Laserfiche WebLink
<br />SERIAL # 2334 <br />* ResmanuJ(c) * 11-06-1996 <br />WHOLE HOUSE <br />HEAT GAIN / HEAT LOSS CALCULATION USING FLA/RES(c) DATA FILES <br />(BASED ON A.C.C.A. MANUAL J - SEVENTH EDITION (c) 1986 by A.C.C.A.) <br /> <br />------------------------------------------------------------------------------- <br /> <br />PROJECT <br />ADDRESS : <br />CITY : <br />OWNER : <br />BLDG CONTR <br />HVAC CONTR <br />Cond FIr Area: 1080 SF * GLASS/SF RATIO = 13.1% * House Faces: North <br />* Climatic Conditions & Design Conditions * <br /> <br />Geographical Location : Florida <br /> <br />---------------------------------------------------------------------------- <br /> <br />Lakeland <br /> <br />---------------------------------------------------------------------------- <br /> <br />North Latitude / Elevation <br />Outdoor Winter Dry Bulb <br />Indoor Winter Dry Bulb <br />Winter (Actual) Temp.Diff. <br />Winter Temp. Diff. (wTd) <br />Outdoor Summer Dry Bulb <br />Outdoor Summer Wet Bulb <br />Outdoor Summer Hum. Ratio Gr/Lb <br />Indoor Summer Relaltive Hum. <br />Indoor Summer Design GrjLb. <br />Indoor Summer Dry Bulb <br />Indoor Summer Wet Bulb <br />Summer Daily Range <br />Summer (Actual) Temp.Diff. <br />Summer (User Sell Temp.Diff. (sTd) <br /> <br />28 Deg. / 214 Ft. Above Sea Level <br />41 Deg. F <br />70 Deg. F <br />29 Deg. F <br />40 Deg. F <br />91 Deg. F <br />76 Deg. F <br />113 <br />50% <br />51 <br />75 Deg. F <br />62.3 Deg. F @ 64 Gr/Lb <br />17 Deg. F M <br />16 Deg. F <br />20 Deg. F <br /> <br />------------------------------------ --------------------------------------- <br /> <br />SUBTOTAL <br /> <br />* HEATING SUMMARY * MF2S1080.DAT * COOLING SUMMARY * <br /> <br />24663.08 :STRUCTURE SENSIBLE <br />:MECH.VENT- 0 Cfm <br />:SENS. + MECH.VENT <br />:TEMP.SWING @ 3 DEG. <br />: OCCUPANT/APPLIANCE <br />1233.15 :DUCT GAIN <br />25896.23 :TOTAL SENSIBLE <br />:TOTAL LATENT <br /> <br />:SENSIBLE + LATENT <br />20% OVERSIZE FACTOR 5179.25 :20% SENS.OVRSZE FTR: <br />ACTUAL + 20% OVERSIZE: 31075.48 :SENS. + 20% OVERSIZE: <br /> <br />DUCT LOSS <br />TOTAL LOSS/BTUH <br /> <br />* EQUIPMENT SELECTION * <br /> <br />EQT MANUF GOODMAN <br />HTG INP/BTUH 27400 <br />SENSIBLE BTUH 21000 <br />TONAGE 2.4 (S)EER 10 <br />NOTES: <br /> <br />CU MOD # CPE30-1 <br />HTG OUTP/BTUH 27400 <br />LATENT BTUH <br />CLG CFM 1000 <br /> <br />AHU MOD # AW30-05 <br />AFUE/HSPF 6.8 TYPE HP <br />TTL CLG BTUH 28600 <br />HTG CFM 1000 <br /> <br />9273.76 <br />0.00 <br />9273.76 <br />1. 00 <br />2400.00 <br />1167.38 <br />12841.14 <br />2671.37 <br /> <br />15512.51 <br />2568.23 <br />15409.37 <br />