Laserfiche WebLink
<br />'!f'"'''~' "\: <br /> <br />ARTICLE 250 - GROUNDING <br /> <br />70-127 70-128 <br /> <br />NATIONAL ELECTRICAl.. CODE <br /> <br />(b) Metal Frame of the Building. The metal frame of the building, where <br />effectively grounded. .1 , , <br /> <br />(FPN): Effectively grounded meansintentional1y connected to earth through a <br />ground connection or connections of sufllciently low ltupedance and having suffi- <br />cient current-canying capacity to prevent the btilldup ofWltagea that may result in <br />undue hazard to c:onnected equipment or to pell!lOllS. . <br /> <br />ee) ~ Electrode. An electrode encased by at least 2 <br />H. Grounding Electrode System inches (SO.8 nun) of concrete, located within and near the bottom 'Of a con- <br />, crete foundation or footing that is in direct contact with the earth, consist- <br />250-81. ,G~ndlng Electrode System., If available on the premises atl ing of at least 20 feet (6.f m) of one or more bare or zinc galvanized or <br />each building or structure served, each Item (a) throuJdt (d) below, and any otherelectricaIJy conductive coated steel reinforcing bars or rods of not <br />made electrodes in accordance with Sections 25O-83'(c) and (d), shall be. less than Ih inch (127 nun) diameter or consisting of at least 20 feet <br />bonded together to form the grounding electrode system. Interior metall (6.1 m) of bare coppe; conductor nots:Oaller than No.4. <br />water piping lOCated more than 5 feet (152 em) from the point of entrance , " , . , <br />to the building shall not be used as a conductor to interconnect the elec- ,(d) Ground RI.ng. A ground nng encircling the building or structure, m <br />trodes and the grounding electrode conductor. The bonding jumper shall be direct contact With the ,elJ!th at a depth below earth surface not less than <br />installed in accordance with Sections 250-92(a) and (b), shall be sized in 2V2 feet (762 nun), COnsISting of at least 20 feet (6.1 m) of bare copper con- <br />accordance with Section 250-94, and shall be connected in the mannerl ductor not smaller than No.2. <br />specified in Section 250-115. The unspliced grounding electrode conductor <br />shall be permitted to run to any convenient grounding electrode available ~~. M~ and. ~ ~ . Where none of the electrodes sp-cc- <br />in the grounding electrode system. It shall be sized for the largest ground- !fled m Section 250-81 IS available, one or more of !he electrodes specified <br />ing electrode conductor required among all the available electrodes m (b) throuJdt (d) below shall be used. Where practicable, made electrodes <br />. . . . .' shall be embedded below permanent moisture level. Made electrodes shall <br />Exceptton No.1: It s'!aU be J!i!'"l#ted to sI?lice the growtding e~ctrode be free fJ;om nonconductive coatings, such as paint or enamel. Where more <br />conductor by means of I17'f!Vt;rsible c:ompresslOn-type connectors listed for than one electrode is used, each electrode of one grounding system (includ- <br />the purpose or the exothennic welding process. ing that used for lightning rods) shall not be less than 6 feet (1.83 m) from <br />Exception No.2: In industrial and commercial buildings where condi. any other electrode of another grounding system. . <br />tions of maintenance and supervision ensure that only qualified persons . , <br />will service the installation and the entire length of the interior metal water (FPN): ~ or more electrodes, that, are effectively bonded together are to be <br />pipe that is being used for the conductor is expos(!d. treated as a smgle electrode Iystem m this sense. ," . <br /> <br />(FPN): See Section 547-8 for special grounding and bonding requirements for "(~) ",etaI Underground Gee PlplngS~ A metal underground gas <br />agncultural buildings. plpmg system shall not be used as a grounding electrode. <br />,. (b) Other Local Metal Underground SptemI or Structu..... Other local <br />,(a) Metal Und~ground Water Pipe. A metal underground ,water,plpe In metal underground systems or structures such' as piping systems and <br />direct contact With the earth for 10 feet (3.05 m) or more (mcludiDg any underground tanks '. , <br />metal well casing effectively bonded to the pipe) and electrically continu- . , <br />ous (or made electrically continuous by bonding around insulating joints or (e) Rod and Pipe ~ectrodeL Rod and plJ?C electrodes sh~ not be ,less <br />sections or insulating pipe).to the pomts of connection of the grounding than 8 feet (~.44 m) I~ length and ,shall conSISt of the foUowmg matenals, <br />electrode condu(;tor and the bonding conductors. Continuity of the ground- and shall be mstalled m the foUowmg manner: <br />ing path or the bonding connection to interior piping shall not rely on water (1) Electrodes of pipe or conduit shall not be smaller than ~4-inch trade <br />meters. A metal underground water I?ipe shall be supplemented by an size and, whereof iron or steel, shall have the outer surface galvanized or <br />additional electrode of a type specified In Section 250-81 or in Section 250- otherwise metal-coated for corrosion protection. <br />83. The supplemental electrode shall ~ permitted to be bonded to the f2) Electrodes of rods ofiron or steel shall be at least %'8 inch (15.87 mm) <br />grounding electnx!e conductor, the groUnded servi~-entrance conductor'I' in diameter. Stainless steel rods less than %'8 inch (15.87 mm)in diameter, <br />the grounded seIVIce raceway, or any grounQed seIVIce enclosure. I nonferrous rods or their equivalent shall be Iisted and shall not be less than <br />W~re the supple~ental electrode ,is a. made electf!XIe as in Section 2;)0- V2 inch (12.7 om't) in diameter. ", <br />83(c) or (d), that portion of !he bondmg Jumper that IS the ,sole connection (3) The electrode shall be installed such"that at least 8 feet (2.44 m) of <br />to the supplemental $founding electr~e shall. not be requaed to be larger length is in contact with the soil. It shall be driven to a depth of not less <br />than No.6 copper wae or No.4 alununum wae. 'than 8 feet (2.44 m) except that, where rock bottom is encountered, the <br />Exceftion: The supplemental electrode shaU be permitted to be bonded I electrode shall be driven at an oblique angle not to exceed 45 degrees from <br />to the Interior metal water piping at a'9' convenient point as covered in the vertical or shall be buried in a trench that is at least 2V2 feet (762 mm) <br />Section 250-81, Exception No.2.:' deep. The upper end of the electrode shall be flush with or below ground <br /> <br />jumper shall be sized in aCC()rdance with Table 25~95 using the rating of <br />the circuit that may enersize the piping. . <br />The equipment grounding conductor for the circuit that may energize the <br />piping shall be permitted to serve as the bondipg means. <br />(FPN): Bonding all piping and metal air ducts within the premises will provide <br />additional safety. , <br />