54.7/ 54.2 deg F <br />COIL SENSIBLE LOAD = 43,019 BTU/hr <br />COIL TOTAL LOAD = 50,700 BTU/hr <br />COOLING SUPPLY AIR TEMPERATURE = 55.0 deg F <br />TOTAL COOLING CFM (actual) = 1,830 CFM <br />TOTAL COOLING CFM (std. air) = 1,829 CFM <br />RESULTING ROOM REL. HUMIDITY = 47.7 % <br />COIL BYPASS FACTOR = 0.050 <br />COIL APPARATUS DEWPOINT = 53.6 deg F <br />REHEAT REQUIRED = 0 BTU/hr <br />************************************************************************ <br />GENERAL INFORMATION: <br />TOTAL COOLING LOAD = 4.23 Tons <br />= 515.97 sqft/Tons <br />TOTAL FLOOR AREA = 2,180.00 sqft <br />OVERALL U-FACTOR = 0.154 BTU/hr/sqft/F <br />COOLING CFM/sqft = 0.84 CFM/sqft <br />************************************************************************ <br />