Laserfiche WebLink
<br />SEP-07-95 .THU. 22:4.6 RICK Z SI'lITH &, ASSOC ARC 813 854 1902 <br /> <br />p.ei <br /> <br />area, east and south walls. <br /> <br />Response: <br /> <br />Separallon Is not required per SBCCI Sectloll 704.1.2.1 and 704.1,2.2 since these arear <br />are considered QCcessory QI'eas, <br /> <br />~OMMENT 7: <br /> <br />Lunch room '''_II be separated fronl the warehouse and the work room with a <br />minimum of O{lt (1) hour fire rated separation. <br /> <br />Response: <br /> <br />Separation is nol required per SBCCI Section 704.1.2,} and 704, J .2.2 since these areas <br />are considered QCcessory areas. <br /> <br />COMMENT 8: <br /> <br />:~Vlde electrically operated smoke detectors in the followlnl areas: bathroom <br />__-'way. pump ro~m. all deslllnated storale areas and ale roQlIl. <br /> <br />Response: <br /> <br />To he addressed by the Electrical Engineer afrecord. <br /> <br />COMMENT 9: <br /> <br />~:~~~~ ~'~ ~:~: ann: ;::~ !lhall require permlttlna and compliance with NFPA 30. <br />ora ;b';ii not Jeop~rdlze the use of the on site fire hydrant. <br /> <br />Response: <br /> <br />To be addressed by the Mechanical Engineer of record <br /> <br />COMMENT 10; <br /> <br />Submit details on fire alarm as Indicated on the electricalle.gend. <br /> <br />Respome: <br /> <br />To be addressed by the Electrical Engineer of record <br /> <br />~OMMENT t 1: <br /> <br />provide fire extlnllulshen pt;r ~FPA 10. <br /> <br />Response: <br /> <br />Adequate fire extinguishers are provided on the plan. <br /> <br />Ir/U'ddlstanc:e not to exceed 300 fed. <br /> <br />Response: <br /> <br />The exit locatlolls comply with the 300 feet maximum travel distance. <br /> <br />ClasslOc:ation ofbuildlnc per ~PA shall be a "SPECIAl, PURPOSE <br />INDUSTRIAL OCCUPANCY". <br /> <br />Response: <br /> <br />Complies. <br /> <br />For dust eontrol- comply with NFPA 91 aDd FSS 403.087. <br /> <br />Resp01'l3e; <br /> <br />To be addressed by the Mechanical Engineer of record <br />