<br />FORM 600A-97
<br />
<br />Code Compliance Checklist
<br />Residential Whole Building Performance Method A - Details
<br />
<br />ADDRESS: Lot: 70, Sub: SILVER OAKS, Plat: PHASE 111, ZEPHYRHILLS, FL, PERMIT #:
<br />6A-21 INFILTRATION REOUCTION COMPLIANCE CHECKLIST
<br />
<br />COMPONENTS SECTION REQUIREMENTS FOR EACH PRACTICE CHECK
<br />Exterior Windows & Doors 606.1,ABC.1.1 Maximum:.3 cfmISQ.ft. window area' .5 cfmlsq.ft. door area.
<br />Exterior & Adjacent Walls 606.1,ABC.1.2,1 Caulk, gasket, weatherstrip or seal between: windows/doors & frames, surrounding wall;
<br /> I foundation & wall sole or sill plate; joints between exterior wall panels at comers; utility I
<br /> penetrations; between wall panels & toplbottom plates; between walls and floor,
<br /> EXCEPTION: Frame walls where a continuous infiltration barrier is installed that extends
<br /> from. and is sealed to the foundation to the top plate.
<br />Floors 606.1.ABC,1,2.2 I Penetrations/openings >118" sealed unless backed by truss or joint members,
<br /> EXCEPTION: Frame floors where a continuous infiltration barrier is installed that is sealed
<br /> to the oerimeter penetrations and seams,
<br />Ceilings 606.1,ABC.1.2,3 Between walls & ceilings; penetrations of ceiling plane of top floor; around shafts, chases,
<br /> soffits, chimneys, cabinets sealed to continuous air barrier; gaps in gyp board & top plate;
<br /> attic access, EXCEPTION: Frame ceilings where a continuous infiltration barrier is
<br /> installed that is sealed at the oerimeter at oenetrations and seams,
<br />Recessed Lighting Fixtures 606.1.ABC.1.2.4 Type IC rated with no penetrations, sealed; or Type IC or non-IC rated, installed inside a i
<br /> I sealed box with 112" clearance & 3" from insulation; or Type IC rated with < 2,0 cfm from
<br /> conditioned soace tested,
<br />Multi-storv Houses 606.1.ABC,1.2.5 Air barrier on oerimeter of floor cavitv between floors.
<br />Additional Infiltration reqts 606.1.ABC,1.3 Exhaust fans vented to outdoors, dampers; combustion space heaters comply with NFPA, I
<br /> have combustion air,
<br />
<br />6A-22 OTHER PRESCRIPTIVE MEASURES (must be met or exceeded bv all residences.)
<br />COMPONENTS SECTION REQUIREMENTS I CHECK
<br />Water Heaters 612,1 Comply with efficiency requirements in Table 6-12. Switch or clearly marked circuit I
<br /> ' breaker (electric) or cutoff (aas) must be provided. Extemal or built-in heat traD reauired, i
<br />Swimming Pools & Spas 612,1 Spas & heated pools must have covers (except solar heated). Non-commercial pools I
<br /> must have a pump timer. Gas spa & pool heaters must have a minimum thermal
<br /> I
<br /> efficiencv of 78%,
<br />Shower heads 612,1 Water flow must be restricted to no more than 2.5 callons oar minute at 80 PSIG.
<br />Air Distribution Systems 610,1 All ducts, fittings, mechanical equipment and plenum chambers shall be mechanically
<br /> I attached, sealed, insulated, and installed in accordance with the criteria of Section 610,
<br /> Ducts in unconditioned attics: R-6 min. insulation,
<br />HVAC Controls 007.1 I Seaarate readilv accessible manual or automatic thermostat for each system. i
<br />Insulation I 004.1, 002.1 I Ceilings-Min, R-19, Cornmon walls-Frame R-11 or CBS R-3 both sides, I
<br /> I Common ceiling & floors R-11,