Laserfiche WebLink
<br />0". <br /> <br /> <br />Fire Chief <br />Robert Hartwig <br /> <br />< jj/ ~(.6 <br />Ju-~ <br />ZEPHYRHILLS FIRE DEPARTMENT <br />Zephyrhills Florida 33540 <br /> <br />I <br /> <br />38410 6th Avenue <br /> <br />Bus (813) 782-8184 <br /> <br />Fax (813) 788-3293 <br /> <br />TO: <br />RE: <br />DA TE : <br />FROM: <br /> <br />CONTRACTOR: BOLANDER PROJECT <br />REQUIREMENTS FOR PROJECT <br />1/31!!/95 <br />ASST. CHIEF JOHNSTON <br /> <br />AS PER OUR DISCUSSION ON 1/26/95: <br /> <br />1. lhr SEPARATION = 2 LAYERS 5/8 TYPE X 1 LAYER EACH SIDE <br />SHALL BE MAINTAINED BETWEEN EACH UNIT <br /> <br />2. CHANGE DOOR SW I NG ON THE OFF I CE UN I T PER NFPA II!! 1 II ALL <br />E X IT DOOF<S SHALL OPEN I N THE DIRECT I ON OF TF<AVEL II <br /> <br />3. INSTALL ONE (1) SMOKE DETECTOR IN OFFICE PER SSBC <br />ELECTRICALLY OPERATED <br /> <br />4. INSTALL ELECTRIC EXIT LIGHTS, ON (1) EACH DOOR WITH <br />1 1/2hr BATTERY BACKUP <br /> <br />5. 4hr' WALL SHALL EXTEND 1I!1" BEYOND THE BORDERING APTS. <br /> <br />6. ALL OTHER REQUIREMENTS WILL DEPEND ON THE OCCUPANT AND THE <br />UNITS INTENDED USE <br /> <br />7. PROVIDE FIRE EXTINGUISHER 2AI0B:C IN OFFICE UNIT, ALL <br />OTHER UNITS MUST HAVE A FIRE EXTINGUISHER ACCESSIBLE WITH <br />A 75" TRAVEL DISTANCE THROUGHOUT PROJECT <br /> <br />. _o;~ <br />J/J - Il 0 ~ Cj)J/J/11LL~~~ ~ <br />,q~ ~r/~Cp> .}Y <br />1"-'j.O _-./lI7Jv, V:11 1.[ (~~ <br />1>> ~V'-, / <br />oA1b,<K'- /~ <br />J',~~ <br />?i <br />