<br />Designator Feature Description
<br /> Isolated Fixed Temp, Isolated fixed 1350F (570C) and rate of rise heat detector, independently trips the LED and alarm
<br /> relay output. Smoke detector activates internal sounder (local alarm) and auxiliary relay, but
<br />H and Rate of Rise Heat does not latch, Approved as both single station smoke alarm and system heat detector. Ideal for
<br /> Detector hotel, motel and dormitory rooms where smoking is allowed,
<br />R Auxiliary Relay Used to activate other devices such as elevator recall, door holders, strobes, etc, Listed for .
<br />releasing service,
<br /> .
<br />S Built-in Sounder 85db built-in sounder alarms when smoke is detected or when power wiring polarity is reversed,
<br /> Built-in Sounder with 8Sdb built-in sounder alarms when smoke is detected or when power wiring polarity is reversed,
<br />55 Sensitivity Status Also, chirps when unit goes outside the approved sensitivity range for more than one day,
<br /> Output Resetting detector will silence chirp for one day, until unit is restored to proper sensitivity,
<br /> Integrated Fixed Integrated fixed 13soF (srC) temperature and rate of nse heat detector offers double protection,
<br />T Temp, and Rate of Either heat detector or smoke detector can trip and latch LED and alarm relay outputs,
<br /> Rise Heat Detector
<br />
<br />!;:SL 429 Series Smoke Detectors
<br />
<br />Architectural and Engineering Specifications
<br />The ESL 429 Senes low-profile, self-diagnostic, two-wire smoke
<br />detectors work on me light scattering principle, A pulsed
<br />infrared light-emitting diode serves as the light source, and a
<br />high-speed photo-diode as the sensing element. When the
<br />amount of light reflected onto the photodiode reaches the
<br />sensitivity setting, the smoke sampling rate increases, Three
<br />(3) successive smoke sensings above the sensitiVity setting are
<br />reaulred to sound an alarm, This design has superior
<br />protection against false alarms caused by dust. insects, RF and
<br />ambient-light.
<br />
<br />A confirmed alarm causes the normally flashing power
<br />indicator LED to light continuously and the optional alarm
<br />relay /available in "R" models) to operate, A trouble indication
<br />is automatically displayed by flashing the LED every second,
<br />This meets NFPA 72 field sensitiVity testing requirements, An
<br />Internal 85 dB horn (available in .5" models) emits a steady
<br />tone when the detector alarms and a pulsed tone when
<br />power polarity is reversed, Also available is the "55" model
<br />which chirps when the unit goes outside the approved
<br />sensitivity range for more than one day, Resetting the detector
<br />will silence chirp for one day, until unit is restored to proper
<br />senSitivity,
<br />
<br />Product Data
<br />
<br />Sensitivity, " , , . " ' , , , , " , ' , , , , ,. , , , , , , , , , , , ' , , " . , "max ,,'"
<br />min,..
<br />Operating temperature range ..'................,..
<br />
<br />3,1 - l,O%/ft,
<br />3,) + O,50%/ft.
<br />320F to 1200F
<br />OOC to 500C
<br />Operating humidity range ...........,...........,......, 0 to 95% RH
<br />Minimum voltage _..e, Q, CRT. CST, CSST ...,............... 8,5 V
<br />
<br />.N.,.""""",."",."",."""""""".."" 6,5V
<br />Maximum voltage. C. Q, CRT, CST, CSST '....'......,...... 33 V
<br />
<br />-AT ...............,....,.,....,.......,....,.......... 20 V
<br />Maximum ripple (peak to peak) ,..........,..,......,........,..... 10%
<br />Typical average standby current ........,...........,..........., 70 J..lA
<br />Field wiring size..,........,.....,...,.,........,...,.,....,... 14 - 24 AWG
<br />
<br />Selection Guide
<br />
<br />The proprietary optical sensing chamber is field replaceable,
<br />allOWing quick and easy cleaning and maintenance,
<br />
<br />Models with auxiliary relays are approved for releasing service,
<br />
<br />The very Jow profile 429 Series detectors are equipped with a
<br />hinged cover, a concealed tamper-resistant latch, and insect
<br />screens,
<br />
<br />All winng terminates in plug-in, clamp-type screw terminals,
<br />The detectors mount to a standard single-gang electrical box,
<br />a four'lnch octagonal, four-inch square electrical box, or
<br />W/REMOLD No 5739 fixture box,
<br />
<br />Smoke Detector Spacing
<br />On smooth ceilings (as defined in NFPA 72), spacing of 30
<br />feet (9,1 meters) may be used as a guide, Other spaCIng may
<br />be used depending on ceiling height. high air movement,
<br />and other conditions or response requirements,
<br />
<br />'~.~I\= =) ".,J=,w
<br />
<br />
<br />-=1 0 =-
<br />
<br />Alarm current.... draws max of 60 mA if not limited by panel
<br />Max, avg, polarity reverse current - CST ..........,.......... ) 0 mA
<br />Sounder specifications .........,......................... 85 dB at ) 0 ft.
<br />Heat detector specifications
<br />fixed temp, ................,......... 1350F:!: 50F (57,rC:!: 2,80C)
<br />rate of rise .., 150F/min, & > I 050F (8.30C/min, & > 40,60C)
<br />Relay specifications .............,....... 2A @ 28 V DC or 120 V AC
<br />PaCkaging ....., 10 detectors are packed In a carton
<br />Color ..,....,....,......,........,..,..,...,.......' white cover/white base
<br />with UV inhibitor to prevent yellOWing
<br />2-wire compatibility .................,., see ESL Compatibility Index
<br />listings UL 268, FM. CSFM and MEA (New York City)
<br />for Canadian ULC listed products use 428 series
<br />
<br />CORPORATE HEADQUARTERS
<br />] 2345 SW Levelon Dr.
<br />Tualalln, OR 97062
<br />Tel.. 503,692,4052
<br />Fax: 503,691.7566
<br />U,S, '" Canada: 800.547.2556
<br />Technical Service: 800,648,7424
<br />
<br />ESLN
<br />
<br />A PRODUCT OF SENTROL, INC
<br />
<br />Scntrol. Ine. reserves the righl
<br />10 change specihcallons
<br />WllhOUl notice,
<br />(f)] 995 Senlrol. Ine.
<br />
<br />E.) HH3.0305,I'I.C 15~
<br />
|