<br />FORM 600A-97
<br />
<br />Code Compliance Checklist
<br />Residential Whole Building Performance Method A - Details
<br />
<br />I ADDRESS:" ,
<br />6A-21 INFILTRATION REDUCTION COMPLIANCE CHECKLIST
<br />
<br />PERMIT #:
<br />
<br />COMPONENTS SECTION REQUIREMENTS FOR EACH PRACTICE CHECK
<br />Exterior Windows & Doors 606,1 ,ABC, 1,1 Maximum:,3 cfm/sa,ft, window area' ,5 cfm/sa,ft, door area,
<br />Exterior & Adjacent Walls 606,1 ,ABC, 1,2,1 Caulk, gasket, weatherstrip or seal between: windows/doors & frames, surrounding wall;
<br /> foundation & wall sole or sill plate; joints between exterior wall panels at corners; utility
<br /> I penetrations; between wall panels & top/bottom plates; between walls and floor.
<br /> EXCEPTION: Frame walls where a continuous infiltration barrier is installed that extends I
<br /> from and is sealed to the foundation to the too olate, I
<br />Floors 606, 1 ,ABC, 1,2,2 Penetrations/openings >1/8" sealed unless backed by truss or joint members, I
<br /> EXCEPTION: Frame floors where a continuous infiltration barrier is installed that is sealed !
<br /> to the oerimeter oenetrations and seams,
<br />Ceilings 606,1 ,ABC, 1,2,3 Between walls & ceilings; penetrations of ceiling plane of top floor; around shafts, chases,
<br /> soffits, chimneys, cabinets sealed to continuous air barrier; gaps in gyp board & top plate;
<br /> attic access, EXCEPTION: Frame ceilings where a continuous infiltration barrier is
<br /> installed that is sealed at the oerimeter at oenetrations and seams,
<br />Recessed Lighting Fixtures 1606,1 ,ABC, 1,2.4 Type IC rated with no penetrations, sealed; or Type IC or non-IC rated, installed inside a
<br /> I sealed box with 1/2" clearance & 3" from insulation; or Type IC rated with < 2,0 cfm from
<br /> i
<br /> conditioned soace tested,
<br />Multi-storv Houses 606,1 ,ABC, 1,2,5 Air barrier on oerimeter of floor cavity between floors, I
<br /> I
<br />Additional Infiltration reqts 606,1 ,ABC.1 ,3 Exhaust fans vented to outdoors, dampers; combustion space heaters comply with NFPA, i
<br /> have combustion air. I
<br />
<br />6A-22 OTHER PRESCRIPTIVE MEASURES (must be met or exceeded bv all residences.)
<br />COMPONENTS SECTION REQUIREMENTS CHECK
<br />Water Heaters 612,1 Comply with efficiency requirements in Table 6-12, Switch or clearly marked circuit
<br /> , breaker (electric I or cutoff (aasl must be orovided, External or built-in heat trao reauired,
<br /> ,
<br />Swimming Pools & Spas 612,1 Spas & heated pools must have covers (except solar heated), Non-commercial pools
<br /> must have a pump timer. Gas spa & pool heaters must have a minimum thermal
<br /> efficiencv of 78%, i
<br /> I
<br />Shower heads 612,1 Water flow must be restricted to no more than 2,5 aallons oer minute at 80 PSIG, i
<br />Air Distribution Systems 610,1 I All ducts, fittings, mechanical equipment and plenum chambers shall be mechanically I
<br /> attached, sealed, insulated, and installed in accordance with the criteria of Section 610, I
<br /> Ducts in unconditioned attics: R-6 min, insulation, I
<br />HVAC Controls 607,1 Senarate readilv accessible manual or automatic thermostat for each svstem, I
<br />Insulation 604,1, 602,1 Ceilings-Min, R-19, Common walls-Frame R-11 or CBS R-3 both sides, I
<br />I I Common ceiling & floors R-11,
<br />
<br />EnergyGauge ™ DCA Form 600A-97
<br />
<br />EnergyGauge<ID/FlaRES'97 FLRCNA-200
<br />
|